background image

VIESMANN

VITOGAS

Low temperature gas boiler

11 to 60 kW

VITOGAS 200-F   

Type GS2

Low temperature gas boilers, 11 to 60 kW

For modulating boiler water temperature

With premix burner for natural gas and LPG

Fully automatic

Permissible operating pressure 3 bar

Product ID: CE-0085 AS 0297

VITOGAS 100-F   

Type GS1D

Low temperature gas boilers, 29 to 60 kW

For modulating boiler water temperature

With partially pre-mixing burner for natural gas and LPG

Fully automatic

Permissible operating pressure 3 bar

Product ID: CE-0085 AS 0297

5822 428 GB

5/2010

Technical guide

Summary of Contents for VITOGAS

Page 1: ...for natural gas and LPG Fully automatic Permissible operating pressure 3 bar Product ID CE 0085 AS 0297 VITOGAS 100 F Type GS1D Low temperature gas boilers 29 to 60 kW For modulating boiler water temperature With partially pre mixing burner for natural gas and LPG Fully automatic Permissible operating pressure 3 bar Product ID CE 0085 AS 0297 5822 428 GB 5 2010 Technical guide ...

Page 2: ...Four way mixer 44 Safety equipment block 44 Plinth for Vitogas 200 F 44 Plinth for Vitogas 100 F 44 Flue gas monitoring sensor 45 5 Design information 5 1 Selection of rated output 45 5 2 System design 45 5 3 Flue system 45 5 4 Safety equipment 45 5 5 Thermal safety shut off valve 45 5 6 Heating circuits 45 5 7 Plastic pipework for radiators 45 5 8 Additional requirements when installing boilers f...

Page 3: ...th the Divicon heat ing circuit distributor 56 Contact temperature sensor 56 Immersion thermostat 56 Contact thermostat 57 Vitotrol 100 type UTDB 57 Vitotrol 100 type UTDB RF 58 Notes regarding room temperature hook up RS function for remote control units 58 Information regarding the Vitotrol 200 and 300 58 Vitotrol 200 59 Vitotrol 300 59 Room temperature sensor 60 KM BUS distributor 60 Flue gas t...

Page 4: ...ing surface made from special cast iron for high operational reliability and a long service life A Highly effective thermal insulation B Heating surfaces made from special cast iron C Atmospheric stainless steel premix burner D Digital Vitotronic boiler control unit Delivered condition Boiler with fitted thermal insulation and atmospheric premix burner for natural gas and LPG according to DVGW Cod...

Page 5: ...UZ 39 1 2 Operating conditions Requirements Implementation 1 Heating water flow rate none 2 Boiler return temperature minimum value 35 ºC Installation of an efficient return tempera ture raising facility e g through 4 way mixer and minimum limit and or return temperature raising pump 3 Low end boiler water temperature also for frost protection 35 ºC Through the Viessmann control unit standard deli...

Page 6: ...s 7 6 7 6 9 7 9 7 11 7 13 8 15 9 17 9 21 9 Permiss operating pressure bar 3 3 3 3 3 3 3 3 3 Boiler connections Boiler flow and return G 1 1 1 1 1 1 1 1 1 Safety flow G 1 1 1 1 1 1 1 1 1 Drain R Gas connection R Connection values in relation to the max load Natural gas E m3 h 1 28 1 76 2 11 2 57 3 39 4 09 4 91 5 61 7 01 Natural gas LL m3 h 1 49 2 04 2 45 2 99 3 94 4 75 5 71 6 52 8 15 LPG kg h 0 95 ...

Page 7: ...SI KV KR GA E d 179 316 409 554 716 173 173 250 580 457 b a 775 877 c 78 SV A Subframe accessory E Drain and diaphragm expansion vessel GA Gas connection KR Boiler return KV Boiler flow SSI Draught hood SV Safety flow Dimensions Rated output kW 11 15 18 22 29 35 42 48 60 a mm 446 446 526 526 596 706 796 886 1076 b mm 500 500 580 580 650 760 850 940 1130 c mm 760 760 760 760 760 780 780 780 780 d m...

