32

DL5 - photocell contact (NC) (red)
DL6 - gate opening (green)
DL7 - gate closing (red)
DL8 - safety strip contact (NC) (red)
DL9 - Encoder output state
DL10 - radio code programming (green) (only for CRX)

FUSES

F1 T100mA 

Fuse for accessories protection 

F2 T5A 

Fuse for motor windings protection 

RELAYS AND MOTOR CONTROL

K1 => Opening command 
K2 => Closing command
K3 => Flashing light command 
Q5 => TRIAC - Motor command in opening and closing

TORQUE =>TR2 - Electronic regulator for motor torque

Power can be controlled by rotating the TORQUE trimmer – this changes the output voltage 
on motor ends (more power is delivered to the motor by rotating the trimmer clockwise).
Actually, the motor is always turned on at full power regardless the trimmer position (to 
guarantee the starting in all the condition) and, then, after 3seconds, the torque control is 
activated.

LOW SPEED =>TR1 - Electronic regulator for low speed on approach

If DIP9 is turned OFF, the low speed on approach can be controlled by rotating the LOW 
SPEED trimmer. The low speed is activated when the gate is 0.50-0.60 meters away from 
the complete closed or open position.

ELECTRONIC BRAKE 

If DIP 10 is turned ON, the electronic brake will activate upon total opening or closing.

GRADUAL START

If DIP11 is turned ON, a gradual movement will be enabled for 1second upon each starting.
In case of an obstacle is detected by any safety inputs (photocell, safety strip or encoder), the 
gradual start is bypassed for the time being to guarantee a more prompt and safe reaction.

POINT C - MOTOR ROTATION DIRECTION CHECK

This operation is meant to help the installer during the installation and for further future 
controls.
1 -  Unlock the operator with the Manual Release, slide the leaf open about halfway and lock 

the operator again.

2 -  Turn 

DIP1 to ON

 position, LED DL1 starts blinking

3 -  Press and hold the 

PROG.Button

, the gate will open or close. Release the button and 

the gate will stop. Press and hold again, the gate will move in the opposite direction.

  The S1 control board has two movement leds
  - DL6 the GREEN led for OPENING
  - DL7 the RED led for CLOSING
   When you press and hold the PROG.Button, if the gate opens with the green led on then 

you may proceed to step 4.

   If the gate moves in the wrong direction compared with the movement leds:
  - turn OFF the main AC power
  -  reverse the V and W motor cables position (the blue motor cable must be always in the 

U position)

  - reverse the limit switch wires marked LSO and LSC
  - turn ON the main AC power and check again the motor direction

4 -  After 3seconds motor starting and for the next 10 seconds  motor working, 

the torque 

control

 is automatically activated.  Set the motor torque by the TORQUE Trimmer which 

varies the output voltage to the head of the motor (turn clockwise to increase torque).

5 -  After other10 seconds motor working, the 

low speed control

 is automatically activated 

(DIP9 OFF). Set the motor low speed by the LOW SPEED Trimmer to select the gate leaf 
low speed in approaching.

6 -  Press and hold the PROG.Button to close completely the gate. Turn DIP1 to OFF, the RED 

led DL1 will stop blinking.

During Point C procedure, safety devices (photocells and safety strip), stop button and 
encoder input are not active.

 

(#) In  Point D and Point E procedures, all of them will be active, so they must be properly 
installed and connected to the control board. Any changing of the safety devices input state, 
will stop the Point D and Point E procedure that must be repeated from the beginning.

POINT D - PROGRAMMING (#) 

THE DIP7 MUST BE TURNED ON
1 - The gate must be fully closed.
2 -  Turn 

DIP2 to ON

 position, LED DL1 starts blinking

3 - 

Press PROG.Button

, motor opens.

4 -  Once reached the open position, the open limit switch will cut out motor and the gate 

travelling will be stored. The gap of time between now (stop of motor) and the next 
pressing of the PROG.Button (see step 5 below) will be then stored as waiting time for 
Automatic Closing feature.

5 -  

Press PROG.Button

, gate closes and the Automatic Closing time is stored (see DIP3 

function to enable or disable the Automatic Closing feature).

6 -  The LED DL1 will turn OFF, signalling exit from the Point D procedure. 
   Closing  of the gate will be carried out at normal speed and only on approaching total 

closing at low speed (depending on the adjustment of LOW SPEED trimmer).

7 -  When the gate leaf reaches the close limit switch plate, the motor stops.
8 -  

Turn  DIP2 to OFF 

position.

