33
TECHNICAL ASSISTANCE SERVICE
Clean the boiler and remove any carbon deposits from the surfaces of the heat exchanger
at least once a year
. This
not only extends the boiler’s working life, but also keeps it efficient in terms of heat output and consumption.
Proceed as follows to clean the boiler. Open the front
door (1) and pull out the turbulators (2). Use cleaning
rods (3) or other tools of suitable size and shape to clean
inside the tubes. Remove any built-up deposits from the
flue gas box through the access door opening.
b
If you are using fuel oil burners with a smoke scale
reading higher than 3, perform the following actions
every 300 hours
of operation.
- Clean the boiler’s heat exchange surfaces.
- Check and clean the turbulators. Replace if worn
or damaged.
2
3
1
CLEANING THE BOILER
RTS 2S
115
150
200
247
319
410
526
736
850 1012 1200 1355 1500 1850
N. waves
22
22
27
32
38
40
55
61
61
71
71
71
71
90
n°