Page 8: ...raught hood SV Safety flow Pressure drop primary circuit The Vitogas 200 F is only suitable for fully pumped hot water heating systems 1 2 3 4 5 6 8 10 20 30 40 50 300 400 500 600 800 1000 2000 3000 4000 5000 6000 8000 Pressure drop in mbar Throughput in l h C E A B D A Rated output 11 and 15 kW B Rated output 18 and 22 kW C Rated output 29 kW D Rated output 35 and 42 kW E Rated output 48 and 60 k...

Page 9: ... solvents and cleaning agents Avoid very dusty conditions Avoid high levels of humidity Prevent freezing and ensure good ventilation Otherwise the system may suffer faults and damage In rooms where air contamination through halogenated hydrocar bons may occur install the boiler only if adequate measures can be taken to provide a supply of uncontaminated combustion air Product information cont VITO...

Page 10: ...life A Highly effective thermal insulation B Heating surfaces made from special cast iron C Partially pre mixing stainless steel rod burner D Digital Vitotronic boiler control unit Delivered condition Boiler with fitted thermal insulation and atmospheric premix burner for natural gas and LPG according to DVGW Code of Practice G 260 or local regulations The boiler is factory fitted for natural gas ...

Page 11: ... 35 ºC Installation of an efficient return tempera ture raising facility e g through 4 way mixer and minimum limit and or return temperature raising pump 3 Low end boiler water temperature also for frost protection 35 ºC Through the Viessmann control unit standard delivery Vitogas 100 F cont VITOGAS VIESMANN 11 5822 428 GB 2 ...

Page 12: ...s Boiler flow and return G 1 1 1 1 1 Drain R Gas connection R Connection values in relation to the max load Natural gas E m3 h 3 39 4 09 4 91 5 61 7 01 Natural gas LL m3 h 3 94 4 75 5 71 6 52 8 15 LPG kg h 2 50 3 02 3 62 4 14 5 17 Flue gas parameters calculation values for sizing the flue gas system to EN 13384 Flue gas temperatures gross values measured at 20 C combustion air tem perature 50 C bo...

Page 13: ... a 775 877 A c 78 A Subframe accessory E Drain and diaphragm expansion vessel GA Gas connection KR Boiler return KV Boiler flow SSI Draught hood Dimensions Rated output kW 29 35 42 48 60 a mm 596 706 796 886 1076 b mm 650 760 850 940 1130 c mm 760 780 780 780 780 d mm 1012 1012 1012 1082 1082 e mm 359 403 449 495 586 f mm 291 357 401 445 544 Vitogas 100 F cont VITOGAS VIESMANN 13 5822 428 GB 2 ...

Page 14: ...rimary circuit The Vitogas 100 F is only suitable for fully pumped hot water heating systems B A 1 2 3 4 5 6 8 10 20 30 40 50 300 400 500 600 800 1000 2000 3000 4000 5000 6000 8000 Pressure drop in mbar Flow rate in m h C A Rated output 29 kW B Rated output 35 and 42 kW C Rated output 48 and 60 kW Installation Minimum clearances Observe the given dimensions to ensure easy installation and maintena...

Page 15: ...high levels of humidity Prevent freezing and ensure good ventilation Otherwise the system may suffer faults and damage In rooms where air contamination through halogenated hydrocar bons may occur install the boiler only if adequate measures can be taken to provide a supply of uncontaminated combustion air Vitogas 100 F cont VITOGAS VIESMANN 15 5822 428 GB 2 ...

Page 16: ...stem connections to the boiler see Viessmann pricelist For DHW cylinders with a cylinder capacity greater than 500 l cylinder banks and further DHW cylinders from the Viessmann pricelist the connecting lines must be set on site DHW cylinder 16 VIESMANN VITOGAS 3 5822 428 GB ...

Page 17: ...l h 327 327 395 567 912 1050 Heating water flow rate for the stated contin uous outputs m3 h 3 0 3 0 3 0 3 0 5 0 5 0 Standby heat loss qBS at a temp differential of 45 K actual value acc to DIN 4753 8 500 l Standard parameter to DIN V 18599 kWh 24 h 1 50 1 70 2 20 3 20 3 70 4 30 Thermal insulation Rigid PUR foam Flexible polyurethane foam Dimensions Length 7 incl thermal insulation a mm 581 581 63...

