34

POINT B - SETTINGS  

DIP 1 

MAINTENANCE CHECK (See Page 36)

DIP 2 

PROGRAMMING (See Point C)

DIP 2-1  PROGRAMMING OF PEDESTRIAN OPENING (See Point D)
DIP 1-2   SAVE/DELETE RADIO CODES FOR COMPLETE OPENING (DIP 1 ON followed 

by DIP 2 ON) (POINT E)

DIP 1-3   SAVE/DELETE RADIO CODES FOR PEDESTRIAN OPENING (DIP 1 ON 

followed by DIP 3 ON) (POINT F)

DIP 1-2-3 SAVE/DELETE RADIO CODES FOR RELAY R-AUX COMMAND (point G)

DIP SWITCHES CONTROL
DIP 4

 

 Photocells always active (OFF) - Photocells active only during closing (ON)

DIP 5

 

Pre-blinking (ON) - Normal blinking (OFF)

DIP 6

 

 Single pulse command (START) and RADIO - step-by-step (ON) - automatic (OFF)

DIP 7

 

Photocells AUTO-TEST activation (ON-activated).

DIP 8-9-10-11

 

IS NOT AVAILABLE

DIP 12

  Activate the radio system SUN/MOON (ON) - SUN-PRO (OFF)

DIP 13

   Contactors management (ON - activated) - NOTE: Even if enabled, DIPs 8-9-10-11 

are excluded from their operation

DIP 14-15-16

 

IS NOT AVAILABLE

TORQUE TRIMMER - Electronic regulator for motor torque 

IS NOT AVAILABLE  

LOW SPEED TRIMMER - Electronic regulator for low speed on approach  

IS NOT AVAILABLE

TCA TRIMMER - AUTOMATIC CLOSING pause time regulator for TOTAL or PEDESTRIAN 
openings
default NOT ACTIVATED and LED DL11 OFF  (trimmer fully rotated counterclockwise)

This trimmer makes it possible to adjust the pause time for total or pedestrian automatic 
closing. Only with gate completely open (total) or partially open (pedestrian) and LED DL11 
ON (trimmer rotated clockwise to activate the feauture). 
The pause time (for a totally opened gate) can be adjusted from a minimum of 2 s up to a 
maximum of 2 minutes.
The pause time (for gate open with PED. control) can be adjusted from a minimum of 2 
seconds to a maximum of 30 seconds.
Ex:  With TCA trimmer setted halfway, you will have 1 minute pause after the total opening 

and 15 seconds of pause after the pedestrian opening prior to have the auto-close of 
the gate.

R-AUX - AUXILIARY RELAY CONTACT (NO)

By default this relay is set as courtesy light (max 700 W - 3 A - 230 Vac) to operate 3 minutes 
at each command, with time renewed at each command.
You can activate the R-AUX contact by TRANSMITTER by performing the memorization 
procedure described in point G.

ELECTRONIC BRAKE 

IS NOT AVAILABLE

GRADUAL START

IS NOT AVAILABLE

LED WARNINGS  

DL1  PROG programming activated  

(red)

DL2  Gate opening  

(green)

DL3  Gate closing  

(red)

DL4  Opening limit switch LSO 

(green)

DL5  Closing limit switch LSC 

(red) 

DL6  STOP command (NC)  

(red)

DL7  PHOTO 1 contact (NC)  

(red) 

DL8  PHOTO 2 contact (NC)  

(red)

DL9  EDGE 1 contact (NC) 

(red)

DL10  EDGE 2 contact (NC) 

(red)

DL11  TCA - automatic closure time enabled  

(red)

DL12  Remotes programming enabled 

(two colors)

DL13  L1 managed by APP 

(blue) 

DL14  Encoder enabled 

(red)

DL15  PROG and RADIO (on MOLEX connector) commands  (green)
B.I.O  Clock command (NO) 

(green)

PED.  Pedestrian command (NO) 

(green)

START  Single impulse command (NO) 

(green)

CLOSE CLOSE command (NO) 

(green)

OPEN  OPEN command (NO) 

(green)  

PROBE

IS NOT AVAILABLE

POINT C - TIMES PROGRAMMING

N.B .:  During the programming the safety functions Coast, Photocells and Stop button 

are active and their performance level is pl “b” according to EN13849-1. their 
intervention stops the programming (the led DL1 from flashing remains lit 
steadily).

