36
INSTALLATION
Menu
Par.
No. Description
Range
Default setting
INSIEME EVOe 32
B/110 LN
UM
Ac-
cess
2000
2063
∆T boiler delivery / boiler return
5...40
15
°C
I
2000
2074
Burner anti-freeze protection
0 = NO
1 = Yes
0…1
1
I
2000
2075
Heating circuit anti-freeze protection
0 = NO
1 = Yes
0…1
1
I
2000
2076
DHW anti-freeze protection
0 = NO
1 = YES
0…1
1
I
2000
2077 DHW anti-freeze protection time
0...24
12
hours
I
2000
2099
Burner ignition stand-by time
It delays the burner ignition after the opening of the
solenoid valve on the fuel supply pipeline
0…60
0
sec
I
Error log
2000
9001 Last error logged
I
2000
9002 Second last error logged
I
2000
9003 Third last error logged
I
2000
9004 Fourth last error logged
I
2000
9005 Fifth last error logged
I
2000
9006 Sixth last error logged
I
2000
9007 Seventh last error logged
I
2000
9008 Eighth last error logged
I
2000
9009 Ninth last error logged
I
2000
9010 Tenth last error logged
I