Page 18: ...acity l 160 200 Length 7 a mm 581 581 Width b mm 608 608 Height c mm 1189 1409 d mm 1050 1270 e mm 884 884 f mm 634 634 g mm 249 249 h mm 72 72 k mm 317 317 300 litre capacity l SPR b a c d e f g h k m BÖ VA WW Z HV SPR HR KW E b BÖ Inspection and cleaning aperture E Drain HR Heating water return HV Heating water flow KW Cold water SPR Cylinder temperature sensor of the cylinder temperature contro...

Page 19: ... E Drain HR Heating water return HV Heating water flow KW Cold water SPR Cylinder temperature sensor of the cylinder temperature control or the control thermostat VA Protective magnesium anode WW DHW Z DHW circulation Capacity l 500 Length 7 a mm 850 Width b mm 898 Height c mm 1955 d mm 1784 e mm 1230 f mm 924 g mm 349 h mm 107 k mm 455 l mm 7 100 m mm 422 n mm 837 excl thermal insulation o mm 7 6...

Page 20: ...m 321 332 h mm 104 104 k mm 505 555 l mm 7 180 7 180 m mm 457 468 n mm 947 1047 excl thermal insulation o mm 7 750 7 850 Performance factor NL To DIN 4708 Cylinder storage temperature Tcyl cold water inlet temperature 50 K 5 K 0 K Capacity l 160 200 300 500 750 1000 Performance factor NL at a heating water flow tem perature of 90 C 2 5 4 0 9 7 21 0 40 0 45 0 80 C 2 4 3 7 9 3 19 0 34 0 43 0 70 C 2 ...

Page 21: ...21 26 41 62 90 96 80 C 21 25 40 58 81 94 70 C 20 25 39 54 70 90 Available water volume Cylinder content heated to 60 C Without booster heating Capacity l 160 200 300 500 750 1000 Draw off rate l min 10 10 15 15 20 20 Available water volume water at t 60 C continuous l 120 145 240 420 615 835 Heat up time The heat up times will be achieved if the max continuous output of the DHW cylinder is made av...

Page 22: ...sor or thermo stat Adjustable feet Protective magnesium anode Fitted thermal insulation made from rigid PU foam Colour of the epoxy coated sheet steel casing Vitosilver DHW cylinders with 160 200 and 300 litre capacity are also available in white Vitocell 100 V type CVA 500 litre capacity DHW cylinder made from steel with Ceraprotect enamel coating for DHW heating Welded in sensor well for cylinde...

Page 23: ...eating water flow rate stated below 90 C kW 32 36 57 l h 550 619 980 80 C kW 25 28 43 l h 430 481 739 70 C kW 16 19 25 l h 275 326 430 Heating water flow rate m3 h 3 0 3 0 3 0 for the stated continuous outputs Standby heat loss qBS at 45 K temperature dif ferential actual values to DIN 4753 8 kWh 24 h 1 30 1 40 1 60 Dimensions Length 7 a mm 633 633 633 Width b mm 667 667 667 Height c mm 1111 1203 ...

Page 24: ...m 892 984 1204 f mm 785 877 1097 g mm 155 155 155 h mm 77 77 77 Performance factor NL to DIN 4708 Cylinder storage temperature Tcyl cold water inlet temperature 50 K 5 K 0 K Cylinder capacity l 130 160 200 Performance factor NL at heating water flow temperature 90 C 2 4 3 3 6 8 80 C 1 9 2 9 5 2 70 C 1 4 2 0 3 2 Performance factor NL The performance factor NL varies according to the cylinder storag...

Page 25: ...ature 90 C 21 24 34 80 C 19 23 30 70 C 16 19 24 Available water volume Cylinder volume heated to 60 C Without booster Cylinder capacity l 130 160 200 Draw off rate l min 10 10 10 Available water volume Water with t 60 C constant l 103 120 150 Heat up time The quoted heat up times will be achieved if the max constant output of the DHW cylinder is made available at the respective flow temper ature a...

