![Riello RS 1300/E C01 Installation, Use And Maintenance Instructions Download Page 10](http://html.mh-extra.com/html/riello/rs-1300-e-c01/rs-1300-e-c01_installation-use-and-maintenance-instructions_1459814010.webp)
20089387
8
GB
Technical description of the burner
4.3
Burner categories - Countries of destination
Tab. B
4.4
Technical data
Tab. C
(1)
Reference conditions: Ambient temperature 20°C - Gas temperature 15°C - Barometric pressure 1013 mbar - Altitude 0 m a.s.l.
(2)
Pressure upstream of the gas train P3)(Fig. 18 a page 21) as declared by EN 676, with 0 mbar in the combustion chamber and at maximum burner
output.
(3)
Sound pressure measured in manufacturer's combustion laboratory, with burner operating on test boiler and at maximum rated output.
"The sound power is measured using the "Free Field" method, required by the EN 15036 standard , and according to an “Accuracy: Category 3”
measurement, as described by the EN ISO 3746 Standard.”
4
The burner is factory set for FS1 operation (1 stop every 24 hours); it can be converted to FS2 operation (continuous - 1 stop every 72 hours), by
changing the parameters using the menu of the AZL Display.
4.5
Electrical data
Tab. D
Gas category
Destination country
I
2H
SE - FI - AT - GR - DK - ES - GB - IT - IE - PT - IS - CH - NO
I
2ELL
DE
I
2L
NL
I
2Er
FR
I
2E(R)B
BE
I
2E
LU - PL
Model
RS 1300/E C01 FS1
RS 1600/E C01 FS1
RS 2000/E C01 FS1
Type
S001T1
1601T1
2001T1
Power
(1)
Delivery
(1)
min - max
kW
2500/7500 - 13000
3500/9500 - 16500
4000/12000 - 19500
Fuels
Natural gas: G20 (methane gas) - G21 - G22 - G23 - G25
Gas pressure at max. output
(2)
-
Gas: G20/G25
mbar
43/65
70/104
92/141
Operation
–
Intermittent (min. 1 stop in 24 hours)
(4)
–
Modulating
Standard applications
Boilers: water, steam, diathermic oil
Ambient temperature
°C
0 - 50
Combustion air temperature
°C max
60
Noise levels
(3)
Sound pressure
Sound power
dB(A)
95
106
95
106
95
106
Weight
Kg
950
1000
1050
Model
RS 1300/E C01 FS1
RS 1600/E C01 FS1
RS 2000/E C01 FS1
Main electrical supply
Auxiliary circuit electrical supply
3 ~ 400V 50 Hz
1 ~ 230V 50 Hz
Fan motor IE3
rpm
V
kW
A
2960
400/690
30
51.6/29.8
2965
400/690
37
63.4/36.6
2965
400/690
45
76/43.9
Ignition transformer
V1 - V2
I1 - I2
230V - 1 x 8 kV
1A - 20mA
Absorbed electrical power
kW max
32
39
47
Protection level
IP 55
Summary of Contents for RS 1300/E C01
Page 2: ...Translation of the original instructions ...
Page 41: ...39 20089387 GB Appendix Electrical panel layout ...
Page 42: ...20089387 40 GB Appendix Electrical panel layout ...
Page 44: ...20089387 42 GB Appendix Electrical panel layout ...
Page 45: ...43 20089387 GB Appendix Electrical panel layout 0 1 1 1 ...
Page 46: ...20089387 44 GB Appendix Electrical panel layout 0 1 0 ...
Page 47: ...45 20089387 GB Appendix Electrical panel layout 0 1 1 1 2 1 3 1 1 1 1 1 1 1 41 4 4 1 1 2 1 ...
Page 48: ...20089387 46 GB Appendix Electrical panel layout 0 0 0 1 0 2 0 0 0 0 0 0 0 30 3 3 0 0 1 0 4 ...
Page 49: ...47 20089387 GB Appendix Electrical panel layout 0 0 1 2 0 0 3 3 3 0 1 4 ...
Page 54: ......
Page 55: ......