20
INSTALLER
ANTI-CONDENSATE PUMP
COMBUSTION GAS EXHAUST
D
3
√
5 D
An anti-condensate pump operates during periods of
no heat request to avoid damage until the boiler returns
to a stable operating temperature. While the system is
operating, this pump must guarantee a flow rate between
20 and 30% maximum flow to ensure a water return
temperature no lower than 55 °C. Pump shutdown must
also be delayed for at least 3 minutes at the beginning of
extended periods of boiler shutdown (overnight or week-
end shutdown etc.).
b
A sensor socket must be positioned at a distance
of 3 to 5 times the diameter of the water return
pipe, upstream from the water fitting, to measure
effective water return temperature and control the
anti-condensate pump or the temperature controller
stabilisation function.
b
Any temperature controllers installed remotely from
the control panel must be compatible with the sys-
tem’s electrical connections and functioning logic.
0
30
60
90
Ø
H
The flue gas exhaust and its connection to the stack must be made in compliance with applicable laws and standards,
using heat resistant, condensate resistant and stress resistant rigid pipe and sealed joints.
RTS 2S
115
150
200
247
319
410
526
736
850 1012 1200 1355 1500 1850
Ø - Diameter
180
200
250
250
250
250
300
350
350
400
400
400
400
450 mm
H
870
946 1005 1005 1130 1130 1290 1405 1405 1445 1445 1580 1580 1695 mm