Problems - Causes - Remedies signalled by LED indicators
Tab. R
56
UV: false flame during operation False flame detected before ignition
Check the flame sensor
57
FR: false flame during operation False flame detected before ignition
Check the wiring
Check the flame sensor
Make sure that earthing is appropriate
58
T8 inlet fault
The system detected the presence of
voltage on T8 at the wrong moment or there
is no voltage when necessary
Check the wiring
Check the actuator
59
Internal hardware fault
Internal fault
Replace the control device
60
Local reset fault
Local reset button pressed for more than 10
seconds or reset button locked
If the problem persists, replace the control
device
61
Open POC fault
The fuel valve is open at the wrong moment Check the wiring
62
UV: strong UV flame fault
The flame sensor is too close to the flame
Increase the distance between the flame
sensor and the flame OR use an orifice to
reduce the view field
63
Internal hardware fault
Internal fault
Replace the control device
No
Faults
Cause
Solution