N.B .:  If the STOP, PHOT 1, PHOT 2, EDGE 1 and EDGE 2 inputs are not connected, 

make jumpers between COM A +/STOP/PHOT 1/PHOT 2/EDGE 1/EDGE 2 before 
proceeding with programming. N.B .: In this case the safety Edge, Photocells 
and Stop button will be ignored.

N.B .:

  The start slow-down point is automatically determined in the time programming phase 

and 50 ÷ 60 cm is activated before reaching the opening or closing limit switch.

N.B.:  TO REPEAT THE PROGRAMMING REPOSITION THE GATE TO 20 CM FROM THE 

CLOSING LIMIT SWITCH AND FOLLOW THE PROCEDURES BELOW.

1 - N.B .:  POSITION THE GATE TO ABOUT 20 CM FROM THE CLOSING LIMIT SWITCH.

2 - Set DIP 2 to ON => LED DL1 will flash briefly.
3 -  Press the PROG or START or OPEN button or the button of the remote control dedicated 

to the total opening (if previously programmed). The gate will start a series of movements. 
DO NOT PASS IN FRONT OF THE PHOTOCELLS WHILE THE GATE IS MOVING. The 
programming ends when the gate is closed and the DL1 LED is off.

4 - AT THE END OF PROGRAMMING, RESET THE DIP 2 ON OFF.

D - PROGRAMMING OF PEDESTRIAN OPENING TIMES

With closed gate and closing limit switch engaged (mandatory).
1 -  

First set DIP 2 to ON

 (LED DL1 flashes quickly) 

and after DIP1 to ON

 (LED DL1 flashes 

slowly).

2 -  Press the PED pedestrian button. or the remote control button dedicated to the pedestrian 

opening (if previously programmed) => The gate opens.

3 - Press the pedestrian button 

PED.

 to stop the run (thus defining the opening of the gate).

4 - Press the pedestrian button to start closing.
5 - 

When the closing limit switch is reached, reset DIP1 and 2 to OFF.

During programming, the safety devices are active and their intervention stops the 
programming (the LED from blinking remains lit steadily and the buzzer sounds for 10 
seconds).
To repeat the programming position the DIP1 and 2 on OFF, close the gate and repeat the 
procedure described above.

F -  RADIO CODES PROGRAMMING PROCEDURE FOR TOTAL OPENING 

(1000 CODES MAX) - with radio module ACG8069

ATTENTION

: before storing the radio codes, use DIP 14 to select which transmitters to use:

DIP 14 OFF

: SUN-PRO variable code transmitters can be memorized:

SUN-PRO 2CH 2-channel - red keys and white led cod. ACG6210
SUN-PRO 4CH 4-channel - red keys and white led cod. ACG6214
SUN-PROX 2CH 2-channel - red keys and yellow led cod. ACG6220
SUN-PROX 4CH 4-channel - red keys and yellow led cod. ACG6224

DIP 14 ON (default)

: You can store transmitters with fixed code SUN and MOON:

SUN 2CH 2-channel - blue keys and white led cod. ACG6052
SUN 4CH 4-channel - blue keys and white led cod. ACG6054
SUN CLONE 2CH 2-channel - blue keys and yellow led cod. ACG6056
SUN CLONE 4CH 4-channel - blue keys and yellow led cod. ACG6058
MOON 2CH 2-channel - black keys and yellow LED cod. ACG6081
MOON 4CH 4-channel - black keys and yellow LED cod. ACG6082
ATTENTION:  it is not possible to memorize at the same time transmitters with fixed code and 

transmitters with variable code.

