22
SETUP WIZARD
The first time the controller is switched on, once the lan-
guage and the clock are set, a prompt will appear asking
whether or not the setup wizard is required. The wizard
can be called up again at a later time if needed, from the
special functions menu. The wizard will guide the user
through the basic settings in the correct sequence, pro-
viding a brief description of each parameter displayed.
Pressing “esc” once, the screen returns to the previous
value, so that it is always possible to go back or make
changes. Pressing “esc“ repeatedly, the steps of the se-
lection procedure can be undone one by one, without
confirming the wizard input. Finally, accessing parameter 4.2 and selecting “Manual” mode, the installer can test the
various outputs with the components connected, and verify whether or not the readings from the sensors are reliable. This
done, automatic mode can be re-activated.
b
Observe the indications for individual parameters given on the following pages, and check whether or not further
settings are needed for the particular application.
Setup wizard
The setup wizard can be accessed in menu 6.18. at any time.
1. Set language and time
2. Commissioning help / setup wizard
a) select or
b) skip
The setup wizard guides through the necessary basic settings in the correct order. Jeder Parameter wird im Reglerdis-
play. Pressing the "esc“ key takes you back to the previous setting.
Free programming
With free commissioning the settings should be made in the following order:
- Menu 9. Language
- Menu 3. Operating hours
- Menu 4. Settings, all values
- Menu 5. Protection Functions (if any adjustments necessary).
- Menu 6. Special Functions (if any adjustments necessary).
In menu operating mode "3.2. Manual”, test the switch outputs with the consumers connected and check the sensor
values for plausibility. Then set to automatic mode.
b
Observe the indications for individual parameters given on the following pages, and check whether or not further
settings are needed for the particular application.
CALIBRATION OF TAP SUPPORT
If the tap support is switched on in the circulation menu or in the commissioning assistant, a calibration is automatically
started after the commissioning help, which is repeated once a week (Sunday at 03:00 o' clock) if not tapped. If the week-
ly calibration is not completed successfully after 10 minutes, it will be cancelled automatically and the controller continues
to work with the "old" values. During commissioning, the calibration must not be interrupted.
Calibration procedure:
During the callibration process a text is shown that the flow rate is measured and no tapping is allowed. After confirmation
the circulation pump is switched off and the controller is waiting until the flow rate has dropped to 0 L/min. Afterwards only
the circulation pump is switched on and after another 60 seconds the flow rate is measured. The display shows a “Please
wait” sign. After another minute, the flow rate is measured again, and the two flow rates are compared. Then the control-
ler waits another 60 seconds and then compares the measured values. If the results are identical (+- 1L/min), the result
is saved. This repeats itself until the values match or the process is interrupted by the maximum runtime of 10 minutes.
Setup wizard
Yes
No
esc
Do you want to run the setup
wizard now?