TECHNICAL ASSISTANCE SERVICE
40
If a remote storage cylinder (accessory) is present,
connect the storage cylinder temperature sensor to the
control panel and set the manufacturer level parameter
“558b2”=0 (see the “Manufacturer level” section).
- Press the
R
key.
Press the
+
-
keys to adjust the setpoint.
Press any of the keys to exit
R
T
M
V
.
The new setting is stored in memory.
If the remote storage cylinder has its own thermostat,
leave the manufacturer level parameter “558b2” = 1 (see
the “Manufacturer level” section). .
- If an outdoor temperature sensor is installed, set
installer parameter “532 Heating curve slope heating
circuit 1” as instructed in the section “Setting function-
ing parameters”.
If any boiler ignition or functioning errors are detected,
the display shows the type of error.
Errors can be of two types:
- PERMANENT errors are those that can only be can-
celled by pressing the
S
key.
- TRANSIENT errors are those that are automatically
cancelled as soon as the cause is rectified (see “Error
codes” on page 52).