background image

18

NexPro

 

-

In heat pump mode the following signals are enabled:

 

-

if the temperature measured by the probe 

S1

 is lower 

than the set point, but the delays set with the 

H20

 and 

H21

 parameters are active, the two-coloured led 

L1

 will 

flash green

 

-

if the heat pump is active and the temperature meas-

ured by the probe 

S1

 is lower than the set point, the 

two-coloured led 

L1

 will be fixed green

 

-

if the set point has been reached or exceeded, the bi-
colour led 

L1

 will be off.

 Switching 

ON/OFF

 of the heat pump must comply with 

the safety times set by the user.

"

-

Timing OFF-ON:

 the time between shut-down and the 

subsequent start of the heat pump shall comply with a 
safety time 

H20 (default 900 sec

.) 

 

-

This time is active at power on of the unit.

"

-

Timing ON-ON:

 the time between switching on and the 

subsequent start of the heat pump shall comply with a 
safety time 

H21 (default 1000 sec

.).

If the outside air temperature, measured by the probe 

S2

,

falls to values lower than 

H05

, the production of domestic 

hot water takes place only using the heater (or boiler, see 

boiler integration section), while the heat pump is forced 

to shut down.

The latter is reactivated (with the electric heater/boiler 

switching off as a result) after 20 min.

  Electrical heater and boiler can’t be activated at the 

same time, as it is not possible to activate both the 

electrical heater and the heat pump or Boiler and 

heat pump.

2.10 Manual mode (electrical heater / 

boiler)

The manual mode is selected using the 

Mode A/M

key. (two-

coloured (led 

L2

 on and red).

In manual mode, only the electrical heater is active (or 

boiler depending the selection made on the value of pa-

rameter H50), while the heat pump is disabled.

Integration with electrical heater

If the parameter H50=1 the electric heater is active. 

The adjustment follows the parameters 

Ut2

 (Manual Set 

point) and 

H28

 (differential).

The activation of the heater is indicated by the led 

L4

 in 

fixed mode, whereas when the set point has been reached, 

the led 

L4

 is off.

The electrical heater is wired in the unit, to terminals FR-

NR and is equipped with a safety thermostat set to 95 °C.

The status of the heater is shown in the synoptic branch at 

parameter r2 (1 = ON; 0= off).

Integration with Boiler

If the parameter H50=2 the external boiler is active. This is 

possible in the

Nex Pro C and Nex Pro CS

 models, where it is 

possible to activate an external boiler as an alternative to 

the electric heater.

For this purpose, the unit has a digital output (clean con-

tact) available on the basic board between the INT-GND 

terminals, enabled for activation of a boiler, according to 

the following schematic: the status of the boiler is shown 

in the synoptic branch at parameter r7 (1 = ON; 0 = OFF). 

The adjustment follows the parameters Ut2 (manual set 

point) and H28 (differential), just as for the electric heater.

The activation of the boiler is indicated by the led L5 com-

ing on in fixed mode. Once the set point has been reached 

the led L5 will switch off

 

-

In der Betriebsart Wärmepumpe erscheinen folgende 
Anzeigen:

 

-

Liegt die vom Fühler 

S1

 gemessene Temperatur unter dem 

Sollwert, es sind jedoch die über die Parameter 

H20 

und 

H21

 eingestellten Verzögerungen aktiv, blinkt die zweifar-

bige LED 

L1

 grün

 

-

Ist die Wärmepumpe aktiv und liegt die vom Fühler 

S1

 

gemessene Temperatur unter dem Sollwert, leuchtet die 
zweifarbige LED 

L1

 

dauerhaft grün

 

-

Ist der Sollwert erreicht oder wird er überschritten, 
bleibt die zweifarbige LED 

L1

 ausgeschaltet.

  Die Ein- und Ausschaltungen der Wärmepumpe unter-

liegen Sicherheitszeiten, die vom Anwender eingestellt 

werden können.

"

-

Zeitschaltung AUS-EIN:

 Zwischen dem Ausschalten und 

dem nachfolgenden Einschalten der Wärmepumpe muss 
eine Sicherheitszeit 

H20 (Standard 900 Sek

.) eingehalten 

werden 

 

-

Dieser Zeitraum wird auch beim Einschalten des Reglers 
eingehalten.

"

-

Zeitschaltung EIN-EIN:

 Zwischen zwei Einschaltungen der 

Wärmepumpe muss eine Sicherheitszeit 

H21 (Standard 

1000 Sek

.) eingehalten werden.

