background image

 

25

 

INSTALLATION

2.8.2 

Flow limits

RTC-80

 boilers do not require a minimum flow rate in order to 

maintain warranty. The boiler has been designed to operate with 

a temperature difference between the supply and return of up 

to 100 °F. Flow should be initiated with the start of the burner 

to minimize temperature fluctuations and control deviations. The 

field installed manual reset high limit (as required by CSD-1) must 

be fitted to the instrument tapping of the heating supply, set to 

210°F and electrically connected into the Control unit or the burner 

enable/disable circuit directly.

RTC-80

 boilers can operate with zero flow, and do not require a 

minimum flow rate.

A minimum flow is recommended only to provide heat transfer, 

and the maximum flow to prevent erosion.

Model

Flow Limits

Maximum

Minimum

RTC 1000-80

130

12

GPM (*)

RTC 1300-80

160

15

GPM (*)

RTC 1700-80

200

20

GPM (*)

RTC 2300-80

290

30

GPM (*)

RTC 3000-80

370

40

GPM (*)

RTC 3800-80

480

50

GPM (*)

RTC 4700-80

580

60

GPM (*)

RTC 5500-80

690

70

GPM (*)

(*) 

Units shown are in US Gallons.

2.8.3 

Water quality requirements

The manufacturer recommends the use of water as heat transfer 

fluid for the central heating system. A chemical treatment system 

must be provided for this water.

The heat transfer fluid (water) for the central heating circuit must 

conform to the quality parameters given in the following table:

Chemical and physical requirements of heating system water

Initial filling 

water

Regular service 

water (*)

ph

6-8

7.5-9.5

Hardness

°fH / ppm

< 5° / 50

< 5° / 50

Electrical con-

ductivity

μs/cm

< 100

Chlorides

mg/l / ppm

< 10 / 10

Sulphides

mg/l / ppm

< 10 / 10

Nitrides

mg/l / ppm

< 10 / 10

Iron

mg/l / ppm

< 0.5 / 0.5

(*) values for water in system after 8 weeks of functioning

 

9

NOTICE:

 

If it proves impossible to treat the heating system water 

supply properly because the water charging system is 

automatic and uncontrolled, if there are no barriers 

installed to prevent water oxygenation and if the heating 

system includes an open expansion vessel, then the 

boiler itself must be separated from the heating system by 

means of a heat exchanger.

If the hardness of the water exceeds the value specified in the 

table, it is mandatory to install a water softening system.

 

9

NOTICE:

 

− Chemical products used for water treatment must be com-

patible with applicable water pollution laws.

 

− Provided they are properly applied, these laws guarantee 

the safe functioning of the heating system.

2.8.4 

Central heating system

Possible causes for corrosion and limescale

Typical problems encountered in central heating systems include:

 

− the breakage of heated surfaces through overheating 

caused by the thermal insulation of limescale deposits on 

the water side

 

− oxygen corrosion

 

− deposit corrosion

 

− stray current corrosion

 

− diffused and localized acid corrosion.

The technical details provided in this section refer specifically to 

domestic and industrial hot water heating systems with working 

temperatures up to 210°F (99°C).

2.8.5 

New central heating systems

Mistakes to avoid and precautions.

To eliminate contact between system water and the air, the fol-

lowing is required:

 

− ensure that the expansion vessel is a closed vessel, and 

of the correct size and pre-charge pressure (the pressure 

should be checked periodically)

 

− ensure that the system is always kept at a pressure high-

er than atmospheric pressure at all points (including the 

pump suction side) and at all operating conditions (pre-

cisely because the seals, gaskets and joints in a water cir-

cuit are designed to resist pressure from within, but not to 

resist a vacuum within)

 

− ensure that no part of the system is made from materials 

that are permeable to gases (e.g. plastic pipes with no ox-

ygen barrier used in floor heating systems).

 

9

NOTICE:

 

The original system filling water and any topping up water 

must always be filtered (using synthetic or metal mesh 

filters with a filtration rating of no less than 50 microns) 

to prevent sludge from forming and triggering deposit 

induced corrosion.