Programming can be done only when the gate is stationary.
1 -  First set DIP 1 to ON and then DIP 2 to ON. The LED DL12 flashes red for 10 seconds.
2 -  Press the TRANSMITTER button (usually channel A) within the allotted 10 seconds. If 

the remote is memorized properly LED DL12 blinks green and a buzzer tone confirms 
the correct memorization. The 10 seconds for programming the codes are automatically 
renewed, with LED DL12 which flashes red, in order to store the next transmitter.

3 -  To finish programming, wait 10 seconds, or press the PROG button briefly. LED DL12 

stops flashing.

4 -  Re-set DIP 1 to OFF and DIP 2 to OFF.
5 -  End of procedure.

G

B

Summary of Contents for SUPER 3600

Page 1: ...024 Il corretto funzionamento dell operatore garantito solo se viene gestito da un quadro di comando RIB Le bon fonctionnement de l op rateur n est garanti que s il est g r par un panneau de contr le...

Page 2: ...nni provocati dalla mancata osservanza nell installazione delle norme di sicurezza e delle leggi attualmente in vigore ATTENTION POUR LA SECURITE DES PERSONNES IL EST IMPORTANT DE SUIVRE TOUTES LES IN...

Page 3: ...sed by the non observance during the installation of the safety standards and of the laws in force at present ACHTUNG F R DIE SICHERHEIT DER PERSONEN IST ES WICHTIG DASS ALLE ANWEISUNGEN GENAU AUSGEF...

Page 4: ...quisto di una nuova apparecchiatura di tipo equivalente Presso i distributori di prodotti elettronici con superficie di vendita di almeno 400 m2 inoltre possibile consegnare gratuitamente senza obblig...

Page 5: ...icace chiusura Il motore protetto da una sonda termica che in caso di utilizzo prolungato interrompe momentaneamente il movimento Misure in mm 1 CARATTERISTICHE TECNICHE SUPER 3600 Peso max cancello k...

Page 6: ...RA Persone esperte fuori da area pubblica Persone esperte area pubblica Persone non esperte mantenuto A B non possibile impulsivo in vista es pulsante C o E C o E C e D o E impulsivo non in vista es t...

Page 7: ...zionare a vista i due finecorsa F agendo sui pomoli P Dopo aver verificato il corretto funzionamento elettrico dei due microswitches si perfeziona la loro posizione fino ad ottenere l arresto in apert...

Page 8: ...2 FOTOCELLULA 2 COSTA 1 24Vdc 0 4A 15 24Vdc 0 4A 15 A TEST A AUTOTEST FOTOCELLULE ANTENNA 433 MHz SCHERMATURA CAVO D ANTENNA 700 W MAX CHIUDE APRE COMUNE ALIMENTAZIONE 230Vac 50 Hz CONDENSATORE COLLE...

Page 9: ...A Comune dei contatti Positivo 24 Vdc LIMIT SWITCH Contatti finecorsa che fermano il motore J8 PROBE NON DISPONIBILE J9 ENCODER NON DISPONIBILE J10 Terminazione RS485 di J11 J11 APP Connettore scheda...

Page 10: ...zioni di sicurezza Costa Fotocellule e Pulsante di stop sono attive ed il loro livello di prestazione pl b in accordo a EN13849 1 il loro intervento ferma la programmazione il led DL1 da lampeggiante...

Page 11: ...rocedura G PROGRAMMAZIONE CODICI RADIO PER REL R AUX MAX 1000 CODICI con modulo radio ACG8069 La gestione tramite telecomando attivabile solo con App RIB GATE R AUX funziona normalmente come luce di c...

Page 12: ...o quindi necessario dare un nuovo comando per farlo richiudere Al ciclo successivo la funzione chiusura automatica viene riattivata se abilitata tramite trimmer TCA e led DL11 acceso FUNZIONAMENTO AD...

