Installation
5.6
Positioning probe - electrode
If, in the previous check, the position of the probe or electrode
was not correct, is necessary:
remove the screw 1)(Fig. 15)
extract the inner part 2)(Fig. 15) of the head, and adjust
them.
WARNING
Before fixing the burner to the boiler, check from
the opening of the blast tube that the probe and
the electrode are correctly positioned, as in
Fig. 16.
WARNING
Do not rotate the probe: leave it as in Fig. 16.
If it is located too close to the ignition electrode,
the control box amplifier may be damaged.
WARNING
Observe the dimensions shown in Fig. 16.
1
2
D8091
Fig. 15
Fig. 16
Probe
Electrode
D10833