 

9

NOTICE:

 

We recommend fitting an 80 mesh dirt filter externally to 

the boiler return to prevent contamination of the boiler by 

the water source.

Summary of Contents for 20165080

Page 1: ...cod 20158857 rev 2 02 2020 RTC 80 1000 5500 USA INSTALLATION OPERATION AND SERVICE MANUAL...

Page 2: ...the appliance Used in conjunction with your own knowl edge and expertise it will enable you to install the appliance quickly easily and correctly Please accept our thanks and congratulations on your c...

Page 3: ...quirements 25 2 8 4 Central heating system 25 2 8 5 New central heating systems 25 2 8 6 Reconditioning old heating systems 26 2 8 7 Elimination of air and gas from central heating system 26 2 8 8 Use...

Page 4: ...connect the boiler from the main electrical supply and shut off the water supply 9Periodically check that pressure in the central heating circuit when cold is approximately 20 psi 1 4 bar and below th...

Page 5: ...njury or death from fire Do not use flammable or combustible material in the boiler room It is recommended not to store any items within 16 inches 415mm of the appliance 9CAUTION Appliance damage from...

Page 6: ...door can open in either direction and can be opened without removing the burner The door is facto ry fitted with hinges on the left but these can be field re versed if necessary to suit individual in...

Page 7: ...rature 8 Heating return low temperature 9 Blind plug 10 Instrument bulb sensor sockets 11 Combustion chamber 12 Flue gas exhaust 13 Flue gas box 14 Inspection window 15 Condensate outlet 16 Boiler dra...

Page 8: ...ficiency 94 0 94 0 94 0 94 0 94 0 94 0 94 0 94 0 1 Values based on natural gas firing Based on standard burner with optional high turndown kit 2 Maximum output dependent upon application 3 Condition 1...

Page 9: ...PM 2 18 psi at 523 GPM Maximum turndown Nat Gas 10 1 10 1 10 1 10 1 10 1 10 1 10 1 10 1 Vent Connections 10 10 12 12 14 14 16 18 Vent Materials AISI 316L AL29 4C 29 Cr 4 Mo Type of Fuel Natural Gas Pr...

Page 10: ...carried out by an autho rized heating engineer Any work on gas piping components may only be carried out by an authorized gas installer The local regulations regarding minimum pressure detectors maxim...

Page 11: ...instructions for that system shall include a parts list and detailed installation instructions e A copy of all instructions for all Product Approved side wall hor izontally vented gas fueled equipment...

Page 12: ...46 x RS 190 E 20067546 x COMBINATION OIL GAS RLS 28 x RLS28 E x RLS 38 x RLS38 E x RLS 50 x RLS 50 E x RLS 70 20067545 x RLS 68 E 20067545 20067545 RLS 100 x x RLS 130 x RLS 160 E x 20067546 x RLS 190...

Page 13: ...d warning label to be applied to the casing upon completion of the installation water treatment instructions E B A D C Inside the combustion chamber C D The second contains the boiler casing complete...

Page 14: ...1 9 16 40 1 3 8 35 1 3 8 35 2 3 4 70 2 3 4 70 3 1 8 80 3 15 16 100 F Flue connection depth inch mm 2 3 8 60 2 3 8 60 3 1 8 80 3 1 8 80 3 9 16 90 3 9 16 90 3 1 8 80 3 1 8 80 H Height of water fittings...

Page 15: ...ial into the envi ronment or leave it within the reach of children since it can become a potential hazard Dispose of packaging material in compliance with the applicable legislation for lifting using...

Page 16: ...e the burner 9WARNING When installing the boiler allow sufficient space around it to access all safety and control devices and to permit easy maintenance 9WARNING Check that the electric protection le...

Page 17: ...A Four Boilers configuration 5 A A A A RTC 80 A Minimum distances Unit 1000 32 inch 1300 32 inch 1700 40 inch 2300 40 inch 3000 48 inch 3800 48 inch 4700 48 inch 5500 48 inch 9WARNING Make sure that t...