Page 26: ...p on the DHW side Delivered condition Vitocell 300 V type EVA peripheral indirect coil 130 to 200 litre capacity The DHW side of the DHW cylinder is made from high alloy stainless steel with fitted rigid polyurethane foam thermal insulation Integral welded sensor well for cylinder temperature sensor or con trol thermostat Integral thermometer Threaded adjustable feet Colour of the epoxy coated she...

Page 27: ...ghput for the stated continuous outputs m3 h 3 0 3 0 3 0 Standby heat loss qBS at 45 K temperature differential actual values to DIN 4753 8 kWh 24 h 1 20 1 30 1 50 Overall dimensions Total length d mm 907 1052 1216 Total width e mm 640 640 640 Total height f mm 654 654 654 Weight DHW cylinder with thermal insulation kg 90 103 116 Heating water content l 5 5 7 8 Heating surface m2 0 8 1 1 2 Connect...

Page 28: ...Tcyl Standard values Tcyl 60 C 1 0 NL Tcyl 55 C 0 75 NL Tcyl 50 C 0 55 NL Tcyl 45 C 0 3 NL Peak output over 10 minutes Relative to the performance factor NL and DHW heating from 10 to 45 C Cylinder capacity l 130 160 200 Peak output l 10 min at heating water flow temperature 90 C 159 199 246 80 C 159 199 246 70 C 148 173 210 Max draw off rate over 10 minutes Based on performance factor NL With boo...

Page 29: ... h Pressure drop in mbar A B A 130 litre cylinder capacity B 160 and 200 litre cylinder capacity Pressure drop on the DHW side 3 4 5 6 8 10 20 30 40 50 60 80 100 500 600 800 1000 2000 3000 4000 5000 6000 8000 10000 DHW throughput in l h Pressure drop in mbar Delivered condition Vitocell 100 H type CHA 130 160 and 200 litre capacity DHW cylinder made from steel with Ceraprotect enamel coating integ...

Page 30: ...from 10 to 45 C and saturated steam from with a max steam veloc ity of 50 m s 0 5 bar kW 83 83 l h 2039 2039 1 0 bar kW 105 105 l h 2580 2580 Standby heat loss qBS at 45 K tempera ture differential actual values to DIN 4753 8 kWh 24 h 1 20 1 30 1 90 2 30 Overall dimensions Total length mm 1072 1236 1590 1654 Total width mm 640 640 830 910 Width without casing mm 768 810 Total height mm 654 654 786...

Page 31: ...city Ø 64 221 c b 35 o m n g WW SPR HV HR h i k l f e a BÖ p KW Z d BÖ Inspection and cleaning aperture HR Heating water return HV Heating water flow KW Cold water SPR Connector R 1 with fem reducer to R for cylinder tempera ture sensor or control thermostat WW DHW Z DHW circulation Dimensions Cylinder capacity litres 350 500 a mm 786 886 b mm 716 795 c mm 830 910 d mm 1256 1320 e mm 1397 1461 f m...

Page 32: ... 182 240 424 583 Max draw off rate over 10 minutes Based on performance factor NL With booster DHW heating from 10 to 45 C Cylinder capacity litres 160 200 350 500 Max draw off rate litres minute at heating water flow temperature 90 C 20 33 45 66 80 C 20 29 45 62 70 C 18 24 42 58 Available water volume Cylinder volume heated to 60 C Without booster Cylinder capacity litres 160 200 350 500 Draw off...

Page 33: ...HA 160 and 200 litre capacity Vitocell 300 H type EHA 350 and 500 litre capacity DHW cylinders made from high alloy stainless steel fitted thermal insulation made from rigid polyurethane foam integral welded sensor well for cylinder temperature sensor or control thermostat integral thermometer and threaded adjustable feet Colour of the epoxy coated sheet steel casing Vitosilver DHW cylinders made ...

Page 34: ...ormation on drinking water filter According to DIN 1988 2 a drinking water filter should be installed in systems with metal pipework Viessmann and DIN 1988 also recom mend the installation of a drinking water filter when using plastic pipes to prevent contamination entering the DHW system The safety valve must be installed Recommendation Install the safety valve higher than the top edge of the cyl...

