21
20009654
GB
Installation
5.10
Position of electrodes
5.11
Combustion head setting
In addition to varying air flow depending on the output requested,
the air gate valve servomotor 4) (Fig. 4) by means of a lifting as-
sembly - varies the setting of the combustion head.
This system allows an optimal setting even at a minimum firing
rate.
For the same servomotor rotation, combustion head opening can
be varied by moving the tie rod onto holes 1-2-3)(Fig. 16).
The choice of the hole (1-2-3) to be used is decided on the basis
of diagram (Fig. 17) against the required maximum output.
Setting is pre-arranged in the plant for the maximum run (hole 3,
Fig. 16).
WARNING
Make sure that the electrodes are positioned as
shown in (Fig. 15).
Fig. 15
mm
4 - 4 , 5
6
-
10 m
m
D3510
0
1
2
3
4
6
3
2
1
4
D3093
Fig. 16
1200
1600
2000
2400
2800
3200
3600
4000
4400
3
2
1
0
800
600
Fig. 17
D9222
RLS 300/E MX
RLS 400/E MX
3
2
1
0
2400 2800 3200 3600 4000 4400 4800 5200
1200 1600 2000
800
D8900
N° holes
Max burner output -
kW
RLS 500/E MX
N° holes
Max burner output -
kW
Summary of Contents for RLS 300/E MX
Page 2: ......
Page 47: ...45 20009654 GB Appendix Electrical panel layout ...
Page 48: ...20009654 46 GB Appendix Electrical panel layout ...
Page 50: ...20009654 48 GB Appendix Electrical panel layout ...
Page 51: ...49 20009654 GB Appendix Electrical panel layout 0 1 1 1 ...
Page 52: ...20009654 50 GB Appendix Electrical panel layout 0 1 0 ...
Page 53: ...51 20009654 GB Appendix Electrical panel layout 0 0 0 1 0 2 0 0 0 0 0 0 0 30 3 3 0 0 1 0 ...