20182250
10
GB
Technical description of the burner
4.8
Firing rates
The
MAXIMUM OUTPUT
is chosen from within the diagram area
(Fig. 3).
The
MINIMUM OUTPUT
must not be lower than the minimum
limit of the diagram:
Model
kW
RLS 310
600
RLS 410
640
RLS 510
660
RLS 610 Gas
1000
RLS 610 Light oil
1300
WARNING
The firing rate value (Fig. 3) has been obtained
considering an ambient temperature of 20 °C, an
atmospheric pressure of 1013 mbar (approx. 0 m
a.s.l.), and with the combustion head adjusted as
shown on page 24.
WARNING
Pre-calibration of the combustion head only for
the burner model RLS 310/M MX:
If the maximum burner output of the burner falls
within:
- area A of the firing rate, it is necessary to replace
the gas nozzles with those supplied (No. 8 gas
nozzles Ø 5,3), Fig. 17 on page 23.
- area B of the firing rate, no modifications are re-
quired.
Fig. 3
Pr
essure in
combu
stio
n hea
d
-
mbar
20096600
Pressure in
co
mb
usti
on hea
d -
mbar
Thermal power –
kW
Thermal power –
kW
RLS 310/M MX
RLS 410/M MX
RLS
510
/M M
X
Fi
ri
ng
r
ate
lig
h
t
oi
l - RLS 610
/M MX
RLS
61
0/M
M
X
Summary of Contents for RLS 310/EV O2 MX
Page 2: ...Translation of the original instructions ...
Page 52: ...20182250 50 GB Appendix Electrical panel layout 0 0 0 0 0 0 0 0 ...
Page 55: ...53 20182250 GB Appendix Electrical panel layout 0 ...
Page 56: ...20182250 54 GB Appendix Electrical panel layout ...
Page 57: ...55 20182250 GB Appendix Electrical panel layout 0 0 1 2 0 0 0 1 0 ...
Page 58: ...20182250 56 GB Appendix Electrical panel layout 0 0 0 1 0 2 0 0 0 0 0 0 0 30 3 3 0 0 1 0 ...
Page 66: ......
Page 67: ......