Page 13: ...re pi facilmente la causa del guasto TABELLA RIASSUNTIVA ALLARMI VISIVI E SONORI SEGNALAZIONI IN FASE DI PROGRAMMAZIONE EVENTO STATO BUZZER STATO LAMPEGGIATORE STATO LED DL1 Dip 1 ON modo uomo present...

Page 14: ...erificare i collegamenti tra quadro elettronico e fotocellule Il cancello non apre e non chiude azionando i vari pulsanti START RADIO OPEN e CLOSE Contatto costa guasto Contatto fotocellule guasto con...

Page 15: ...ori prestazioni degli apparati sopracitati bisogna installare un antenna accordata sulla frequenza del radio ricevitore installato N B Fare molta attenzione che il filo centrale del cavo non vada a co...

Page 16: ...IVE DELLA COSTA VERTIGO Wi Fi 8 cod ACG8042 VERTIGO Wi Fi 10 cod ACG8043 COSTA SENZA FILI cod ACG3016 TRASMETTITORE RADIO RED per costa meccanica o elettrica da alimentare con 3 batterie stilo tipo AA...

Page 17: ...serrure lectrique pour une fermeture efficace Le moteur est prot g par une sonde thermique qui interrompt momentan ment le mouvement en cas de non utilisation prolong e Mesures en mm 1 CARACTERISTIQU...

Page 18: ...DE COMMANDE USAGE DE LA FERMETURE Personne expertes zone sans publique Personne expertes zone avec publique Personnes non expertes homme presente A B Pas possible impulsion en vue ex bouton C ou E C...

Page 19: ...came H en ouverture et en fermeture positionner vue les deux fins de course F en agissant sur les pommeaux P Apr s avoir contr l le fonctionnement lectrique correct des deux microinterrupteurs parfai...

Page 20: ...R 2 2K 1 4W COMMUN COMMUN COMMUN COMMUN CORDON 2 PHOTOCELLULES 2 CORDON 1 A TEST A AUTOTEST PHOTOCELULES ANTENNE 433 MHz ENVELOPPE ANTENNE 24Vdc 0 4A 15 24Vdc 0 4A 15 700 W MAX FERMETURE OUVERTURE CO...

Page 21: ...lules 2 NF EDGE 1 Contact barres palpeuse 1 NF EDGE 2 Contact barres palpeuse 2 NF J7 COM A Commun des contacts Positif 24 Vdc LIMIT SWITCH Contact fin de course qui arr te la fermeture du moteur J8 P...

Page 22: ...ART Commande impulsif vert CLOSE Commande fermeture vert OPEN Commande ouverture vert PROBE PAS DISPONIBLE C PROGRAMMATION DE LA DUR E N B Lors de la programmation les fonctions de s curit Coast Photo...

Page 23: ...ne s obtient que lorsque le portail est stationnaire 1 Positionner le DIP 1 sur ON et ensuite le DIP 3 sur ON 2 La LED DL12 clignote vert 6 fois indiquant la saturation de la m moire 1000 codes pr se...

Page 24: ...lignotant et le buzzer sont activ s avec 2 tons toutes les 5 secondes pendant une minute BOUTON D ARR T COM A STOP Fonction de s curit PL b selon EN13849 1 Pendant le mouvement le bouton d arr t effec...

Page 25: ...circuits externes connect s aux sorties de la centrale doivent tre ex cut s pour garantir l isolation double ou renforc e par rapport aux parties tension dangereuse Toutes les entr es sont g r es par...

Page 26: ...pi ton et R AUX 2 Tonalit s teint Effectue 2 clignotements verts SIGNALISATIONS PENDANT LE FONCTIONNEMENT V NEMENT TAT BUZZER TAT CLIGNOTEUR TAT LED ET SORTIE SIGNAL Bouton d arr t enfonc teint teint...

