0ML190480RUENUC
page 7 / 24
The life expectancy of batteries is temperature dependence at which they are stored
and operated. Batteries should be used in a 70 F (21 C) environment. Consider that
for every 15 F (8.3 C) increase in temperature, the life expectancy is halved.
Exposure to temperatures in excess of 90 F (32 C) should be limited to no more than
30 days per year. Under no circumstances should the battery be exposed to
temperatures over 104 F (40 C) which can lead to thermal runaway, a condition that
damages the battery. Thermal runaway can cause batteries to swell and if the battery
body burst, the hazardous contents may be exposed.
MAINTAINING PROPER AMBIENT TEMPERATURE USUALLY REQUIRES
INSTALLING THE PRODUCT IN A TEMPERATURE CONTROLLED SPACE.
EQUIPMENT ROOMS WITHOUT COOLING SYSTEMS DO NOT GENERALLY
MAINTAIN THE PROPER CONDITIONS FOR GOOD BATTERY LIFE.
Summary of Contents for MASTER HP
Page 1: ...UNINTERRUPTIBLE POWER SUPPLY MASTER HP UL 55 100Ah BATTERY CABINET User Manual ...
Page 2: ...0ML190480RUENUC page 2 24 RPS SpA Viale Europa 7 37045 Legnago VR Italy www riello ups com ...
Page 17: ...0ML190480RUENUC page 17 24 ...
Page 18: ...0ML190480RUENUC page 18 24 ELECTRICAL DRAWING ...
Page 20: ...0ML190480RUENUC page 20 24 ...
Page 21: ...0ML190480RUENUC page 21 24 ...
Page 23: ...0ML190480RUENUC page 23 24 Fig 14 battery cabinet terminal block detail ...
Page 24: ...0ML190480RUENUC page 24 24 Fig 15 Connections diagram of auxiliary signals ...