20148124
28
GB
Start-up, calibration and operation of the burner
6.1
Notes on safety for the first start-up
6.2
Burner adjustment
It is recommended to adjust first the light oil burner and then the
gas burner.
The optimum calibration of the burner requires an analysis of the
flue gases at the boiler outlet and interventions on the following
points.
•
Nozzles
See information on page 18.
•
Combustion head
The adjustment of the head that has already been carried out
as on page 19 does not require any modifications unless the
burner output in the 2nd stage is changed.
•
Pump pressure:
In order to change pump pressure, act on screw 5) (Fig. 22).
See information on page 18.
•
Fan damper
See servomotor adjustment on. page 32
6.3
Adjustments prior to ignition
Combustion head adjustment is already described on page 19.
In addition, the following adjustments must also be made:
–
Slowly open the manual valves situated upstream of the gas
train.
–
Adjust the minimum gas pressure switch to the start of the
scale.
–
Adjust the maximum gas pressure switch to the end of the
scale.
–
Adjust the air pressure switch to the start of the scale.
–
Purge the air from the gas line.
We recommend using a plastic tube routed outside the
building and to purge air until gas is smelt.
–
Fit a U-type pressure gauge or a differential pressure gauge
(Fig. 33), with socket (+) on the gas pressure of the pipe
coupling and (-) in the combustion chamber.
Used to derive the approximate MAX output of the burner
using the table on page 24.
–
Connect two lamps or testers to the two gas line solenoid
valves to check the exact moment in which voltage is
supplied. This operation is not required if each of the two
solenoid valves is equipped with a pilot light that signals
voltage passing through.
6
Start-up, calibration and operation of the burner
ATTENTION
The first start-up of the burner must be carried out
by qualified personnel, as indicated in this manual
and in compliance with the standards and
regulations of the laws in force.
ATTENTION
Check the correct working of the adjustment,
command and safety devices.
ATTENTION
Before starting up the burner, refer to section
“Safety test - with no gas supply” on page 36.
ATTENTION
Carry out the fuel change with burner off.
CAUTION
Before starting up the burner, it is good practice to
adjust the gas train so that ignition takes place in
conditions of maximum safety, i.e. with gas
delivery at the minimum.
+
D8367
Fig. 33
Summary of Contents for RLS 800/M MX
Page 2: ...Translation of the original instructions ...
Page 52: ...20148124 50 GB Appendix Electrical panel layout ...
Page 53: ...51 20148124 GB Appendix Electrical panel layout 0 1 1 1 ...
Page 55: ...53 20148124 GB Appendix Electrical panel layout 0 1 2 2 2 0 ...
Page 56: ...20148124 54 GB Appendix Electrical panel layout 0 1 1 1 2 3 45678 9 55 ...
Page 62: ......
Page 63: ......