Page 18: ...ttings on RTC 80 boilers Before installing the boiler flush out all the pipes of the central heating circuit to remove any machining residues oils scale dirt and debris RTC 1000 80 RTC 4700 80 M M 7 6...

Page 19: ...3 13 16 350 28 13 16 732 D Distance between heating return 2 and safety device fitting inch mm 11 13 16 300 17 3 4 450 23 5 8 600 27 9 16 700 29 1 2 750 33 1 2 850 33 1 2 850 33 1 2 850 E Distance bet...

Page 20: ...20 INSTALLATION 2 6 Sensor manifold installation 1000 1300 1700 2300 3000 3800 4700 5500 Sensor manifold type 2 1 2 150 3 150 4 150 5 150 6 150 NPS...

Page 21: ...47 64 95 mm 3 47 64 95 mm 3 47 64 95 mm C 4 29 64 113 mm 4 1 4 108 mm 4 21 64 110 mm 4 21 64 110 mm 4 21 64 110 mm D 3 15 16 100 mm 3 15 16 100 mm 3 15 16 100 mm 3 15 16 100 mm 3 15 16 100 mm E 5 5 8...

Page 22: ...l diameter probe sockets 7 mm Thermowell length L100 mm Boiler RTC 80 1000 1300 1700 2300 3000 3800 4700 Sensor manifold type NPS 2 1 2 150 3 150 4 150 4 150 5 150 5 150 6 150 Thermowell length min ma...

Page 23: ...ets 15 mm Thermowell length L170 mm 3 Inlet operating temperature thermowell G 1 2 for n 2 3 instrument bulb Internal diameter probe sockets 7 mm Thermowell length L100 mm Boiler RTC 80 5500 Sensor ma...

Page 24: ...0 63 61 0 28 46 0 18 31 0 08 RTC 1300 80 120 0 46 80 0 20 60 0 12 40 0 05 RTC 1700 80 156 0 41 104 0 18 78 0 11 52 0 05 RTC 2300 80 212 1 74 141 0 78 106 0 39 71 0 18 RTC 3000 80 276 1 65 184 0 73 138...

Page 25: ...xpansion vessel then the boiler itself must be separated from the heating system by means of a heat exchanger If the hardness of the water exceeds the value specified in the table it is mandatory to i...

Page 26: ...iency 2 8 7 Elimination of air and gas from central heating system When designing new heating systems it is necessary to eliminate the air and other gases that form in the system Recently added fill o...

Page 27: ...needed water supplies and recovery circuits must be condi tioned by suitable treatment systems Refer to the values list ed in the table in the paragraph Water quality requirements 0CAUTION It is prohi...

Page 28: ...MAKE UP WATER FLOW LT RETURN WATER INLET 1 Boiler 2 Burner 3 Isolation valves 4 Central heating system pump 5 Non return valves 6 Automatic vent valve 7 Boiler safety valve 8 Boiler drain valve 9 Y s...

Page 29: ...em pump 5 Non return valves 6 Automatic vent valve 7 Boiler safety valve 8 Boiler drain valve 9 Y strainer 10 Pressure reducer 11 Expansion tank 12 Water softener filter 13 Siphon 14 Condensate outlet...

Page 30: ...er 3 Isolation valves 4 Central heating system pump 5 Non return valves 6 Automatic vent valve 7 Boiler safety valve 8 Boiler drain valve 9 Y strainer 10 Pressure reducer 11 Expansion tank 12 Water so...

Page 31: ...tion valves 4 Central heating system pump 5 Non return valves 6 Automatic vent valve 7 Boiler safety valve 8 Boiler drain valve 9 Y strainer 10 Pressure reducer 11 Expansion tank 12 Water softener fil...

Page 32: ...ion valves 4 Central heating system pump 5 Non return valves 6 Automatic vent valve 7 Boiler safety valve 8 Boiler drain valve 9 Y strainer 10 Pressure reducer 11 Expansion tank 12 Water softener filt...

Page 33: ...system pump 5 Non return valves 6 Automatic vent valve 7 Boiler safety valve 8 Boiler drain valve 9 Y strainer 10 Pressure reducer 11 Expansion tank 12 Water softener filter 13 Siphon 14 Condensate ou...

