ENGLISH
7
b
The straight length includes the first bend (connection into the boiler), terminals
and joints. An exception is made for the vertical Ø 60-100 mm coaxial pipe, whose
straight length excludes bends.
b
The boiler is supplied without the flue gas exhaust/air suction kit, since it is possible
to use the accessories for condensing appliances that best fit the installation
characteristics (see RIELLO catalogue).
b
The maximum lengths of the pipes refer to the flue accessories available in the
RIELLO catalogue.
b
It is compulsory to use specific pipes.
b
The non insulated flue gas outlet pipes are potential sources of danger.
b
The use of a longer pipe causes a loss of output of the boiler.
b
Make sure the flue gas discharge pipe is tilted 3° towards the boiler.
b
The exhaust pipes can face in the direction most suited to the installation
requirements.
b
As envisaged by current legislation, the boiler is designed to take in and dispose of
flue gas condensate and/or meteoric water condensate deriving from the flue gas
discharge system using its own siphon.
b
If a condensate relaunch pump is installed, check the technical data (provided by the
manufacturer) regarding output, to ensure it operates correctly.
“Forced open” installation (B23P-B53P) (Fig.14)
In this configuration the boiler is connected to the ø 80 mm flue gases discharge pipe by
means of an adaptor.
- Po
sition the adaptor so that the Ø 60 pipe goes fully into the flue gases tur
ret of the boiler.
-
Once positioned, make sure that the 4 notches (A) on the flange connect to the groove
(B) on the Ø 100 of the adaptor.
-
Fully tighten the screws (C) that tighten the two locking terminals of the flange so the
bend itself is restrained.
Coaxial pipes (ø 60-100 mm) (Fig. 15)
-
Position the bend so that the Ø 60 pipe goes fully up against the flue gases turret of the
boiler.
-
Once positioned, make sure that the 4 notches (A) on the flange connect to the groove
(B) on the Ø 100 of the bend.
-
Fully tighten the screws (C) that tighten the two locking terminals of the flange so the
adaptor itself is restrained.
Twin pipes (ø 80 mm) (Fig. 16)
The combustion air suction pipe should be selected from the two inputs, remove the closing
plug fixed with the screws and fix the specific air deflector.
- P
osition the adaptor on the flue gases pipe so that the Ø 60 pipe goes fully up
against
the flue gases turret of the boiler.
-
Once positioned, make sure that the 4 notches (A) on the flange connect to the groove
(B) on the Ø 100 of the adaptor.
-
Fully tighten the screws (C) that tighten the two locking terminals of the flange so the
adaptor itself is restrained.
If the Ø 60-100 to Ø 80-80 splitter kit is used instead of the twin pipe system, there is a loss
in the maximum lengths as shown in the table.
- Plac
e the splitter so that the Ø 60 pipe goes fully up against the flue gases turret of the
boiler.
-
Once positioned, make sure that the 4 notches (A) on the flange connect to the groove
(B) on the Ø 100 of the splitter.
-
Fully tighten the screws (C) that tighten the two locking terminals of the flange
so the
adaptor itself is restrained.
Ø50
Ø60
Ø80
Loss of length (m)
0.5
1.2
5.5 for flue gases pipe
7.5 for air pipe
Coaxial pipes (ø 80-125 mm) (Fig. 17)
-
Place the adaptor vertical attachment so that the Ø 60 pipe goes fully up against the flue
gases turret of the boiler.
-
Once positioned, make sure that the 4 notches (A) on the flange connect to the groove
(B) on the Ø 100 of the adaptor.
-
Fully tighten the screws (C) that tighten the two locking terminals of the flange so the
adaptor itself is restrained.
-
Then fit the Ø 80-125 adaptor kit on the vertical fitting
Twin pipes with Ø 80 pipework Ø50 - Ø60 - Ø80) (Fig. 18)
Thanks to the boiler characteristics, a Ø80 flue gas exhaust pipe can be connected to
the Ø50 - Ø60 - Ø80 piping ranges.
b
For the pipe, you are advised to make a project calculation in order to respect the
relevant regulations in force.
The table shows the standard configurations allowed.
