TECHNICAL ASSISTANCE SERVICE
62
Nr.
Characteristic
Range
U/M
Default
setting
558 Parameter with 8 bits (= b7b6b5b4b3b2b1b0)
b0= PARAMETER FIXED IN THIS MODEL
DO NOT CHANGE SETTING.
0
b1=Type of building
0/1=Light/heavy duty
0
b2=Connection of storage cylinder temperature sensor
b2=1-------> Termostato bollitore (*)
b2=0-------> Sonda
1
b3= PARAMETER FIXED IN THIS MODEL
DO NOT CHANGE SETTING.
0
b4= PARAMETER FIXED IN THIS MODEL
DO NOT CHANGE SETTING.
0
b7b6b5= PARAMETER FIXED IN THIS MODEL
DO NOT CHANGE SETTING.
0 1 0
596 PARAMETER FIXED IN THIS MODEL
DO NOT CHANGE SETTING.
s
120
604 Parameter with 8 bits (= b7b6b5b4b3b2b1b0)
0…255
b1b0=Functioning of control board or local/system time
00=Independent
01=Slave without remote adjustment
10=System master time
00
b2=LPB bus distributed power
0=bus distributed power OFF
1=AUTOMATIC bus distributed power
0
b3=LPB bus distributed power status
0=bus distributed power OFF
1=bus distributed power ON
1
b4=Storage of LPB bus events in non-volatile memory
0=Not permitted
1=Permitted
0
b6b5=DHW filled from own circuit, own section, system
00=Local
01=Section
10=System
00
b7=Priority required for accessory controller over other predefined
external output
0/1=priority no/yes
0
605 LPB address
1
606 LPB section
0
608 PARAMETER FIXED IN THIS MODEL
DO NOT CHANGE SETTING.
48,5
(TAU 55)
-
34
(TAU 75)
-
25
(TAU 110)
609 PARAMETER FIXED IN THIS MODEL
DO NOT CHANGE SETTING.
13,5
(TAU 55)
-
15,5
(TAU 75)
-
12
(TAU 110)
610 PARAMETER FIXED IN THIS MODEL
DO NOT CHANGE SETTING.
88
(TAU 55)
-
71
(TAU 75)
-
62,5
(TAU 110)
611 PARAMETER FIXED IN THIS MODEL
DO NOT CHANGE SETTING.
4000
(TAU 55)
-
3500
(TAU 75)
-
3100
(TAU 110)
612 PARAMETER FIXED IN THIS MODEL
DO NOT CHANGE SETTING.
1300
(TAU 55)
-
1300
(TAU 75)
-
1500
(TAU 110)
613 PARAMETER FIXED IN THIS MODEL
DO NOT CHANGE SETTING.
5300
(TAU 55)
-
5500
(TAU 75)
-
6200
(TAU 110)
618 PARAMETER FIXED IN THIS MODEL
DO NOT CHANGE SETTING.
0
619 PARAMETER FIXED IN THIS MODEL
DO NOT CHANGE SETTING.
0
620 PARAMETER FIXED IN THIS MODEL
DO NOT CHANGE SETTING.
0
621 PARAMETER FIXED IN THIS MODEL
DO NOT CHANGE SETTING.
0
(*) Storage cylinder not connected or with own thermostat: set to 1. Storage cylinder with temperature sensor: set to 0.
If a thermostat is connected to the input terminal of the storage cylinder temperature sensor, top quality contacts
(e.g. gold contacts) must be used.