13
20095199
GB
Technical description of the burner
Electrical connection of flame detector
It is important for signal transmission to be almost totally free
of any disturbances or loss:
always separate the detector cables from the other cables:
– line capacitance reduces the magnitude of the flame sig-
nal.
– Use a separate cable.
Respect the allowed cable lengths.
The grounding of the burner must be in compliance with the
rules in force; the grounding of the boiler alone is not
enough.
Technical data
Control box
Mains voltage
AC 230 V -15 % / +10 %
Mains frequency
50 / 60 Hz ±6 %
Power absorption
< 30 W (normal)
Safety class
I, with components in compliance with II and III, ac-
cording to DIN EN 60730-1
Load on ‘input’
terminals
F1 unit fuse (internal)
6,3 AT
Main fuse of perm. network (external)
Max. 16 AT
Undervoltage
–
Safety switch-off from operating position to mains
voltage
–
Restart when mains voltage picks up
< AC 186 V
> AC 195 V
Input currents and input voltages
–
UeMax
–
UeMin
–
Iemax
–
IeMin
UN +10%
UN -15%
1.5 mA peak
0.7 mA peak
Voltage detection
–
On
–
Off
AC 180...253 V
< AC 80 V
Load on ‘output’
terminals
Total load on the contacts
–
Mains voltage
–
Total unit input current (safety circuit)
- Fan motor contactor
- Ignition transformer
- Valve
AC 230 V, 50 / 60 Hz
Max. 5 A
Single contact loading
Fan motor contactor
–
Rated voltage
–
Nominal current
–
Power factor
AC 230 V, 50 / 60 Hz
2A
cos
> 0.4
Alarm output
–
Rated voltage
–
Nominal current
–
Power factor
AC 230 V, 50 / 60 Hz
1A
cos
> 0.4
Ignition transformer
–
Rated voltage
–
Nominal current
–
Power factor
AC 230 V, 50 / 60 Hz
2A
cos
> 0.2
Fuel valve
–
Rated voltage
–
Nominal current
–
Power factor
AC 230 V, 50 / 60 Hz
2A
cos
> 0.4
Display operation
–
Rated voltage
–
Nominal current
–
Power factor
AC 230 V, 50 / 60 Hz
0,5A
cos
> 0.4
Summary of Contents for RS 200/EV BLU TL
Page 2: ...Original instructions...
Page 43: ...41 20080730 GB Appendix Electrical panel layout 0 1 1 0 2 0 00 0 1 3 414 56 2 7 8 03 59 3 A...
Page 44: ...20080730 42 GB Appendix Electrical panel layout...
Page 49: ......
Page 50: ......
Page 51: ......