COMMISSIONING AND MAINTENANCE
21
3
COMMISSIONING AND MAINTENANCE
3.1 Preparation for first commissioning
Prior to commissioning, it is necessary to check that:
—
all the safety conditions have been met
—
all distances have been respected
—
the electrical connections have been properly completed
—
the electrical power supply's values are correct
—
the earthing has been carried out correctly
—
all the connections have been properly tightened
Microswitch setting
On the main electronic board there are microswitches to man-
age some functions.
factory settings
Model
SW2
1
2
3
4
25
OFF
ON
OFF
OFF
35
OFF
ON
OFF
ON
50
OFF
ON
OFF
OFF
70
OFF
ON
OFF
ON
SW2_1
It selects the transmission channel between the unit and the
remote control.
Selectable options are:
OFF = channel “A” (factory setting)
ON = channel “b”
9
The channel must be the same for the unit and the remote
control.
9
Do not change such setting to prevent communication in-
terruptions with the remote control.
SW2_2
It enables and disables the roomcard function:
ON = enabled (factory setting).
—
if contact CN51 is open, the unit switches off and cannot be
activated via external control
—
if contact CN51 is closed, the unit can be activated via ex-
ternal control
OFF = disabled.
—
if contact CN51 is open, the unit switches off, but it can be
activated via external control
—
if contact CN51 is closed, the unit activates automatically
9
Contact CN51 is bridged by factory default.
SW2_3 e SW2_4
9
Do not change factory setting
Purifying filter installation
Air purifying filters to absorb microscopic dust particles, pollen,
moulds or polluting agents are supplied with the device:
—
no. 1 antibacterial filter (green)
—
no. 1 photocatalytic filter (black)
9
The device is designed to be installed with two purifying
filters. Chose among the ones supplied according to your
needs.
For the installation:
1 Mesh filters
1
—
open the front panel
—
take out the mesh filter by grabbing the relevant fins
1 Mesh filters
2 Air purifying filter
2
1
—
insert the purifying filters into the prearranged slots
—
to reposition them, proceed in reverse order
9
Keep the purifying filters sealed until their actual use.
9
Installing the purifying filters reduces the air flow and re-
sults in lower performance. It is advised to use the device at
the highest speeds.
Time setting
The current time must be set before using the remote control:
Summary of Contents for R32 Series