Family Aqua Condens 3.5 BIS
28
TECHNICAL DATA
DESCRIPTION
FAMILY AQUA CONDENS 3.5 BIS
UM
Fuel
G20
G31
Appliance category
●
Country of destination
II2H3P
● (+)
Type of appliance
B23P-B53P-C13,C13x-C33,C33x-C43,C43x-
C53,C53x-C83,C83x-C93,C93x
Heating
Nominal heat input
34,60
kW
Nominal heat output (80°/60°)
33,74
kW
Nominal heat output (50°/30°)
36,50
kW
Reduced heat input
3,50
6,20
kW
Reduced heat output (80°/60°)
3,41
6,04
kW
Reduced heat output (50°/30°)
3,71
6,57
kW
Nominal Range Rated thermal output (Qn)
34,60
kW
Minimum Range Rated thermal output (Qm)
3,50
6,20
kW
Domestic hot water
Nominal heat input
34,60
kW
Nominal heat output (*)
34,60
kW
Reduced heat input
3,50
6,20
kW
Reduced heat output (*)
3,50
6,20
kW
Useful efficiency Pn max - Pn min (80°/60°)
97,5-97,3
%
Useful efficiency 30% (47° return)
103,1
%
Combustion efficiency
97,7
%
Useful efficiency Pn max - Pn min (50°/30°)
105,5-105,9
%
Useful efficiency 30% (30° return)
108,0
%
Efficiency at average Pn Range Rated (80°/60°)
97,6
%
Efficiency at average Pn Range Rated (50°/30°)
106,1
%
Residual discharge head of boiler without pipes
199
Pa
Mass flue gas flow rate maximum output
15,614
15,288
g/s
Mass flue gas flow rate minimum output
1,498
2,740
g/s
Air capacity
43,090
43,945
Nm
3
/h
Flue gas capacity
46,561
45,286
Nm
3
/h
Air excess index ( ) maximum output
1,304
1,376
Air excess index ( ) minimum output
1,235
1,376
CO
2
at maximum**/minimum**
9,00/9,50
10,00/10,00
%
CO S.A. at maximum**/minimum** lower than
180/10
200/15
ppm
NOx S.A. at maximum**/minimum** lower than
35/15
35/15
ppm
Flue gases temperature (maximum/minimum output)
74/62
77/62
°C
NOx class
6
Heating operating
Heating maximum operating pressure
3
bar
Minimum pressure for standard operation
0,25 - 0,45
bar
Maximum permissible temperature
90
°C
Selection field of the domestic hot water temperature (± 3°C)
20 - 80
°C
Electrical supply
230 - 50
Volt-Hz
Maximum electrical power consumption
107
W
Circulator electrical power (1.000 l/h) (max - min)
39 - 4
W
Pump head available to the system
237
mbar
for system capacity
1.000
l/h
Electrical protection level
X5D
IP
Expansion tank
10
l
Expansion tank pre-charge
1
bar
DHW operating
Maximum - minimum pressure
8 - 0,15
bar
Hot water quantity with ∆t 25°C
19,8
l/min
Hot water quantity with ∆t 30°C
16,5
l/min
Hot water quantity with ∆t 35°C
14,2
l/min
Selection field of the DHW temperature
35 - 60
°C
Flow limiter
15
l/min
DHW minimum capacity
2
l/min
(+) The installation of this product is allowed only in the destination Countries contained in the data plate, regardless of the present translation language.
(*) Average value of various hot water operating conditions.
(**) Check performed with concentric pipe Ø 60-100 - length 0.85m - water temperature 80-60°C.