Family Aqua Condens 3.5 BIS
16
Code
Fault description
RESET
icon
Icon
27
RETURN PROBE LIMIT TEMPERATURE (T)
NO
YES
28
RETURN-DELIVERY PROBE
DIFFERENTIAL (D)
YES
YES
29
FLUE GAS PROBE OVER-
TEMPERATURE (D)
YES
YES
34
FAN (cycle start) (D)
AIR PRESSURE SWITCH ALARM
YES
NO
37
FAN CYCLE IN PROGRESS (high rpm) (D)
YES
YES
40
INSUFFICIENT SYSTEM PRESSURE (D**)
YES
NO
41
INSUFFICIENT SYSTEM PRESSURE (T**)
NO
YES
42
WATER PRESSURE TRANSDUCER (D)
YES
YES
50-59
ELECTRONIC CARD (D)
YES
YES
60
DHW PROBE 1 (T) (°)
NO
YES
65
MINI-ACCUMULATION ALARM
(NOT DISPLAYED ON THIS MODEL)
YES
YES
70
PRIMARY PROBE SHORT
CIRCUIT/OPEN (D)
YES
YES
71
DELIVERY PROBE OVER-
TEMPERATURE (T)
NO
NO
72
RETURN PROBE SHORT CIRCUIT/OPEN (D)
YES
YES
75
SECOND HEATING SYSTEM
PROBE ABSENT
NO
YES
77
LOW TEMPERATURE THERMOSTAT (T)
NO
YES
78
DELIVERY/RETURN DIFFERENTIAL (T)
NO
YES
79
DELIVERY/RETURN DIFFERENTIAL (D)
YES
NO
80
SYSTEM FAULT (D)
YES
YES
81
SYSTEM FAULT (T)
NO
YES
82
SYSTEM FAULT (D)
YES
YES
83
SYSTEM FAULT (T)
NO
YES
89
STOP SIGNAL SENT TO THE OT DEVICES
-
-
91 (-) PRIMARY HEAT EXCHANGER CLEANING (-)
NO
YES
J0
CONNECTION FAILURE BETWEEN
INTERFACE AND MAIN CARD
-
-
J1
CONNECTION FAILURE WITH THE
REMOTE CONTROL PANEL
-
-
(D) Definitive
(T) Temporary. In this operating status, the boiler attempts to resolve
the fault situation autonomously
(°) See the NOTE on the previous page
(**) If these two errors arise, check the pressure shown on the
hydrometer.
If the pressure is insufficient (< 0.4 bar - red field), perform the
filling operations described in the “Filling and draining the systems”
chapter.
If the system pressure is sufficient (> 0.6 bar - light blue field), the
fault is due to a lack of circulating water. Contact the Technical
Assistance Centre.
(-) Contact the Technical Assistance Centre.
4.7
Temporary switch-off
In the event of a temporary absence, weekends, short journeys and
so on: press . The display will visualise the words “ENERGY FOR
LIFE” and the anti-freeze icon.
In this way (leaving the electricity and fuel supplies enabled),
the boiler is protected by the following systems:
-
Antifreeze
: when the boiler water temperature falls to 7°C, the
circulator is activated and, if necessary, also the burner (at the
minimum output) to bring the water temperature back within the
safety values (35°C). The icon will flash on the display, indicating
that the anti-freeze function is active.
-
Circulator anti-locking
: an operation cycle is activated every 24 h.
4.8
Switching off for long periods
The long term non use of the
Family Aqua Condens 3.5 BIS
boiler
causes the execution of the following operations:
- press . The wording “ENERGY FOR LIFE” and the antifreeze
icon are displayed
- set the system's main switch to "off"
- turn off the fuel and water taps of the heating and domestic hot
water system.
In this case, the anti-freeze and anti-blocking systems are
deactivated.
Drain the heating and domestic water system if there is any risk
of freezing.
4.9
Maintenance
Periodic maintenance is an “obligation” required by law and is
essential to the safety, efficiency and lifetime of the boiler.
It allows for the reduction of consumption, polluting emissions and
keeping the product reliable over time.
Before starting maintenance operations:
- perform the analysis of the combustion products to check the boiler
operation status then cut the electrical supply by turning off the
system’s general switch
- close the fuel and water taps of the heating and domestic hot water
system.
The appliance must be systematically controlled at regular intervals
to make sure it works correctly and efficiently and conforms to
legislative provisions in force. The frequency of controls depends on
the conditions of installation and usage, it being anyhow necessary
to have a complete check carried out by authorized personnel from
the Servicing Centre every year.
- Check and compare the boiler’s performance with the relative
specifications. Any cause of visible deterioration must be
immediately identified and eliminated.
- Closely inspect the boiler for signs of damages or deterioration,
particularly with the drainage and aspiration system and electrical
apparatus.