9
20152093
GB
Technical description of the burner
4.3
Models available
Tab. B
4.4
Technical data
Tab. C
(1) Reference conditions: Ambient temperature 20°C - Gas temperature 15°C - Barometric pressure 1013 mbar - Altitude 0 m a.s.l.
(2) Pressure at the test point of the pressure switch (Fig. 29 on page 29) with zero pressure in the combustion chamber and at maximum burner output.
(3) Sound pressure measured in manufacturer's combustion laboratory, with burner operating on test boiler and at maximum output.
The sound power is measured using the "Free Field" method, required by the EN 15036 standard, and according to an “Accuracy: Category 3”
measurement, as described in EN ISO 3746.
4.5
Electrical data
Tab. D
Designation
Power supply voltage
Start-up
Code
RS 200/M BLU
TL
3 ~ 230 / 400V - 50Hz
Direct
20145799
Model
RS 200/M BLU
Type
1106T
Output
(1)
Max.
kW
Mcal/h
1380 ÷ 2400
1187 ÷ 2064
Min.
kW
Mcal/h
550
473
Fuel
Natural gas: G20 (methane) G21 - G22 - G23 - G25 - G31
Gas pressure at max. output
(2)
- Gas: G20 / G25 / G31
mbar
28 / 35.6 / 19.6
Operation
–
Intermittent (min. 1 stop in 24 hours)
–
Progressive two-stage or modulating by kit (see ACCESSORIES).
Standard applications
Boilers: water, steam, diathermic oil
Ambient temperature
°C
0 - 40
Combustion air temperature
°C max
60
Noise levels
(3)
Sound pressure
Sound power
dB(A)
80.5
91.5
Model
RS 200/M BLU
Type
1106T
Main electrical supply
Auxiliary circuit electrical supply
3 ~ 400V +/-10% 50Hz
1N ~ 230V +/-10% 50Hz
Fan motor IE3
Hz
rpm
V
kW
A
50
2935
400
5.5
10.2
Ignition transformer
V1 - V2
I1 - I2
230 V - 1 x 8 kV
1 A - 20 mA
Absorbed electric power
kW max
5.9
Protection level
IP 44