2-5 Troubleshooting 

The SunWide is very rugged and designed for the most extreme operating conditions. 
Most PV system problems will be caused by connections, voltage drops, and loads. 
Troubleshooting the SunWide controller is simple. Some basic troubleshooting 
procedures are listed below. 
 
CAUTIONS:  
1. Troubleshooting should be done by qualified personnel only. 
2. Remember that a battery can cause serious damage if shorted. 
3. There are no user serviceable parts, fuses or circuit breakers inside the SunWide. 
4. Observe all normal precautions when working with energized circuitry. 
 

1. BATTERY IS NOT CHARGING 

z

 

Check the green LED indicator. The green CHARGING LED should be on if it is 
daytime. 

z

 

Check that the proper battery charging has been selected by DIP Switches. 

z

 

Check that all wire connections in the system are correct and tight. Check the 
polarity (+ and –) of the connections. 

z

 

Measure the PV array open-circuit voltage and confirm it is within normal limits. If 
the voltage is low or zero, check the connections at the PV array itself. Disconnect 
the PV from the controller when working on the PV array. 

z

 

Check that the load is not drawing more energy than the PV array can provide. 

z

 

Check if there are excessive voltage drops between the controller and the battery. 
This will cause undercharging of the battery. 

z

 

Check the condition of the battery. Determine if the battery voltage declines at 
night with no load. If unable to maintain its voltage, the battery may be failing. 

z

 

Measure the PV voltage and the battery voltage at the SunWide terminals. If the 
voltage at the terminals is the same (within a few tenths of volts) the PV array is 
charging the battery. If the PV voltage is close to the open circuit voltage of the 
panels and the battery voltage is low, the controller is not charging the batteries and 
may be damaged. 

 

2. BATTERY VOLTAGE IS TOO HIGH 

z

 

First check the operating conditions to confirm that the voltage is higher than 
specifications.  

z

 

Check that the proper battery charging has been selected by DIP Switches. 

z

 

Check that all wire connections in the system are correct and tight. 

z

 

Disconnect the PV array and momentarily disconnect the lead from the BATTERY 
positive terminal. Reconnect the battery terminal and leave the PV array 
disconnected. The Green charging light should not be lit. Measure the voltage at the 
SOLAR terminals (with the array still disconnected). If the Green charging light is 
on or battery voltage is measured at the SOLAR terminals, the controller may be 
damaged. 

 
3. LOAD NOT OPERATING PROPERLY 

z

 

Press the LIGHT TEST button to turn the lights on. This will assist in 

Summary of Contents for SW-10CL

Page 1: ...INVERTEK SUNWIDE SERIES SW 10CL SW 20CL SW 30CL SW 45CL Installation and Operation Manual Solar Battery Charging Load Control Lighting Control MANUAL VER 2 1008 RICH ELECTRIC CO LTD...

Page 2: ...working with batteries Lead acid batteries can generate explosive gases and short circuits can draw thousands of amps from the battery Read all instructions provided with the battery z Do not exceed...

Page 3: ...r 12V system Twice or four times of 12V is for 24V and 48V system LVR 12 6V initial setting User select 12 0 12 8V 13 0V 13 2V 13 4 13 6 13 8 for 12V system Twice or four times of 12V is for 24V and 4...

Page 4: ...F 2 4 6 8 10 2 1 3 1 4 1 6 1 2 2 3 2 4 2 6 2 8 2 D D SOLAR BATTERY LOAD Normal Voltages 12V 24VDC R ABSOR Length Model L L1 SW 10CL SW 20CL 168 mm 161 mm SW 30CL 236 mm 229 mm 1 5 RP SW Remote Panel D...

Page 5: ...ing terminal for Battery cable Positive Battery Connecting terminal for Battery cable Negative Load Light Connecting terminal for DC Load Light Positive Load Light Connecting terminal for DC load Ligh...

Page 6: ...Float Solid Orange Charging in the state of Equalization Solid Red Charging in the state of fault Over Current Blinking Red Charging in the state of fault Over Temp Load Status LED Blinking Green If t...

Page 7: ...charge battery load control state PUSH Manual Equalize LVR When there is a fault occurring push Manual Equalize LVR to reset it HOLD Manual Equalize LVR Battery charge control mode Hold Manual Equaliz...

Page 8: ...Make sure the PV and load currents will not exceed the ratings of the SunWide model being installed 3 The connections to the SunWide terminals are shown in the panel drawing SunWide SW 30CL CHARGE LOA...

Page 9: ...ight Also be careful not to shortcircuit the PV array while connected to the controller since this will damage the controller 6 Connect the LIGHT last If the red LED indicator lights the battery capac...

Page 10: ...night and measure the length of night at different time and area zone The desired lighting hours can be set for the precise control to turn on and turn off the light in order to achieve power saving...

Page 11: ...further heating or gassing of the battery Battery Charging Notes The SunWide manages many different charging conditions and system configurations Some useful functions to know follow below Solar Overl...

Page 12: ...ff on 2 Sealed 14 1 13 4 14 2 1 28 off on off 3 Sealed 14 3 13 4 14 4 2 28 off on on 4 Flooded 14 4 13 4 15 1 3 28 on off off 5 Flooded 14 6 13 4 15 3 3 28 on off on 6 Flooded 14 8 13 4 15 3 3 28 on o...

Page 13: ...not be recharged with a limited solar resource If the battery temperature rises the battery may heat and gas too much Equalization A colder battery will lose part of the benefit of the equalization A...

Page 14: ...qualization at a higher voltage can reverse the hardening sulfate crystals In addition to slowing or preventing lead sulfation there are also other benefits from equalizations of the solar system batt...

Page 15: ...ions in both the manual and automatic mode Typical Equalizations The automatic equalizations will occur at the selected charging program from Dip Switch 3 5 When an equalization begins auto or manual...

Page 16: ...low rate of maintenance charging while reducing the heating and gassing of a fully charged battery When the battery is fully recharged there can be no more chemical reactions and all the charging cur...

Page 17: ...D LVR LVD Voltage System 12V 24V 48V 12V 24V 48V Red Red 12 6 25 2 50 4 11 1 22 2 44 4 Red Green 12 8 25 6 51 2 11 3 22 6 45 2 Green Red 13 0 26 0 52 0 11 5 23 0 46 0 Green Green 13 2 26 4 52 8 11 7 2...

Page 18: ...is correctly connected LEDs are on the load should be connected very carefully with regard to polarity If the polarity is reversed the controller cannot detect this There are no indications Loads wit...

Page 19: ...rned off after the selected lasting hours and turned on again before sunrise 2 1 Light is turned on for two hours after sunset turned off after two hours and turned on again one hour before sunrise Li...

Page 20: ...alse transitions due to lightning or dark storm clouds Measure Night Length The LIGHTING CONTROL options that turn the lights on again before sunrise require that the SunWide measure the length of the...

Page 21: ...excessive voltage drops between the controller and the battery This will cause undercharging of the battery z Check the condition of the battery Determine if the battery voltage declines at night wit...