6
Dip Switch 7
ON: Lighting control
OFF: Load Control
OFF:
Lights remain turned off.
2,4,6,8,10:
Hours light is turned on after sunset.
2/1, 3/1, 4/1,
6/1, 2/2, 3/2,
4/2, 6/2,
8/2:
Light is turned on after sunset, turned off after the selected
lasting hours, and turned on again before sunrise.
2/1: Light is turned on for two hours after sunset, turned off
after two hours and turned on again one hour before sunrise.
Lighting control
Switch
D/D:
Dusk-to-Dawn, light is on all night
Remote Panel
Connecting port for the optional LCD remote panel for SW-30CL model
BVS + /
–
Connecting terminal for Battery Voltage Sensor to compensate for voltage
loss due to cable resistance.
BTS
Battery Temperature Sensor is built in SunWide for temperature
compensation
LED Status Indicators
Charge Status LED
Blinking Green:
Charging is in the state of Bulk or Absorption
Solid Green:
Charging is in the state of Float
Solid Orange:
Charging in the state of Equalization
Solid Red:
Charging in the state of fault: Over Current
Blinking Red:
Charging in the state of fault: Over Temp.
Load Status LED
Blinking Green:
If the battery charge state falls below the disconnect setpoint voltage (Initial
setting: 11.1V for 12V system, 22.2V for 24V system and 44.4V for 48V
system) lasting for six minutes, the green LED will blink to be ready for load
disconnection.
Solid Orange:
After six minutes of battery voltage under setpoint, the orange LED will lit to
show the low voltage disconnection for loads.
Blinking Orange:
When the battery voltage recovers to above the reconnect setpoint (Initial
setting: 12.6V for 12V system, 25.2V for 24V system and 50.4V for 48V
system), the orange LED will blink to be ready for reconnection for six
minutes.
Solid Green:
Battery discharges to DC load; after six minutes of reconnection process, the
green LED will be lit to show battery successfully discharges to DC load
Solid Red:
Load control in fault: Load Over Current
Blinking Red:
Load control in fault: Over Temperature