Page 35: ...bled unit and com pact design Low radiation losses through all round thermal insulation shells Low electricity costs and precise control characteristics through the use of high efficiency pumps and optimised mixer curve Also available with staged pumps The bypass valve for hydraulic balancing of the heating system is available as an accessory as a threaded component for inserting into the prepared...

Page 36: ...thout thermal insulation and with out mixer drive extension set HR Heating return HV Heating flow A Overflow valve accessory for multi stage circulation pump B Ball valves with thermometer as programming unit C Circulation pump D Bypass valve accessory E Three way mixer Heating circuit connec tion R 1 1 Flow rate max m3 h 1 0 1 5 2 5 a female Rp 1 1 a male G 1 1 2 b female Rp 1 1 b male G 1 1 2 In...

Page 37: ... pump D Ball valve Heating circuit connec tion R 1 1 Flow rate max m3 h 1 0 1 5 2 5 a female Rp 1 1 a male G 1 1 2 b female Rp 1 1 b male G 1 1 2 Installation example Divicon with triple manifold HV HR 120 120 120 b a d c 180 180 HV HR shown without thermal insulation HR Heating return HV Heating flow Dimensions Manifold with heating circuit connection R and R 1 R 1 a 135 183 b 535 583 c 784 784 d...

Page 38: ...5 1 kg 1 dm Select the smallest possible mixer within the application range with value Result of this example Divicon with three way mixer R Circulation pump curves and pressure drop on the heating water side The residual pump head results from the difference between the selec ted pump curve and the pressure drop curve of the respective heating circuit distributor or further components pipe assemb...

Page 39: ...th mixer B Divicon R 1 with mixer C Divicon R 1 with mixer D Divicon R R 1 and R 1 without mixer Grundfos VIUPS 25 40 Head min Head max A B C D 0 10 20 30 0 100 200 300 40 400 0 0 5 1 0 1 5 2 0 2 5 Pump rate in m h Pressure drop head mbar kPa A Divicon R with mixer B Divicon R 1 with mixer C Divicon R 1 with mixer D Divicon R R 1 and R 1 without mixer Grundfos VIUPS 25 60 Max head Min head 60 600 ...

Page 40: ... use of regulated pumps is also recommended for smaller capacities Design information The use of differential pressure regulated heating circuit pumps requires heating circuits with variable flow rate e g single line and twin line systems with thermostatic valves underfloor heating with thermostatic or zone valves Wilo Stratos Para 25 1 7 Very economical HE pump in accordance with Energy Label A O...

Page 41: ... D A B C E F G H K L M 40 0 10 20 30 0 100 200 300 400 0 0 5 1 0 1 5 2 0 2 5 Pump rate in m h Pressure drop head mbar kPa 50 500 60 600 A Divicon R with mixer B Divicon R 1 with mixer C Divicon R 1 with mixer D Divicon R R 1 and R 1 without mixer E Stage 1 F Stage 2 G Stage 3 H Min proportional pressure K Max proportional pressure L Min constant pressure M Max constant pressure Bypass valve Part n...

Page 42: ...ection option for expansion vessel HV Heating water flow HR Heating water return Part no 7466 337 for Divicon R 1 HV HR HV HR 120 495 HV HR 420 183 120 A 180 G 2 Rp G 2 A Connection option for expansion vessel HV Heating water flow HR Heating water return Pressure drop 0 0 0 5 1 1 5 2 Flow rate in m h 0 5 1 1 5 2 3 2 5 3 5 2 5 Pressure drop kPa A B A Manifold for Divicon R and R 1 B Manifold for D...

Page 43: ...r expansion vessel HV Heating water flow HR Heating water return Pressure drop 0 0 0 5 1 1 5 2 Flow rate in m h 0 5 1 1 5 2 3 2 5 3 5 2 5 Pressure drop kPa 4 4 5 5 4 5 5 5 A B A Manifold for Divicon R and R 1 B Manifold for Divicon R 1 Wall mounting bracket Part no 7465 894 for individual Divicon With screws and dowels a for Divicon with mixer without mixer a mm 151 142 Part no 7465 439 for manifo...