Page 27: ...ia Bluetooth 4 2 APP8064 Module Wi Fi pour Carte APP pour g rer le tableau de contr le via un r seau Wi Fi local WLAN APP8066 Module RJ45 pour Carte APP pour g rer le tableau de contr le via un r seau...

Page 28: ...e ACG8047 PAIRE DE POTEAUX pour NOVA code ACG8039 DISPOSITIFS Wi Fi MASTER Wi Fi FICHE DE GESTION SYST ME SANS FILS embrochable 12 30V ac dc code ACG6094 avec bornes visser 12 30V ac dc code ACG6099 N...

Page 29: ...D Key selector E Tuned aerial F Flashing lamp H Galvanized column for P E cells I Photo electric cells internal L Safety strip fixed to column M Mecanichal or electrical safety strip with RED transmit...

Page 30: ...to EN 12453 standard COMMAND TYPE USE OF THE SHUTTER Skilled persons out of public area Skilled persons public area Not skilled persons Hold to run operation A B Not possible Impulsive in sight e g pu...

Page 31: ...he two limit switches F by turning knobs P and judging by sight After checking for correct operation of the two microswitches precisely adjust their positions so that the gate will stop in the desired...

Page 32: ...R 2 2K 1 4W COMMON COMMON COMMON COMMON EDGE 2 PHOTOCELL 2 EDGE 1 A TEST A PHOTOCELLS AUTO TEST ANTENNA 433 MHz ANTENNA BRAIDING 24Vdc 0 4A 15 24Vdc 0 4A 15 700 W MAX CLOSE OPEN COMMON POWER SUPPLY 2...

Page 33: ...ls contact 2 NC EDGE 1 Edge 1 contact NC EDGE 2 Edge 2 contact NC J7 COM A Common contacts Positive 24 Vdc LIMIT SWITCH Limit switches that cuts off the motor J8 PROBE IS NOT AVAILABLE J9 ENCODER IS N...

Page 34: ...umpers between COM A STOP PHOT 1 PHOT 2 EDGE 1 EDGE 2 before proceeding with programming N B In this case the safety Edge Photocells and Stop button will be ignored N B The start slow down point is au...

Page 35: ...flashes of LED DL12 and two tones of the buzzer 3 LED DL12 blinks orange again for 10 seconds and you can add new codes as shown above 4 Re Set DIP 1 2 3 to OFF 5 End of procedure RADIO CODES MEMORY...

Page 36: ...ZZER It has the task to signal the intervention of the security the anomalies and the memorization and cancellation of the radio codes SIGNAL 24Vdc GATE OPEN WARNING LIGHT COM A SIGNAL Signals when th...

Page 37: ...econds Dip 1 2 3 transmitter code programming for R AUX relay Off Off Flashes orange for 10 seconds Correct transmitter codes programming for full opening and R AUX relay 1 Tone Off Turns green once C...

Page 38: ...ons between the control panel and the photocells The gate does not open or close by activating the various START RADIO OPEN and CLOSE buttons Faulty safety edge contact Faulty photocells contact with...

Page 39: ...the local network LAN SPARK In order to make the systems mentioned above give the best performances you need to install an antenna tuned on the frequency of the radio receiver installed N B Pay attent...

Page 40: ...SS PHOTOCELLS SUBSTITUTING THE SAFETY STRIP8 VERTIGO Wi Fi 8 code ACG8042 VERTIGO Wi Fi 10 code ACG8043 SAFETY STRIP WITHOUT WIRES code ACG3016 RED RADIO TRANSMITTER for mechanical and electrical safe...

Page 41: ...riegelung kein elektrisches Sicherheitsschloss Der Motor wird durch eine thermische Sonde gesch tzt die im Fall eines langen Einsatzes momentan die Bewegung unterbricht Abmessungen in mm 1 TECHNISCHE...