Wenn die vom Fühler 

S2

 gemessene Außentemperatur

unter den Wert 

H05

 sinkt, erfolgt die Brauchwarmwasser-

aufbereitung nur durch den Widerstand (oder Kessel, siehe 

Absatz Integrierter Kessel) und die Wärmepumpe wird aus-

geschaltet.

Letztere wird wieder nach Ablauf einer Zeit von 20 Min. aktiviert 

(was das Ausschalten des Widerstands/Kessels zur Folge hat).

  Widerstand und Kessel und Wärmepumpe können in 

keinem Fall gleichzeitig aktiviert werden, ebensowenig 

ist es möglich gleichzeitig Widerstand und Wärmepum-

pe oder Kessel und Wärmepumpe zu aktivieren.

2.10 Manuelle Betriebsweise (Wider-

stand/Kessel)

Die manuelle Betriebsweise wird mittels der Taste 

Mode A/M

 

eingeschaltet. (zweifarbige LED 

L2

 leuchtet rot).

Im manuellen Betrieb ist nur der elektrische Widerstand 

(oder Kessel entsprechend der bei Parameter H50 getroffe-

nen Auswahl) aktiv, während die Wärmepumpe ausgeschal-

tet bleibt.

Integrierter Widerstand

Wenn der Parameter H50=1, ist der elektrische Widerstand aktiv. 

Die Einstellung richtet sich nach den Parameter 

Ut2

 (Sollwert 

manuell) und 

H28

 (Differential).

Die Aktivierung des Widerstands wird durch das dauerhafte 

Aufleuchten der LED 

L4

 angezeigt, während sich bei Errei-

chung des Sollwerts die LED 

L4

 ausschaltet.

Der Widerstand ist bereits im Gerät an die Klemmen FR-NR 

angeschlossen und mit einem auf 95°C geeichten Sicher-

heitsthermostat ausgestattet.

Der Zustand des Widerstandes ist im Menübereich Übersicht bei 

Parameter r2 ersichtlich (1=eingeschaltet; 0=ausgeschaltet).

Integrierter Kessel

Wenn der Parameter H50=2, ist der externe Kessel aktiv. Dies 

ist bei den Modellen 

Nex Pro C und Nex Pro CS

 möglich, bei 

denen als Alternative zum elektrischen Widerstand ein ex-

terner Kessel aktiviert werden kann.

Zu diesem Zweck sieht die Basisplatine des Geräts einen Di-

gitalausgang (potentialfreier Kontakt) zwischen den Klem-

men INT-GND vor, der bei Aktivierung eines Kessels laut fol-

gendem Plan aktiviert wird: Der Zustand des Kessels ist im 

Menübereich Übersicht bei Parameter r7 ersichtlich (1=ein-

geschaltet; 0=ausgeschaltet). Die Einstellung richtet sich 

nach den Parameter Ut2 (Sollwert manuell) und H28 (Diffe-

rential), wie beim elektrischen Widerstand.

Die Aktivierung des Kessels wird durch das dauerhafte Auf-

leuchten der LED L5 angezeigt. Bei Erreichung des Sollwertes 

schaltet sich die LED L5 aus

Summary of Contents for NexPro 300

Page 1: ...rb 1 05 2016 NexPro EN HEAT PUMP FOR DOMESTIC HOT WATER INSTRUCTIONS FOR THE INSTALLER AND FOR THE TECHNICAL ASSISTANCE CENTRE DE W RMEPUMPE F R BRAUCHWARMWASSERAUFBEREITUNG BEDIENUNGSANLEITUNG F R DE...

Page 2: ...chmals vielen Dank Riello S p A HEAT PUMP FOR DOMESTIC HOT WATER W RMEPUMPE F R BRAUCHWARMWASSERAUFBEREITUNG MODEL CODE Nex Pro 20035655 Nex Pro C 20035656 Nex Pro CS 20035657 MODELL CODE Nex Pro 2003...

Page 3: ...10 2 1 1 Verpackung 10 2 1 2 Handling und Transport 10 2 1 3 Kontrolle bei bernahme der Lieferung 10 2 1 4 Lagerung 11 2 2 Installation und Inbetriebnahme 11 2 2 1 Begriffsbestimmungen 11 2 3 Sicherhe...

Page 4: ...n We remind you that the use of products that employ elec trical energy and water requires that a number of essen tial safety rules be followed including This appliance must not be used by children an...

Page 5: ...gas f rmigen Gemischen und oder festen Partikeln verun reinigt ist Der Einsatz des Ger ts f r andere als die vorgesehenen Zwecke die nicht mit den Beschreibungen in diesem Handbuch bereinstimmen f hr...

