37
ENGLISH
NOTE
MENU DE-
SCRIPTION
DESCRIPTION SETTINGS RAN-
GE
DEFAULT
SC ACS 160
DEFAULT
SC ACS 225
NOTE
IF 6.10.4.1 ON
5.1
Anti-legionella
-
-
-
5.1.1
Anti-legionella
function
on / off
off
off
5.1.2
Anti-legionella
Temp.
60-99°C
70°C
70°C
5.1.3
Anti-legionella
resid. time
1-120min
15min
15min
5.1.4
Anti-legionella
cycle
-
never
never
5.1.5
Anti-legionella
times
-
antileg pe-
riod settings
antileg period
settings
5.1.6
Start manually
yes/no
No
No
5.2
Limescale
protection
-
-
-
5.2.1
Limescale
protection
on / off
off
off
5.3
Setpoint auto
reg.
-
-
-
5.3.1
Setpoint auto
reg.
on / off
off
off
5.4
Sizing protec-
tion
-
-
-
5.4.1
Sizing R1
Daily/weekly/off
off
off
5.4.2
Sizing R2
Daily/weekly/off
off
off
5.4.3
Sizing R3
Daily/weekly/off
off
off
5.4.4
Sizing V1
Daily/weekly/off
off
off
5.4.5
Sizing V2
Daily/weekly/off
off
off
6. SPECIAL
FUNCTIONS
PRIMARY CIR-
CULATION
6.1
v1 signal
-
-
-
6.1.1
Signal type
0-10V/PWV
PWM
PWM
6.1.2
Signal setting
-
MANUAL
MANUAL
6.1.3
Output signal
Normal/inverted
INVERTED
INVERTED
6.1.4
PWM off
0-15%
98%
98%
6.1.5
PWM on
2-50%
87%
87%
6.1.6
PWM max
50-100%
7%
7%
6.1.7
show signal
-
-
-
6.2
V1 speed
-
-
-
6.2.2
Purging type
6-600 s
8 s
8 s
6.2.3
Regulation time
1-15 min
1 min
1 min
6.2.4
MAX speed
15-100%
100%
100%
6.2.5
MIN speed
10-95%
10%
10%
MENU' DE-
SCRIPTION
DESCRIPTION SETTINGS RAN-
GE
DEFAULT
SC ACS 160
DEFAULT
SC ACS 225
6. SPECIAL
FUNCTIONS
6.3
v2 signal
-
-
-
6.3.1
Signal type
0-10V/PWV
0-10V
0-10V
6.3.2
Signal setting
-
MANUAL
MANUAL
6.3.3
Output signal
Normal/Inverted
NORMAL
NORMAL
6.3.4
0-10V off
0.-1.5V
3.5 V
3.5 V
6.3.5
0-10V on
0.0-5.0V
3.5 V
3.5 V
6.3.6
0-10V max
5.0-10.0V
9.5 V
9.5 V
6.3.7
show signal
-
-
-
6.5
V3 signal
-
-
-
6.5.1
Signal setting
-
MANUAL
MANUAL
6.5.2
Output signal
Normal/Inverted
INVERTED
INVERTED
6.5.3
PWM off
0-15%
98%
98%
6.5.4
PWM on
2-50%
87%
87%
6.5.5
PWM max
50-100%
7%
7%
6.5.8
show signal
-
-
-