Page 42: ...ntlichen Bereichs Erfahrene Personen ffentlicher Bereich Nicht fachkundige Personen Gedr ckt halten A B nicht m glich Impulsiv in Sicht z B Wandtaster C oder E C oder E C und D oder E impulsiv au er S...

Page 43: ...schalter F durch Bet tigung der Kn pfe P auf Sicht zu positionieren Nach berpr fung der beiden Mikroschalter auf deren korrekte Funktionsweise Elektrik ist ihre Position genau einzustellen bis der Sto...

Page 44: ...NGSKONTAKT GEMEINSAMER ERDUNGSKONTAKT GEMEINSAMER GEMEINSAMER KONTAKTLEISTE 2 FOTOZELLE 2 KONTAKTLEISTE 1 A TEST A AUTOTEST FOTOZELLEN ANTENNE 433 MHz ANTENNE ZOPFFLECHTEN 24Vdc 0 4A 15 24Vdc 0 4A 15...

Page 45: ...takt 1 NS PHOT 2 Fotozellen Kontakt 2 NS EDGE 1 Ripppen Kontakt 1 NS EDGE 2 Ripppen Kontakt 2 NS J7 COM A Gemeinsame erdungskontakte Positive 24 Vdc LIMIT SWITCH Steckverbinder f r elektrische oder ma...

Page 46: ...VERF GBAR POINT C ZEITPROGRAMMIERUNG N B W hrend der Programmierung sind die Sicherheitsfunktionen Leerlauf Fotozellen und Stopptaste aktiv und ihr Leistungsniveau ist gem EN13849 1 b Ihr Eingriff st...

Page 47: ...1 und DIP 3 auf OFF stellen 4 Ende des Vorgangs H PROGRAMMIERUNG FUNKCODES F R R AUX RELAIS 1000 CODES MAX MIT RADIO MODUL ACG8069 Die Fernsteuerungsverwaltung kann nur mit der RIB GATE App aktiviert...

Page 48: ...r TCA aktiviert wurde und die LED DL11 leuchtet Es muss daher ein erneuter Schlie befehl gegeben werden Beim anschlie enden Bewegungszyklus wird die automatische Schlie funktion wieder aktiviert wenn...

Page 49: ...Spannung garantiert werden kann Alle Eing nge werden von einem programmierten integrierten Schaltkreis der bei jedem Start eines Laufes eine Selbstkontrolle vornimmt verwaltet WARTUNGS BERPR FUNG N B...

Page 50: ...fussg nger ffnung R AUX relais 2 T ne Abgeschaltet Blinkt 2 mal gr n SIGNALISIERUNGEN W HREND DES BETRIEBS EREIGNIS STATUS BUZZER STATUS BLINKLEUCHTE LEDZUSTAND UND AUSGANGSSIGNAL Stopptaste eingedr...

Page 51: ...uerungen hinzuzuf gen APP8064 WLAN Modul f r APP Karte Verwalten des Steuerung ber das lokale Wi Fi Netzwerk WLAN APP8066 RJ45 Modul f r APP Karte Verwalten der Steuerung ber das lokale Netzwerk LAN S...

Page 52: ...ULEN f r NOVA Kode ACG8039 Wi Fi VORRICHTUNGEN MASTER Wi Fi KARTE F R DEN BETRIEB DES SYSTEMS OHNE KABEL mit Verbinder 12 30V ac dc Kode ACG6094 mit Endblockierung 12 30V ac dc Kode ACG6099 NOVA Wi Fi...

Page 53: ...radura el ctrica para un cierre eficaz El motor est protegido por una sonda t rmica que en caso de uso prolongado interrumpe moment neamente el movimiento Medidas en mm 1 CARACTER STICAS T CNICAS SUPE...

Page 54: ...xpertas fuera de un rea p blica Personas expertas rea p blica Personas no expertas mantenido A B non posivel impulsivo a la vista por ejemplo bot n C o E C o E C e D o E impulsivo no a la vista p e ma...

