TECHNICAL ASSISTANCE SERVICE
55
Error
code via
QAA
Diagnostic
info
Description of error
Type of fault
System action
Procedure
132
93
Gas feed pressure
switch (GPS) tripped
The pressure switch
input has been
configured as a switch
that prevents start-up
(FaEinstellFlags2) and
the switch is open during
safety time
Safety shutdown
Check for blockages in
the air/gas feed lines;
check the pressure
switch
132
94
Gas feed pressure
switch (GPS) tripped
The pressure switch
input has been
configured as a switch
that prevents start-up
(FaEinstellFlags2) and
the switch is open during
safety time. Start-up
prevented for two hours
Safety shutdown
Check for blockages in
the air/gas feed lines;
check the pressure
switch
132
285
Gas feed pressure
switch (GPS) tripped
Shutdown at wrong time.
The error masking time
has been interrupted
Safety shutdown
Check for blockages in
the air/gas feed lines;
check the pressure
switch
133
101
No flame
The flame does not
appear at the end of the
safety time--> Repetition
Safety shutdown
Check the connections
to the burner
133
102
No flame
The flame does not
appear at the end of the
safety time
Burner lockout
(permanent). Lockout
reset required
Check the connections
to the burner
140
521
Illegal LPB address
Illegal segment number
or LPB device number
Message
Contact Technical
Assistance Service
148
517
Interface/base unit LPB
incompatibility
LPB incompatibility
between interface unit
and base unit
Message
Contact Technical
Assistance Service
151
1
Internal control board
error
Software error or internal
error
Can be a Message or
a Safety Shutdown or
a (permanent) burner
lockout with manual reset
request
Contact Technical
Assistance Service
151
…
Internal control board
error
Software error or internal
error
Can be a Message or
a Safety Shutdown or
a (permanent) burner
lockout with manual reset
request
Contact Technical
Assistance Service
151
632
Internal control board
error
Software error or internal
error
Can be a Message or
a Safety Shutdown or
a (permanent) burner
lockout with manual reset
request
Contact Technical
Assistance Service
152
6
Parameter setting error
Wrong setting
Can be a Message or
a Safety Shutdown or
a (permanent) burner
lockout with manual reset
request
Contact Technical
Assistance Service
152
…
Parameter setting error
Wrong setting
Can be a Message or
a Safety Shutdown or
a (permanent) burner
lockout with manual reset
request
Contact Technical
Assistance Service
152
610
Parameter setting error
Wrong setting
Can be a Message or
a Safety Shutdown or
a (permanent) burner
lockout with manual reset
request
Contact Technical
Assistance Service
153
259
Lockout caused by unit Generic error or internal
error
Burner lockout
(permanent). Lockout
reset required
Undefined software error.
Reset the control card
154
400
Generic error
The boiler return
temperature is above the
safety threshold (boiler
tempe Sd_RL_
groesser_VL)
Safety shutdown
OEM parameter not
editable via QAA.
Generic error. Check
the system. Return
temperature too high