20009654
20
GB
Installation
5.9
Nozzle installation
The burner complies with the emission requirements of the
EN 267 standard.
In order to guarantee that emissions do not vary, recommended
and/or alternative nozzles specified by Riello in the Instruction
and warning booklet should be used.
Fit the nozzle with the box spanner, fitting the spanner through
the central hole in the flame stability disk (Fig. 14).
Nozzles with no fuel shutoff needle must be fitted on the nozzle
holder.
To set the delivery range within which the nozzle must work, noz-
zle return line fuel pressure must be adjusted according to
Tab. G and Tab. H (pag. 20).
5.9.1
Recommended nozzles
Intermediate flow rates may be obtained by choosing the nozzle
with a nominal flow rate slightly higher than that actually required.
Complete range of nozzles:
Bergonzo type B5 60°:
150 - 200 - 225 - 250 - 275 - 300 -
325 - 350 - 375 - 400 - 425. We normally recommend 60°
angles of pulverisation.
Tab. G
Fluidics type N2 50°:
160 - 180 - 200 - 225 - 250 - 275 - 300
- 330 - 360 - 400 - 450. We normally recommend 50° angles
of pulverisation.
Tab. H
WARNING
It is advisable to replace nozzles every year
during regular maintenance operations.
CAUTION
The use of nozzles other than those specified
by Riello S.p.A. and inadequate regular main-
tenance may result into emission limits non-
conforming to the values set forth by the reg-
ulations in force, and in extremely serious cas-
es, into potential hazards to people and
objects.
The manufacturing company shall not be lia-
ble for any such damage arising from nonob-
servance of the requirements contained in this
manual.
WARNING
Do not use any sealing products such as gas-
kets, sealing compound, or tape.
Be careful to avoid damaging the nozzle seal-
ing seat.
The nozzles must be screwed into place
tightly but not to the maximum torque value
provided by the wrench.
2
D3509
Fig. 14
Model
Nozzles
RLS 300-400/E MX
–
Bergonzo
type B5 60°
–
Fluidics
type N2 50°
RLS 500/E MX
–
Fluidics
type N2 50°
kg/h
Delivery
pressure
bar
Return
pressure
bar
kg/h
kW
RLS 300
-400/E MX
150
21
13
51
600
21
19
106
1250
200
22
8.5
67
800
22
17.5
150
1800
300
20
7
100
1200
20
17.5
257
3000
375
20
6.5
148
1750
20
15.5
305
3600
425
20
7.5
68
1950
20
17.5
365
4300
kg/h
Delivery
pressure
bar
Return
pressure
bar
kg/h
kW
RL
S 500/E MX
250
24
9
94
1120
25
15.5
210
2500
360
24
7.5
116
1380
25
14
260
3090
400
24
8.5
153
1820
25
15
355
4220
450
24
8
164
1950
25.5
16
425
5050
RL
S 3
00-40
0/E
MX
200
23
9.5
67
800
23
15
150
1800
250
24
9
94
1120
25
15.5
210
2500
360
24
7.5
116
1380
25
14
260
3090
400
24
8.5
153
1820
25
16.5
365
4300
Summary of Contents for RLS 300/E MX
Page 2: ......
Page 47: ...45 20009654 GB Appendix Electrical panel layout ...
Page 48: ...20009654 46 GB Appendix Electrical panel layout ...
Page 50: ...20009654 48 GB Appendix Electrical panel layout ...
Page 51: ...49 20009654 GB Appendix Electrical panel layout 0 1 1 1 ...
Page 52: ...20009654 50 GB Appendix Electrical panel layout 0 1 0 ...
Page 53: ...51 20009654 GB Appendix Electrical panel layout 0 0 0 1 0 2 0 0 0 0 0 0 0 30 3 3 0 0 1 0 ...