ENGLISH
25
-
anti-freeze function (only with storage cylinder with probe connected):
the function
starts if the temperature measured by the storage tank probe falls below 5°C. A heat
request is generated in this phase with the ignition of the burner at minimum output,
which is maintained until the outlet water temperature reaches 55° C.
b
The activation of the ANTI-FREEZE function is indicated by a scrolling message on
the foot of the REC10 display.
-
circulator anti-locking:
the circulator activates every 24 hours of stoppage for 30
seconds.
5.18 Switching off for lengthy periods
The long term non use of the
Family
boiler causes the following operations to be carried out:
- set the status of the boiler to
- set the system's main switch to "off"
- close the fuel and water taps of the heating and domestic hot water system.
In this case, the anti-freeze and anti-blocking systems are deactivated. Drain the heating
and domestic water system if there is any risk of freezing.
OFF
HOT WATER ONLY
HEATING AND HOT WATER
BOILER
Closing
position
ON
OFF
5.19 System reset
b
This operation must be carried out only by professionally qualified personnel.
Whenever necessary, it is possible to restore the factory settings by carrying out a SYSTEM
RESET:
-
access the technical parameters as explained in the section“ Accessing the technical
parameters”.
- select INSTALLATION with the "UP" and "DOWN
" keys, confirming the selection
RANGE RATED
WEATHER COMPENSATION
PARAMETERS
CALIBRATION
TECHNICAL
INSTALLER
INSTALLATION
-
select SYSTEM RESET with the "
UP" and "DOWN
" keys, confirming the selection
ZONES MANAGER
SENSOR CALIBRATION
INSTALLATION
SYSTEM RESET
INSTALLER
-
select CONFIRM to confirm the system reset or else CANCEL to cancel the operation
.
CANCEL
CONFIRM
Note:
After a reset it is necessary to carry out a new configuration of the system; for details
about this procedure, see the following section.
5.20
System configuration
b
This operation must be carried out only by professionally qualified personnel.
When restarting after a replacement of the REC10 rather than after a “SYSTEM RESET”,
the remote control an initial screen with the firmware revision. Pressing “
ENTER
” starts a
guided procedure for configuring the system; select the desired options with the “
UP
” and
“
DOWN
” keys, confirming the selection
:
PRESS ANY KEY TO
CONTINUE
REC10R
R02.06
Welcome home
- LANGUAGE selection:
ENGLISH
- setting TIME and DATE
ENTER TIME AND DATE
TIME & DATE
12
17
18/11/2013
:
- setting the operating mode of the REC10:
MASTER
: select this option when the REC10 is also a MACHINE INTERFACE.
- configuration selection:
MAIN PCB
: to reset the current boiler configuration on REC10 MASTER and finish the
operation
NEW
: to set a new system configuration restoring the factory setting of the parameters
NEW
MAIN PCB
SELECT THE TYPE OF
CONFIGURATION
-
Whenever a “NEW” configuration is selected, proceed as follows
- select functionality of the REC10:
ON BOARD
: if the REC10 is used only as a system interface and not as an ambient
regulator
AMBIENT
: if the REC10 is used as a system interface and also as an ambient regulator
of the zone where it is installed
ON BOARD
WHERE IS THE REC10 INSTALLED?
AMBIENT
BOILER
- selection of the type of boiler on:
-
CH ONLY
: if the boiler does not manage the domestic hot water (case A).
-
HW TANK
: if the boiler manages a domestic hot water storage cylinder. Note: in this case
the specific type of domestic hot water request will be requested, THERMOSTAT (case B)
or TEMPERATURE PROBE (case C).
-
If the storage cylinder with probe is selected you are also asked whether to manage also
the solar heating system: answer NO to this question.
INSTANTANEOUS
HW TANK
CH ONLY
SELECT THE PLANT CONFIGURATION
PLANT