Page 55: ...ovimiento de la camme H ya sea en abertura que en cierre posicionar en vista los dos finales de carrera F operando con los p mulos P Despu s de haber verificado el correcto funcionamiento el ctrico de...

Page 56: ...LED R 2 2K 1 4W COM N COM N COM N COM N BANDA 2 FOTOC LULA 2 BANDA 1 A TEST A AUTOPRUEBA DE FOTOC LULAS ANTENA 433 MHz ARMADURA ANTENA 24Vdc 0 4A 15 24Vdc 0 4A 15 700 W MAX CIERRE ABRE COM N ALIMENTAC...

Page 57: ...as 1 NC PHOT 2 Contacto de las fotoc lulas 2 NC EDGE 1 Contacto banda de seguridad 1 NC EDGE 2 Contacto banda de seguridad 2 NC J7 COM A Com n de los contactos Positivo 24 Vdc LIMIT SWITCH Contactos d...

Page 58: ...pertura NA verde PROBE NO DISPONIBLE C PROGRAMACI N DE LOS TIEMPOS N B Durante la programaci n las funciones de bandas de seguridad fotoc lulas y Stop est n activas y su nivel de rendimiento es pl b s...

Page 59: ...ON 2 El led verde DL10 parpadea 6 veces indicando la condici n de memoria saturada 1000 c digos presentes Sucesivamente el led DL12 permanece activo por 10 segundos permitiendo una posible cancelaci n...

Page 60: ...minuto PULSADOR DE STOP COM A STOP Durante cualquier operaci n el pulsador de STOP ejecuta la detenci n de la cancela Si se presiona con la cancela totalmente abierta o parcialmente utilizando el mand...

Page 61: ...s averiadas En caso que las fotoc lulas no estan conectadas realice el puente entre COM A y PHOTO 1 PHOTO 2 DL9 o DL10 apagado Bandas de seguridad averiados En caso que las bandas de seguridad no esta...

Page 62: ...000 c digos memorizados Apagado Apagado Realiza 6 parpadeos verdes Anulaci n c digos radio de apertura total peatonal y R AUX 2 Tonos Apagado Realiza 2 parpadeos verdes SE ALIZACIONES DURANTE EL FUNCI...

Page 63: ...uetooth 4 2 APP8064 M dulo wi fi para Tarjeta APP para administrar el panel de control a trav s de una red Wi Fi local WLAN APP8066 M dulo RJ45 para Tarjeta APP para administrar el panel de control a...

Page 64: ...es Conforme a la norma EN13849 1 2007 Unido a un cuadro electr nico RIB es un dispositivo de protecci n de Clase 2 c d ACG6202 E S SPARK Para obtener las mejores prestaciones de los citados aparatos e...

Page 65: ...2 Fotozellen FIT SLIM FIT SYNCRO mit Selbstkontrolle 2 fotoc lulas FIT SLIM FIT SYNCRO con autotest 2 fotocellule F97P F97I con autotest 2 photocellules F97P F97I avec autotest 2 photocells F97P F97I...

Page 66: ...UTOTEST est activ e et qu une seule photocellule est connect e un cavalier doit tre cr entre les bornes PHOT 1 et PHOT 2 Si le cavalier n est pas ex cut l autotest choue et le portail ne bouge pas WAR...

Page 67: ...forzo Super CCA1215 Protezione ingranaggio SUPER CCU6207 Cuscinetto 6207 35x72x17 CCU6307 Cuscinetto 6307 35x80x21 CEL1433 Pressacavo CAL1437 Condensatore 50 F 470V CME1034 Albero traino Super CME1063...

Page 68: ...2006 42 CE angewendet wurden Die bereinstimmung mit den genannten harmonisierten Normen sieht die Vermutung der bereinstimmung mit den festgelegten grundlegenden Anforderungen der Richtlinie vor die u...

Reviews: