36
INSTALLATION
Menu
Par.
No.
Description
Range
Default
setting
INSIEME
EVOe 25 K LN
Default
setting
INSIEME
EVOe 32 K LN
UM
Access
2000
2043
Time for which the priority is alternately assigned to
domestic and heating circuits when the Par. 2042 is
set to "0” mode (for heater only).
0...120
60
60
min
I
2000
2041
Primary setpoint for heater with thermostat
50...82
75
75
°C
I
2000
2044 Circulator post-circulating time in domestic mode.
10...900
120
120
sec
I
2000
2045
DHW Enable PO Input
0 = DHW always enabled
1 = DHW enable input via PO input
0...1
0
0
I
2000
2048 DHW setpoint with instant production
40…70
45
45
°C
U
2000
2049
Circulator modulation in DHW mode
The circulator modulation can vary between 50% = 5
and 100% = 10
5...10
9
9
10*%
I
2000
2052
DCW minimum temperature setpoint of DHW ex-
changer (it activates pump and diverting valve on
domestic circuit)
10...35
25
25
°C
I
2000
2053
DCW maximum temperature setpoint of DHW ex-
changer (it deactivates pump and diverting valve on
domestic circuit)
10...35
25
25
°C
I
2000
2056 Boiler minimum holding temperature for DHW in-
stant production
20...82
60
60
°C
I
2000
2061
Boiler setpoint for DHW instant production
40...82
80
80
°C
I
2000
2062
∆T boiler switch-off setpoint for DHW production
0...3
1
1
°C
I
2000
2063
∆T boiler delivery / boiler return
5...40
15
15
°C
I
2000
2074
Burner anti-freeze protection
0 = NO
1 = Yes
0…1
1
1
I
2000
2075
Heating circuit anti-freeze protection
0 = NO
1 = Yes
0…1
1
1
I
2000
2076
DHW anti-freeze protection
0 = NO
1 = YES
0…1
1
1
I
2000
2077
DHW anti-freeze protection time
0...24
12
12
hours
I
2000
2099
Burner ignition stand-by time
It delays the burner ignition after the opening of the
solenoid valve on the fuel supply pipeline
0…60
0
0
sec
I
Error log
2000
9001
Last error logged
I
2000
9002 Second last error logged
I
2000
9003 Third last error logged
I
2000
9004 Fourth last error logged
I
2000
9005 Fifth last error logged
I
2000
9006 Sixth last error logged
I
2000
9007 Seventh last error logged
I
2000
9008 Eighth last error logged
I
2000
9009 Ninth last error logged
I
2000
9010
Tenth last error logged
I
9
Delays in domestic water delivery may occur when operating on the parameter 2099.