Page 44: ... 15 to 40 kW Part no 7143 780 for 50 and 63 kW 232 80 144 with safety valve R or R blow off pressure 3 bar with pressure gauge with automatic air vent valve with automatic shut off facility incl thermal insulation Plinth for Vitogas 200 F Height 250 mm Part no 7196 461 for 11 to 22 kW Part no 7196 462 for 29 to 35 kW Part no 7196 463 for 42 to 60 kW Plinth for Vitogas 100 F Height 250 mm Part no 7...

Page 45: ...ng pressure and max 2700 kW rated output D G H for all other operating conditions 5 5 Thermal safety shut off valve According to paragraph 4 section 5 of the FeuVo 96 or local regula tions thermally activated shut off equipment must be installed in com bustion equipment or in gas lines immediately upstream of the com bustion equipment which will shut off the gas supply if the external temperature ...

Page 46: ...0 Low water indicator According to the EN 12828 special low water level protection can be omitted for boilers up to 300 kW as long as heating can be reliably prevented when the water level is too low Viessmann Vitogas are equipped with type tested thermostats and high limit safety cut outs Tests have verified that the burner will be automatically switched OFF in the event of water shortage due to ...

Page 47: ...h with individual and seven day programs With cylinder thermostat With integral diagnostic system Vitotronic 200 type KW4 Weather compensated digital boiler control unit For single boiler systems For one heating circuit without mixer With cylinder thermostat With digital time switch with individual and seven day programs With separate switching times for central heating DHW heating and the DHW cir...

Page 48: ...00 150 200 Type KC3 KC4 KB2 KW4 KW5 Components Boiler water temperature sensor x x x x x Cylinder temperature sensor x x x x Outside temperature sensor x x Boiler water temperature sensor Specification Lead length 1 6 m fully wired IP rating IP 32 to EN 60529 ensure through appropriate design and installation Sensor type Viessmann Pt500 Permissible ambient temperature during operation 0 to 130 C d...

Page 49: ...rature limit 75 C adjustable to 87 C or 95 C Adjusting the high limit safety cut out 110 C adjustable to 100 C Specification Rated voltage 230 V Rated frequency 50 Hz Rated current 6 A Protection class I IP rating IP 20 D to EN 60529 ensure through design installation Function Type 1B to EN 60730 1 Permissible ambient temperature during operation 0 to 40 C use in the living space or boiler room st...

Page 50: ...ly with auxiliary module part of the standard delivery for Viessmann boil ers 1 0 5 A 230 V Total 6 A 230 V Delivered condition Boiler water temperature sensor Cylinder temperature sensor Bag with technical documentation Heating system with DHW cylinder Order the circulation pump with check valve for cylinder temperature control separately 6 5 Vitotronic 150 type KB2 part no 7186 570 Specification...

Page 51: ...0 V Rated frequency 50 Hz Rated current 6 A Power consumption 5 W Protection class I IP rating IP 20 D to EN 60529 ensure through appro priate design installa tion Function Type 1B to EN 60 730 1 Permissible ambient temperature during operation 0 to 40 C Installation in living spaces or boiler rooms standard ambient con ditions during storage and transport 20 to 65 C Rated capacity of the relay ou...

Page 52: ...ckup 5 years Setting heating programs The heating system frost protection see frost protection function applies to all heating programs You can select the following operating programs with the program keys Heating and DHW Only DHW Standby mode External heating program changeover via control module V Summer mode DHW only The burner starts only when the DHW cylinder needs reheating con trolled by th...

Page 53: ...it safety cut out DIN STB 106005 or DIN STB 98108 or DIN STB 116907 Operation and fault displays Plug connection chamber Connection of external equipment via a system plug Connection of three phase consumers via additional contactors Programming unit With digital time switch Backlit display with plain text user prompts Adjustment and display of temperatures and codes Fault message display Rotary s...

