37
20148124
GB
Maintenance
Check Mode
With burner flame on:
hold the reset button on the flame control pressed for at
least 3 sec.;
the button colour will change from green to yellow;
each operating status signalling LED will be compared to
20% of the maximum brightness;
press the reset button again (<0.5sec) to reset the standard
operation of the signalling LEDs.
7.2.4
Safety components
The safety components should be replaced at the end of their life
cycle indicated in the following table.
Tab. N
ATTENTION
The specified life cycles do not refer to the
warranty terms indicated in the delivery or
payment conditions.
Safety component
Life cycle
Flame control
10 years or 250.000
operation cycles
Flame sensor
10 years or 250.000
operation cycles
Gas valves (solenoid)
10 years or 250.000
operation cycles
Pressure switches
10 years or 250.000
operation cycles
Pressure adjuster
15 years
Servomotor (electronic
cam)(if any)
10 years or 250.000
operation cycles
Oil valve (solenoid)(if any)
10 years or 250.000
operation cycles
Oil regulator (if present)
10 years or 250.000
operation cycles
Oil pipes/ couplings
(metallic) (if present)
10 years
Flexible hoses (if present)
5 years or 30,000 pressurised
cycles
Fan impeller
10 years or 500.000 start-ups
Summary of Contents for RLS 800/M MX
Page 2: ...Translation of the original instructions ...
Page 52: ...20148124 50 GB Appendix Electrical panel layout ...
Page 53: ...51 20148124 GB Appendix Electrical panel layout 0 1 1 1 ...
Page 55: ...53 20148124 GB Appendix Electrical panel layout 0 1 2 2 2 0 ...
Page 56: ...20148124 54 GB Appendix Electrical panel layout 0 1 1 1 2 3 45678 9 55 ...
Page 62: ......
Page 63: ......