Page 6: ...eit der Au en luft neue umweltfreundliche W rme zu entziehen Es k nnen auch zus tzliche Energiequellen verwendet wer den indem W rmetauscher an Heizkessel oder Solarzellen angeschlossen werden Das Sta...

Page 7: ...ree energy sources model NEX PRO CS Modulierende Einstellung des L fters entsprechend der Luft und Wassertemperatur Funktion Dynamischer Sollwert Regelung der Mindestintervalle zwischen aufeinander fo...

Page 8: ...ahresverbrauch AEC 5 kWh 826 Daily consumption QELEC 5 Tagesverbrauch QELEC 5 Wh 4000 Maximum power input Maximale Stromaufnahme A 6 5 Refrigerant K ltemittel type Typ R134A Refrigerant charge K ltemi...

Page 9: ...60 160 160 mm 660 660 660 Transport weight Transportgewicht kg 122 137 155 POSITION POSITION DESCRIPTION BESCHREIBUNG 1 Hot water Warmwasser M 1 2 Boiler delivery Kesselvorlauf M 1 3 Probe well F hler...

Page 10: ...igneten Material umwickelt das erst bei der Mon tage abgenommen werden darf 2 1 2 Handling und Transport F r das Handling sind je nach Gewicht geeignete Mittel zu verwenden wie in der letztg ltigen Fa...

Page 11: ...von Vibrations und W rmequellen gehalten werden Die Herstellerfirma haftet nicht f r Sch den durch un sachgem e Entladung oder mangelnden Schutz f r Witterungseinfl ssen 2 2 Installation und Inbetrieb...

Page 12: ...baren Parameter Bearbeitung der Alarmsituationen Kontrolle der Betriebsmittel 2 6 Benutzerschnittstelle Zeichenerkl rung Abb 5 1 Display 2 Key UP 3 Key DOWN 4 Key SET 5 Key ON OFF 6 Key activation ant...

Page 13: ...e total operation hours KEY SET Allows to View the parameters list View the selected parameter Confirm the modification of the parameter KEY ANTIBACTERIAL TREATMENT Push the key to activate the antiba...

Page 14: ...GND INT POWER SUPPLY BASIC BOARD BASISPLATINE THERMOSTAT LOW PRESSURE ELEKTRONISCHE ANODE OPTIONAL EIN AUS BER TIMER BOILER ENABLING EING NGE AUSG NGE ON OFF WITH CONTACTOR 3mF COMPRESSOR P FAN S C R...

Page 15: ...tion enabling r3 NC FC compressor ignition enabling r1 DIGITAL OUTPUTS INT GND volt free contact for boiler enabling r7 DER DIGITALEING NGE ZUSTAND Hp GND hoher Druck ID1 Bp GND niedriger Druck nur Vo...

Page 16: ...t to the right of the display being on and fixed To exit from displaying mode press and hold the SET key or wait 60 seconds since the last release of UP DOWN or SET keys 2 8 Betriebslogik 2 8 1 Einste...

Page 17: ...i Ger te Luft Wasser W rmepumpe und elektrischer Wider stand erfolgt steuert der mit zwei F hlern einem Was sertemperaturf hler S1 und einem Lufttemperaturf hler S2 ausgestattete Regler das Anlaufen d...

Page 18: ...die vom F hler S1 gemessene Temperatur unter dem Sollwert es sind jedoch die ber die Parameter H20 und H21 eingestellten Verz gerungen aktiv blinkt die zweifar bige LED L1 gr n Ist die W rmepumpe akti...

Page 19: ...to force the antibacterial treatment at any time 2 11 Betriebsweise zyklische antibak terielle Behandlung Die zyklische antibakterielle Behandlung wird ber die Taste Zyklus ausgew hlt Das Ger t kann h...

Page 20: ...rt ein bzw ausgeschaltet werden Der dynamische Sollwert ist nur f r die W rmepumpe aktiv F r den dynamischen Sollwert m ssen folgende Parameter eingestellt werden H34 Neigung der Kompensierungsgeraden...

Page 21: ...er NEX PRO an eine Anlage mit mehreren zus tz lichen Energiequellen angeschlossen muss die Einschalt priorit t der verschiedenen Quellen festgelegt werden und normalerweise erfolgt dies unter Ber cksi...

Page 22: ...lers besteht die Wahlm glichkeit ob der Widerstand nur in den Stunden gespeist werden soll in denen der Tarif am g nstigsten ist Zu diesem Zweck steht an der Basisplatine des Ger ts ein normalerweise...

Page 23: ...m des Verdichters gekop pelt d h l uft der L fter l uft auch der Verdichter Der Parameter F02 bestimmt die Art der Regelung F02 0 EIN AUS Regelung F02 1 modulierende Regelung Im Falle der modulierende...

Page 24: ...HoursElect Heater Visualize HoursGasHeater ResetCount HoursPdC Reset Count HoursElect Heater Reset Count days Reset Count HoursGasHeater VisualizeOn Off Elect Heater contactGND RES VisualizeOn Off Un...

Page 25: ...ckw chter ZustandsanzeigeNiederdruckw chter ZustandsanzeigeWiderstand berEin AusKontakt ZustandsanzeigeMaschine berEin AusKontakt ZustandsanzeigeVerdichter ZustandsanzeigeWiderstand ZustandsanzeigeL f...

Page 26: ...ime between switching off and switching on Time OFF ON expressed in ten second intervals H21 100 0 255 10 SEC Minimum time between two successive starts Time ON ON expressed in ten second intervals H2...

Page 27: ...halten und Einschalten EIN AUS Zeit ausge dr ckt in Zehntelsekunden H21 100 0 255 Sek 10 Mindestzeitraum zwischen zwei aufeinander folgenden Einschaltungen EIN EIN Zeit ausgedr ckt in Zehntelsekunden...

Page 28: ...fttempera tur bei deren berschreiten der L fter im niedrigsten Drehzahlbe reich aktiviert werden muss F06 6 0 10 C Temperatur differenz f r Aktivierung des L fters im h chsten Dreh zahlbereich F07 15...

Page 29: ...ellt die kontinu ierliche Dauer des Zustands S1 AL5 ein bei deren berschreiten der Alarm hohe Tem peratur ausgel st wird AL7 10 0 255 Anz 3 Anzahl Ausl sun gen Stunde Hoher Druck Wech sel von automati...

Page 30: ...vor der Inbetrieb nahme Pr fen Sie vor dem Starten des Ger tes den korrekten Anschluss des Erdungskabels das Vorhandensein einer Schutzsicherung an der Steck dose das korrekt eingesteckte Versorgungs...

Page 31: ...umen auf in denen ent flammbare Gase saure angreifende und korrosive Sub stanzen vorhanden sind die die verschiedenen Bauteile irreparabel besch digen k nnen Planen Sie f r Installations Reparatur und...

Page 32: ...Solar heating circuit pump D Temperature sensor E Solar panels F Safety valve G Expansion tank 3 1 1 Hinweise f r die Installation des Modells NEX PRO CS Zeichenerkl rung Abb 14 A NEX PRO CS B BWW Umw...

Page 33: ...reducer 3 Inspection valve 4 Non return valve 5 Drain valve 6 Safety diaphragm valve 7 Circulation pump 8 Drain Only for NEX PRO C and NEX PRO CS models Only for NEX PRO CS models 3 2 Wasseranschl ss...

Page 34: ...pe bildet flie t durch das auf der R ckseite des Ger ts austre tende durch den Isoliermantel gef hrte Abflussrohr ab mit gewinde von 1 2 Dieser Austritt muss an eine Leitung angeschlossen werden damit...

Page 35: ...adjustment of 90 from fully open Fig 17 A to fully closed fig 17 B 3 5 Luftverteilung mit motorgesteuerter runder Regelklappe Zubeh rcode 20039876 Die Verbindung der D mpfer ist in Abb 16 dargestellt...

Page 36: ...tversorgung getrennt ist Die elektrischen Anschl sse an die Steuertafeln d rfen nur von Fachpersonal unter Beachtung des beigepackten Schaltplans durchgef hrt werden F hren Sie eine Kontrolle der Elek...

Page 37: ...ige Wartung 3 7 1 Hinweise Vor jedem Wartungseingriff muss sichergestellt sein dass das Ger t nicht unter Spannung steht und auch nicht verse hentlich unter Spannung gestellt werden kann Bei jeder War...

Page 38: ...UNGEN M GLICHE URSACHEN Der Verdichter und oder L f ter schalten sich nicht ein Die eingestellten Sicher heitszeiten sind noch nicht abgelaufen Das System ist ges ttigt keine anstehende Star terforder...

Page 39: ...39 NexPro...

Page 40: ...range of products the appear ance and dimensions the technical data the equipment and accessories can be subject to variation Da das Unternehmen dauerhaft bestrebt ist seine Produkte zu verbessern k...

Reviews: