H
Parameter
Description
11 InFL
Influence of room probe on calculation
of heating delivery setpoint tempera-
ture (available with OTBus connection
between the WiFi Box and the boiler
or the RF receiver and the boiler or the
Hi, Comfort T100
and the boiler, if pro-
vided for by the OTBus protocol).
Default set to 10.
The value can be set from 0°C to 20°C.
ESC
MODE
T Mand risc= T Mand Curva + ( CLI * InFL *
Δ
T Amb)
T Mand Curva
= Delivery temperature calculated using the thermoregu-
lation curve set under parameter CLI
CLI
= thermoregulation curve
InFL
= room influence
Δ
T Amb
= (room temperature set) – (current room temperature)
9
Setting the parameter InFL=0, with the external probe disconnected
from the boiler and the web external probe not enabled on the
app, the heating delivery temperature (for the area controlled by
Hi, Comfort T100
) is the same as the temperature set under param-
eter LLCH.
9
By setting parameter InFL >0, with the external sensor not connected to the
boiler and the web external sensor not enabled on the app, the heating de-
livery temperature (for the zone controlled by Hi, Comfort T100) is as follows:
Heating del. T = LLCH + ( InFL *
Δ
T Amb )
13 CALI
Correction of the temperature detected by
the
Hi, Comfort T100
room probe.
The value can be set with a hysteresis of
+-7°C.
ESC
MODE