39
20148124
GB
Maintenance
7.3
Opening the burner
Remove the tie-rods 1) and 6)(Fig. 45) of the lever for
moving the head and opening the dampers, loosening the
nuts 2).
Disconnect the socket 3) of the servomotor.
Disconnect the socket 7) of the derivation unit.
Disconnect the socket 4) of the gas pressure switch.
Remove the screws 5).
At this point, it is possible to open the burner on the hinge.
7.4
Closing the burner
Refit following the steps described but in reverse order; refit all
burner components as they were originally assembled.
DANGER
Disconnect the electrical supply from the burner
by means of the system main switch.
DANGER
Close the fuel shut-off valve.
Wait for the components in contact with heat
sources to cool down completely.
5
5
1
2 6
5
5
7
3
4
D10721
Fig. 45
After carrying out maintenance, cleaning or
checking operations, reassemble the cover and
all the safety and protection devices of the burner.
Summary of Contents for RLS 800/M MX
Page 2: ...Translation of the original instructions ...
Page 52: ...20148124 50 GB Appendix Electrical panel layout ...
Page 53: ...51 20148124 GB Appendix Electrical panel layout 0 1 1 1 ...
Page 55: ...53 20148124 GB Appendix Electrical panel layout 0 1 2 2 2 0 ...
Page 56: ...20148124 54 GB Appendix Electrical panel layout 0 1 1 1 2 3 45678 9 55 ...
Page 62: ......