Page 34: ...ral heating system pump 5 Non return valves 6 Automatic vent valve 7 Boiler safety valve 8 Boiler drain valve 9 Y strainer 10 Pressure reducer 11 Expansion tank 12 Water softener filter 13 Siphon 14 C...

Page 35: ...p of conden sate Pcc in inch W C 1 3 3 7 2 11 Neutralizing the condensate Installation of a condensate neutralization kit is always recom mended The following table states the rate of condensate flow...

Page 36: ...e being eliminated to the floor drain 3 2 3 1 See Draining the condensate A i Description Symbol Unit RTC 80 1000 1300 1700 2300 Height of flue gas outlet A inch mm 21 1 16 535 25 635 Diameter of flue...

Page 37: ...tem is positive 0 2 W C for proper combustion and light off A draft control system may be required to ensure proper draft when two or more boilers are connected to a common stack Con sult the flue mat...

Page 38: ...ou vers should be in a fixed position or interlocked with equipment so that they open automatically during equipment operation The combustion air damper opening shall be located as follows top louver...

Page 39: ...nge fixing nuts System B on the larger sizes comes with a hinge fixing plate a nut and an internal compression spring A B A Smaller sizes system A Larger sizes system B Axis of door rotation 2 14 Chan...

Page 40: ...the plug 1 taking care not to lose the compressed spring inserted in the threaded tube 2 3 4 2 3 6 6 5 6 5 6 4 4 4 Remove the bolt 3 and the nuts 4 Remove the nuts 4 that secure the hinge plate 5 to t...

Page 41: ...d as follows Unscrew the nut and washer 1 from the earth terminal Attach the earth cable s eye connector 2 to the terminal Make sure that the cable is of adequate size and complies with legislation in...

Page 42: ...ross beams 8 and the screws provided Fit the top rear panel 9 the bottom rear bracket 10 and then the bottom rear panels 11 and 12 Fit the front top panel 13 Fit the top panels 14 15 16 and 17 Smaller...

Page 43: ...and low temperature For an optimum energy yield we recommend supplying a flow rate of 10 of the total nominal flow rate via the low temperature flange with a return temperature below the dew point If...

Page 44: ...slowly and observe the pressure gauge whilst doing so Vent the heating system via the radiator air vent valves If the water pressure drops as a result of venting the system Top up the system with wate...

Page 45: ...ghtness Start the burner Complete the burner test report regarding the individual output stages Conduct a tightness test on the hot gas side After a short time in operation tighten the screws in the c...

Page 46: ...em re mains operational especially when there is a risk of frost 9NOTICE Always keep the oil supply valve shut off if the burner is shut down for an extended period of time 4 1 Shutting down the heati...

Page 47: ...h OFF Close all the gas cocks 9DANGER Risk to life from electric shock Before opening a unit disconnect electrical power and lockout to prevent accidental reactivation 9DANGER Risk to life from explos...

Page 48: ...The first time opening the door remove the spare hinge as sembly B bushing bolt and washer opposite the pivot side of the door Remove the deposits accumulated in the flue box through the opening of th...

Page 49: ...stinction is generally made between open vented and sealed unvented systems In practice open vented systems are hardly installed nowadays We will therefore be using a sealed unvent ed heating system t...

Page 50: ...uired Check and clean the burner Visual inspection and remove any contamination Check all safety equipment safety shutdown Function check Flue gas analysis with test report for each output stage See t...

Page 51: ...heck the vent valve The boiler has reached the set tempera ture but the radiators are still cold Air in the circuit Bleed the circuit Pump malfunctioning Check release the pump Problem with minimum te...

Page 52: ...the environment we use the best possible technology and materials taking into account economic points of view Packaging For the packaging we participate in the country specific recycling systems whic...

Page 53: ...53...

Page 54: ...54...

Page 55: ...55...

Page 56: ...ond Park Road Hingham Massachusetts U S A 02043 2165 Meadowpine Blvd Mississauga ON L5N6H6 CANADA www rielloboilers com The manufacturer strives to continuously improve all products appearance dimensi...

Reviews: