Maintenance
Voltage on the QRI cell
Minimum value for correct operation: 3.5V DC (value on AZL dis-
play at about 50%).
If the value is lower, it could be due to:
–
cell not positioned correctly
–
low voltage (lower than 187V)
–
bad regulation of the burner
In order to measure, use a voltmeter with a 10V DC scale con-
nected as in the diagram (Fig. 34).
Gas leaks
Make sure that there are no gas leaks on the pipe between the
gas meter and the burner.
Gas filter
Change the gas filter when it is dirty.
Combustion
In case the combustion values found at the beginning of the inter-
vention do not respect the standards in force or, in any case, do
not correspond to a proper combustion, contact the Technical As-
sistance Service in order to carry out the necessary adjustments.
Tab. N
7.2.4
Electrical panel
In the event of maintenance/replacement of components in the
lower part of the electrical panel, access is possible via the front
of the panel itself, following the directions below:
unscrew the screws 2) of the control panel 1)(Fig. 35);
extract the control panel 1) and turn it 90°, hooking it with the
brackets 3) in the profile of the electrical panel as shown in
Fig. 35;
after performing the operation, install the control panel 1) in
the electrical panel with the appropriate screws 2), arranging
the cables present.
7.2.5
Safety components
The safety components should be replaced at the end of their life
cycle indicated in the following table.
The specified life cycles do not refer to the warranty terms indi-
cated in the delivery or payment conditions.
Tab. O
EN 676
Air excess
CO
Max. output.
1.2
Max. output.
1.3
GAS
Theoretical max CO
2
0 % O
2
CO
2
% Calibration
mg/kWh
= 1.2
= 1.3
G 20
11.7
9.7
9
100
G 25
11.5
9.5
8.8
100
G 30
14.0
11.6
10.7
100
G 31
13.7
11.4
10.5
100
DANGER
Turn off the burner's power supply using the main
system switch.
WARNING
Failure to install the control panel 1) in the seat of
the electrical panel, results in the machine's loss
of "IP" protection.
Safety component
Life cycle
Flame control
10 years or 250.000
operation cycles
Flame sensor
10 years or 250.000
operation cycles
Gas valves (solenoid)
10 years or 250.000
operation cycles
Pressure switches
10 years or 250.000
operation cycles
Pressure adjuster
15 years
Servomotor (electronic
cam) (if present)
10 years or 250.000
operation cycles
Oil valve (solenoid)
(if present)
10 years or 250.000
operation cycles
Oil regulator (if present)
10 years or 250.000
operation cycles
Oil pipes/ couplings
(metallic)(if present)
10 years
Flexible hoses (if present)
5 years or 30.000
pressurised cycles
Fan impeller
10 years or 500.000 start-ups
0...10 V
Ri > 10 M
:
X10-02 / 6
X10-02 / 4
X10-02 / 2
LMV...
+
D9174
Fig. 34
1
2
1
3
Fig. 35
20094732
Summary of Contents for RS 1300/E C01
Page 2: ...Translation of the original instructions ...
Page 41: ...39 20089387 GB Appendix Electrical panel layout ...
Page 42: ...20089387 40 GB Appendix Electrical panel layout ...
Page 44: ...20089387 42 GB Appendix Electrical panel layout ...
Page 45: ...43 20089387 GB Appendix Electrical panel layout 0 1 1 1 ...
Page 46: ...20089387 44 GB Appendix Electrical panel layout 0 1 0 ...
Page 47: ...45 20089387 GB Appendix Electrical panel layout 0 1 1 1 2 1 3 1 1 1 1 1 1 1 41 4 4 1 1 2 1 ...
Page 48: ...20089387 46 GB Appendix Electrical panel layout 0 0 0 1 0 2 0 0 0 0 0 0 0 30 3 3 0 0 1 0 4 ...
Page 49: ...47 20089387 GB Appendix Electrical panel layout 0 0 1 2 0 0 3 3 3 0 1 4 ...
Page 54: ......
Page 55: ......