![Riello RS 1300/E C01 Installation, Use And Maintenance Instructions Download Page 25](http://html.mh-extra.com/html/riello/rs-1300-e-c01/rs-1300-e-c01_installation-use-and-maintenance-instructions_1459814025.webp)
23
20089387
GB
Installation
Example RS 1300/E C01 FS1 with G20 natural gas:
Operation at maximum modulating output
Gas pressure at test point 1)(Fig. 23)
=
50 mbar
Pressure in combustion chamber
=
10 mbar
50 - 10
=
40 mbar
A pressure of 40 mbar, column 1, corresponds in Tab. J to an out-
put of 12500 kW.
This value serves as a rough guide; the effective output must be
measured at the gas meter.
To calculate the required gas pressure at test point 1) (Fig. 23),
set the maximum modulating output required from the burner op-
eration:
–
find the nearest output value in Tab. J for the burner in ques-
tion.
–
read, on the right (column 1), the pressure at the test point 1)
(Fig. 23).
–
Add this value to the estimated pressure in combustion
chamber.
Example RS 1300/E C01 FS1 with natural gas G20:
Operation at maximum modulating output
Gas pressure at an output of 12500 kW
=
40 mbar
Pressure in combustion chamber
=
10 mbar
40 + 10
=
50 mbar
pressure required at test point 1)(Fig. 23).
5.11.5 Pilot - gas train connection
The burner is fitted with a dedicated gas train that is fixed to the
pipe coupling.
It should be connected to the main train downstream the fil-
ter or the pressure adjuster (depending on configuration).
5.11.6 Ignition pilot burner
For proper operation, adjust gas pressure (measured at pressure
test point 1)(Fig. 24) as follows:
Tab. K
In the case of ignition problems check:
correct positioning of the ignition electrode;
the gas pressure, according to indications.
WARNING
Supply pressure 68 ÷ 500 mbar.
Model
Gas
mbar
Sm
3
/h
RS 1300/E C01 FS1
G20
26
19
RS 1600/E C01 FS1
G20
26
19
RS 2000/E C01 FS1
G20
26
19
WARNING
Check pilot flame stability before starting up the
main burner.
1
2
Fig. 23
20094557
Fig. 24
20094558
Summary of Contents for RS 1300/E C01
Page 2: ...Translation of the original instructions ...
Page 41: ...39 20089387 GB Appendix Electrical panel layout ...
Page 42: ...20089387 40 GB Appendix Electrical panel layout ...
Page 44: ...20089387 42 GB Appendix Electrical panel layout ...
Page 45: ...43 20089387 GB Appendix Electrical panel layout 0 1 1 1 ...
Page 46: ...20089387 44 GB Appendix Electrical panel layout 0 1 0 ...
Page 47: ...45 20089387 GB Appendix Electrical panel layout 0 1 1 1 2 1 3 1 1 1 1 1 1 1 41 4 4 1 1 2 1 ...
Page 48: ...20089387 46 GB Appendix Electrical panel layout 0 0 0 1 0 2 0 0 0 0 0 0 0 30 3 3 0 0 1 0 4 ...
Page 49: ...47 20089387 GB Appendix Electrical panel layout 0 0 1 2 0 0 3 3 3 0 1 4 ...
Page 54: ......
Page 55: ......