Start-up, calibration and operation of the burner
6.9
Operation sequence of the burner
6.9.1
Burner starting
Key to layout
(Fig. 40 - Fig. 41)
MV - Fan motor
MP - Pump motor
SM - Servomotor
TA - Ignition transformer
TL - Limit pressure switch/thermostat
TR - Control pressure switch/thermostat or output regulator
Y
- Light oil/gas valve
6.9.2
Undesired shut-down during operation
If the flame should accidentally go out during operation, the burn-
er will lock out within 1s.
To check the full operating programme, refer to the LMV instru-
ment reference handbook, supplied during the technical service
training.
6.10
Final checks (with the burner working)
Open the thermostat/pressure switch TL:
Open the thermostat/pressure switch TS:
the burner must stop.
Rotate the maximum gas pressure switch knob to the mini-
mum end-of-scale position.
Rotate the air pressure switch knob to the maximum end-of-
scale position.
the burner must stop in lockout.
Switch off the burner and disconnect the voltage.
Disconnect the minimum gas pressure switch connector.
the burner must not start
Disconnect the QRI cell wire.
the burner must stop in lockout due to firing failure
Make sure that the mechanical locking systems on the differ-
ent adjustment devices are fully tightened.
Fig. 40
D9200
NORMAL FIRING
Fig. 41
D9201
NO FIRING
Summary of Contents for RLS 300/E MX
Page 2: ......
Page 47: ...45 20009654 GB Appendix Electrical panel layout ...
Page 48: ...20009654 46 GB Appendix Electrical panel layout ...
Page 50: ...20009654 48 GB Appendix Electrical panel layout ...
Page 51: ...49 20009654 GB Appendix Electrical panel layout 0 1 1 1 ...
Page 52: ...20009654 50 GB Appendix Electrical panel layout 0 1 0 ...
Page 53: ...51 20009654 GB Appendix Electrical panel layout 0 0 0 1 0 2 0 0 0 0 0 0 0 30 3 3 0 0 1 0 ...