GENERAL INFORMATION
1.4
Safety and control devices
The control panel, apart from managing the functions of the
thermal unit
INSIEME EVOe K LN
, allows to highlight any anom-
aly which may affect its correct operation, ensuring the thermal
unit safety by stopping it and automatically closing the burner
light oil valve.
The burner control and adjustment board is also used to ensure
the burner safety by managing its correct operation.
Any anomaly which may affect the generator operation forces
it to stop (lock-out) and is promptly signalled with a numerical
error code on the regulator display.
The following are installed on the water circuit:
−
Safety thermostat
: fitted on the generator body, it in-
tervenes by stopping (permanent error) the thermal unit
if the boiler temperature exceeds the limit threshold of
110°C;
−
Safety valve
: intervenes if the boiler pressure exceeds the
limit threshold of 3 bar;
−
Pressure transducer
: sends a signal to the electronic reg-
ulator which views and continually checks the primary
circuit pressure to switch on the generator or cause it to
stop in case of low pressure;
−
Boiler temperature probes (delivery and return)
: im-
mersion probe on the delivery line of the generator is
used by the regulator to view and check the delivery wa-
ter temperature and check the correct switching on and
off of the burner based on the programmed setpoint. The
regulator uses the same probe to switch off the genera-
tor in case of overtemperature, before the triggering of
the safety thermostat. The contact probe placed on the
return line of the boiler is used by the regulator to view
the return water temperature with which it calculates,
together with the delivery temperature, the temperature
difference between delivery and return (
∆
t), which allows
regulating the modulation of the circulator in heating
mode.
−
Domestic circuit temperature probes (plate exchang-
er)
: there are two temperature probes on the domestic
plate exchanger circuit. One immersion probe is placed
on the domestic cold water inlet and the other one on
the domestic hot water outlet. The regulator uses these
two probes to view and check the domestic water tem-
perature and manage the functions (DHW Setpoint, DHW
request) of the relevant parameters.
9
The intervention of a safety device indicates a potentially
dangerous malfunction in the system. Contact the manu-
facturer’s Technical Assistance Service immediately.
9
Safety devices must only be replaced by the manufactur-
er's Technical Assistance Service using original spare parts.
Refer to the spare parts catalogue supplied with the boiler.
After making the repair, check that the appliance is working
properly.
0
The appliance must not be put in service, even temporarily,
when tampered safety devices are not in operation or have
been tampered with.
Always check that the boiler is functioning correctly after repairs
have been made.
1.5
Identification
The products are identified by:
Serial number plate
Contains the serial number, the model and the main tech-
nical data.
S
X
%
mg/kWh
NO
Pms= bar T = °C
Qn(min)=
Pn(min)=
T067793GE
Qn(max)=
Pn(max)=
Mod.
Cod.
N°
kW
kW
kW
kW
kW
D= l/min
kW
kW
kW
Pmw= bar T = °C
IP
W
V~Hz
RIELLO S.p.A.
Via Ing.Pilade Riello 7
37045 Legnago (VR) - ITALY
TIPO/TYP/TYP/TYPE/TIPO/TIPO:
COMBUSTIBILE/COMBUSTIBLE/BRENNSTOFF/BRANDSTOF/FUEL/COMBUSTIBLE/COMBUSTÍVEL:
PAESE DI DESTINAZIONE/PAYS DE DESTINATION/BESTIMMUNGSLAND/LAND VON BESTEMMING
COUNTRY OF DESTINATION/PAÍS DE DESTINO/PAÍS DE DESTINO:
l
T067793GE
Mod.
Cod.
N°
Qn(max)
kW
Pn(max)
kW
bar
Pms
RIELLO S.p.A.
Via Ing.Pilade Riello 7
37045 Legnago (VR) - ITALY
Data plate
This lists the technical specifications and performance of the
product.
DHW section
Central heating section
Qn
Rated heat input
Pn
Rated useful heat output
IP
Electric degree of protection
Pmw
Maximum operating pressure, DHW circuit
Pms
Maximum operating pressure, CH circuit
T
Maximum permitted temperature
η
Efficiency
D
Specific flow rate
NOx
NOx class
9
If these plates or any other means of clearly identifying the
product are defaced, removed or lost, proper installation