Installation
5.11.2 Gas train
Approved according to standard EN 676 and provided separately
from the burner.
5.11.3 Gas train installation
The gas train is prearranged to be connected to the burner by the
flange 1) (Fig. 22).
5.11.4 Gas pressure
Tab. J indicates the pressure drops of the combustion head and
gas butterfly valve, on the basis of the burner operating output.
The values shown in Tab. J refer to:
–
Natural gas G 20 NCV 9.45 kWh/Sm
3
(8.2 Mcal/Sm
3
)
–
Natural gas G 25 NCV 8.13 kWh/Sm
3
(7.0 Mcal/Sm
3
)
Tab. J
Column 1
Combustion head pressure drop.
Gas pressure measured at test point 1)(Fig. 23), with:
•
combustion chamber at 0 mbar;
•
burner working at maximum modulating output;
•
combustion head set as on page 21.
Column 2
Pressure loss at gas butterfly valve 2)(Fig. 23) with maximum
opening: 90°.
To calculate the approximate output at which the burner oper-
ates:
–
subtract the pressure in combustion chamber from the gas
pressure measured at test point 1) (Fig. 23).
–
Find, in Tab. J related to the burner concerned, the pressure
value closest to the result of the subtraction.
–
Read off the corresponding output on the left.
DANGER
Disconnect the electrical power using the main
switch.
Check that there are no gas leaks.
Pay attention when handling the train: danger of
crushing of limbs.
Make sure that the gas train is properly installed
by checking for any fuel leaks.
The operator must use the required equipment
during installation.
1
Fig. 22
20094555
kW
1
p (mbar)
2
p (mbar)
G 20
G 25
G 20
G 25
RS 13
00/E
2500
1.6
2.4
0.2
0.3
3500
3.1
4.7
0.4
0.6
4500
5.1
7.8
0.7
1
5500
7.7
11.6
1
1.5
6500
10.7
16.2
1.5
2.1
7500
14.3
21.6
1.9
2.8
8500
18.4
27.8
2.5
3.6
9500
23
34.7
3.1
4.5
10500
28
42.4
3.8
5.5
11500
33.6
50,8
4.6
6.6
12500
40
60,1
5.5
7.8
13000
43
65
5.9
8.5
RS 1600
/E
3500
3.1
4.6
0.4
0.6
5000
6.4
9.5
0.8
1.2
6500
10.8
16.1
1.5
2.1
8000
16.5
24.4
2.2
3.2
9500
23.2
34.5
3.1
4.5
11000
31.1
46.2
4.2
6
12500
40.2
59.6
5.5
7.8
14000
50.4
74.8
6.8
9.8
15500
61.7
91.7
8.4
12
16500
70
104
9.5
13.6
R
S
20
00/E
4000
3.8
6
0.5
0.8
5500
7.3
11.2
1
1.5
7000
12
18.2
1.7
2.5
8500
17.5
26.8
2.5
3.6
10000
24.2
37
3.5
5
11500
32
49
4.6
6.6
13000
4.1
62.6
6
8.5
14500
5.1
78
7.3
10.5
16000
62
95
9
12.8
17500
74
113.5
10.7
15.3
19000
83
13.4
12.6
18
19500
92
141
13.3
19
Summary of Contents for RS 1300/E C01
Page 2: ...Translation of the original instructions ...
Page 41: ...39 20089387 GB Appendix Electrical panel layout ...
Page 42: ...20089387 40 GB Appendix Electrical panel layout ...
Page 44: ...20089387 42 GB Appendix Electrical panel layout ...
Page 45: ...43 20089387 GB Appendix Electrical panel layout 0 1 1 1 ...
Page 46: ...20089387 44 GB Appendix Electrical panel layout 0 1 0 ...
Page 47: ...45 20089387 GB Appendix Electrical panel layout 0 1 1 1 2 1 3 1 1 1 1 1 1 1 41 4 4 1 1 2 1 ...
Page 48: ...20089387 46 GB Appendix Electrical panel layout 0 0 0 1 0 2 0 0 0 0 0 0 0 30 3 3 0 0 1 0 4 ...
Page 49: ...47 20089387 GB Appendix Electrical panel layout 0 0 1 2 0 0 3 3 3 0 1 4 ...
Page 54: ......
Page 55: ......