Page 54: ... the outside tem perature drops below approx 1 C With active frost protection the heating circuit pumps are switched ON and the boiler water is maintained at the set value for reduced mode i e at a low end temperature of approximately 20 C The allocated temperature is maintained for boilers with a low end tem perature limit The frost protection function is stopped when the outside tempera ture ris...

Page 55: ...dio clock receiver x x x Function extension 0 10 V x x Ext Extension H5 x x x x Vitocom 100 x x x Control module V x x Extension kit for one heating circuit with mixer Part no 7450 650 Components Mixer motor with connecting cable Plug for the heating circuit pump and flow temperature sensor con tact temperature sensor The mixer motor is mounted directly onto the Viessmann mixer DN 20 to 50 and R t...

Page 56: ...ow temperature sensor immersion sensor Specification Lead length 4 0 m fully wired IP rating IP 32 to EN 60529 ensure through appropriate design and installation Sensor type Viessmann Ni500 Permissible ambient temperature during operation 0 to 120 C during storage and transport 20 to 70 C Contact temperature sensor Part no 7183 288 For capturing the flow and return temperature 4 0 4 2 76 Specifica...

Page 57: ...ller With switching output two point output With digital time switch With individual and seven day programs Programming unit with user prompts 3 preselected time programs individually adjustable Constant manual mode with adjustable set room temperature Frost protection mode Holiday program With selector keys for party and economy mode Installation in the main living room on an internal wall opposi...

Page 58: ...the control unit plus an additional 2 core cable for the 230 V power supply 130 2 9 130 3 0 80 80 Specification room temperature controller Rated voltage 3 V Transmission frequency 868 MHz Transmission 10 mW Range approx 25 to 30 m inside buildings subject to construc tion IP rating IP 20 to EN 60529 ensure through appropriate design installation Function RS Type 1B to EN 60730 1 Permissible ambie...

Page 59: ...re for reduced mode is adjusted at the control unit Vitotrol 300 Part no 7248 907 KM BUS subscriber The Vitotrol 300 remote control regulates the required set room tem perature for one heating circuit in standard and reduced mode the heating program and the switching times for central heating DHW heating and the DHW circulation pump The Vitotrol 300 provides a backlit display as well as backlit he...

Page 60: ...ecification Lead length 3 0 m fully wired Protection IP 32 to EN 60529 safeguard through appro priate design and installa tion Permissible ambient temperature during operation 0 to 40 C during storage and transport 20 to 65 C Flue gas temperature sensor Part no 7450 630 For scanning the flue gas temperature flue gas temperature monitor ing and maintenance indication if the set temperature has been...

Page 61: ...ard through appro priate design and installa tion Permissible ambient temperature during operation 0 to 40 C during storage and transport 20 to 65 C Functions in connection with the function extension 0 10 V accessory 0 10 V input aVF Defaulting an additional set boiler water temperature Switching output aBJ zero volt contact Night contact to signal reduced mode and to regulate the heating circuit...

Page 62: ...ign and installation Function Type 1B to EN 60 730 1 Permissible ambient temperature during operation 0 to 55 C Installation in living spaces or boiler rooms standard ambi ent conditions during storage and transport 20 to 85 C On site connection Fault input DE 1 230 V Control module V Part no 7143 513 KM BUS user may only be used as an alternative to the function extension 0 10 V The following fun...

Page 63: ...lastic pipework 45 R Room temperature controller 57 58 Room temperature sensor 60 Room thermostat 57 58 S Safety assembly to DIN 1988 35 T Temperature sensor Outside temperature 48 Room temperature 60 Thermostat Contact temperature 57 Immersion temperature 56 Time switch 52 54 U Underfloor heating systems 45 V Vitocom 100 type GSM 62 Vitotrol 200 59 300 59 UTDB 57 UTDB RF 58 Keyword index VITOGAS ...

Page 64: ...ached paper Subject to technical modifications Viessmann Limited Hortonwood 30 Telford Shropshire TF1 7YP GB Telephone 44 1952 675000 Fax 44 1952 675040 E mail info uk viessmann com Viessmann Werke GmbH Co KG D 35107 Allendorf Telephone 49 6452 70 0 Fax 49 6452 70 2780 www viessmann com ...