Table of standard pipe configuration (*)
Air suction
1 Bend 90° Ø 80
4.5m pipe Ø80
Flue gas discharge
1 Bend 90° Ø 80
4.5m pipe Ø80
Reduction from
Ø
80 to
Ø
50 from
Ø
80 to
Ø
60
Flue base bend 90°, Ø
50 or
Ø
60 or
Ø
80
For ducting pipe lengths see table
(*)
Use flue gas system accessories made of plastic (PP) for condensing boilers: Ø50
and Ø80 class H1 and Ø60 class P1.
The boilers are factory set to:
25 IS:
6.200 r.p.m. in heating mode and 7.600 in domestic hot water mode and the maximum
attainable length is 5m for the Ø 50 pipe, 18m for the Ø 60 pipe and 98m for the Ø 80 pipe.
35 IS:
6.900 rpm in heating mode and 7.800 in domestic hot water mode, and the maximum
length that can be reached is 2m for the Ø 50, 11m for the Ø 60 pipe and 57m for the Ø
80 pipe.
Should greater lengths be required, compensate the pressure drop with an increase in the
r.p.m.of the fan, as shown in the adjustments table, to provide the rated heat input.
b
The minimum calibration should not be modified.
Table of adjustments
Fan rotations
r.p.m.
Pipework ducts
ΔP at boiler
outlet
maximum length [m]
Heating
DHW
Ø 50
Ø 60
Ø 80
Pa
25 IS
6.200
7.600
5
18
98
174
6.300
7.700
7 (*)
23 (*)
125 (*)
213
6.400
7.800
9 (*)
28 (*)
153 (*)
253
6,500
7.900
11 (*)
33 (*)
181 (*)
292
6.600
8.000
13 (*)
38 (*)
208 (*)
332
6.700
8.100
15 (*)
43 (*)
236 (*)
371
6.800
8.200
17 (*)
48 (*)
263 (*)
410
6.900
8.300
19 (*)
53 (*)
291 (*)
450
7.000
8.400
22 (*)
58 (*)
319 (*)
489
7.100
8.500
24 (*)
63 (*)
346 (*)
528
35 IS
6.900
7.800
2
11
57
190
7.000
7.900
3 (*)
15 (*)
75 (*)
229
7.100
8.000
4 (*)
19 (*)
93 (*)
269
7.200
8.100
6 (*)
22 (*)
112 (*)
308
7.300
8.200
7 (*)
26 (*)
130 (*)
348
7.400
8.300
9 (*)
30 (*)
148 (*)
387
7.500
8.400
10 (*)
33 (*)
166 (*)
426
7.600
8.500
12 (*)
37 (*)
184 (*)
466
7.700
8.600
13 (*)
40 (*)
202 (*)
505
7.800
8.700
15 (*)
44 (*)
220 (*)
544
(*) Maximum length that can be installed ONLY with class H1 discharge pipes.
The Ø50 or Ø60 or Ø80 configurations contain Lab test data.
In the event of installations that differ from the indications in the “standard configurations”
and “adjustments” tables, refer to the equivalent linear lengths below.
b
In any case, the maximum lengths declared in the booklet are guaranteed, and it is
essential not to exceed them.
Linear equivalent in metres Ø80 (m)
COMPONENT
Ø 50
Ø 60
Bend 45°
12.3
5
Bend 90°
19.6
8
Extension 0.5m
6.1
2.5
Extension
1.0m
13.5
5.5
Extension 2.0m
29.5
12
3.14
Installation on collective flues in positive pressure (fig.
18a-18b-18c)
The collective flue is a flue gas exhaust system suitable for collecting and expelling the
combustion products of several appliances installed on several floors of a building.
The positive pressure collective flues can only be used for type C condensing appliances.
Therefore the B53P/B23P configuration is forbidden. The installation of boilers under
collective pressure flues is allowed exclusively in G20. The boiler is sized to operate
correctly up to a maximum internal pressure of the flue no higher than the value of 25 Pa.
Check that the fan speed corresponds to what is shown in the table “technical data”.
Make sure that the air intake and exhaust pipes of the combustion products are watertight.