POINT E - PROGRAMMING OF PEDESTRIAN OPENING (#) 

THE DIP7 MUST BE TURNED ON
1 - The gate must be fully closed.
2 - Turn  

DIP2 to ON

 position, the LED DL1 starts blinking quickly

3 -  Immediately, turn also 

DIP1 to ON

 position, the LED DL1 starts blinking slowly

4 - Press the pedestrian pushbutton 

PED.Button

, the gate opens

5 -  When the gate leaf is opened enough for the pedestrian crossing, press the pedestrian 

pushbutton 

PED.Button

 to stop the travel (thus defining the opening stroke of the motor). 

The gap of time between now (stop of the motor) and the next pressing of the PROG.
Button (see step 6 below) will be stored as waiting time for Pedestrian Automatic Closing 
feature.

6 - 

 Press the pedestrian pushbutton PED.Button,

 gate closes and the Pedestrian 

Automatic Closing time is stored (see DIP3 function to enable or disable the Automatic 
Closing feature).

7 - Turn  

DIP1 to OFF

 position

8 - Turn  

DIP2 to OFF

 position

POINT F -  PROGRAMMING RADIO CODES FOR COMPLETE OPENING

(UP TO 62 CODES - ONLY FOR CRX MODELS)

You can only programme the codes if the gate is closed. 
1 -  Position DIP 1 to ON and then DIP 2 to ON.
2 -  The red programming DL1 LED will flash ON and OFF, one second on each, for 10 

seconds. 

3 -  Press the remote control button (normally channel A) within the 10 seconds proscribed. If 

the remote control has been correctly programmed, the DL10 LED (green) will flash once.

4 -  The code programming time resets automatically so that you can programme the next 

remote control. 

5 -  To finish programming, let 10 seconds pass and then press the PROG. button briefly. The 

red DL1 LED will stop flashing. 

6 -  Reposition DIP 1 to OFF and DIP 2 to OFF.
7 -  You have completed the procedure

PROCEDURE FOR DELETING ALL RADIO CODES USED ONLY FOR COMPLETE OPENING 

You can only delete the codes if the gate is closed. 
1 - Position DIP 1 to ON and then DIP 2 to ON.
2 -  The red programming DL1 LED will flash ON and OFF, one second on each, for 10 

seconds. 

3 -  Press and hold the PROG button for 5 seconds. The green DL10 LED will flash twice to 

confirm that the stored codes have been deleted. 

4 -  The red programming DL1 LED remains active and you can programme new codes as 

shown above if required. 

5 -  Reposition DIP 1 to OFF and DIP 2 to OFF.
6 -  You have completed the procedure.

HOW TO CHECK IF THE MEMORY IS FULL FOR RADIO CODES USED ONLY FOR 
COMPLETE OPENING 

You can only check the memory if the gate is closed. 
1 -  Position DIP 1 to ON and then DIP 2 to ON.
2 -  The green DL10 LED will flash 6 times if the memory is full (64 codes have been stored). 
3 -  After this, the DL1 programming LED will remain active for 10 seconds, so that you can 

delete all codes if required. 

4 -  Reposition DIP 1 to OFF and DIP 2 to OFF.
5 -  You have completed the procedure

POINT G -  PROGRAMMING RADIO CODES FOR PEDESTRIAN OPENING

(UP TO 62 CODES - ONLY FOR CRX MODELS)

G

B

Summary of Contents for SUPER 2200

Page 1: ...unctioning in dead man mode when the safety devices are failing According to current European Norms Mit arbeit im mannsbeisein im fall eines ausfalls der Sicherheiten In bereinstimmung mit der aktuell...

Page 2: ...ERVER SOIGNEUSEMENT CES INSTRUCTIONS 1 Si la centrale lectrique ne dispose d aucun interrupteur il faut en installer un de type magn tothermique en amont de cette derni re omnipolaire avec ouverture m...

Page 3: ...THE SAFETY OF THE PEOPLE IT IS IMPORTANT TO FOLLOW ALL THE INSTRUCTIONS INSTALLATIONSVORSCHRIFTEN BEACHTET WERDEN 1 Wenn nicht bereits an der elektrischen Schaltzentrale vorgesehen muss vor der Schal...

Page 4: ...istema respetando las normas y las leyes vigentes SEGUIR TODAS LAS INSTRUCCIONES DE INSTALACI N 1 Este manual de instrucciones est exclusivamente dirigido a personal especializado que conozca los crit...

Page 5: ...ore a chiave E Antenna radio F Lampeggiatore H Colonnina portafotocellula I Fotocellula per protezione interna L Costa meccanica M Costa con sistema RED CARATTERISTICHE TECNICHE SUPER 2200 VENTILATO P...

Page 6: ...econdo la norma EN12453 TIPO DI COMANDO USO DELLA CHIUSURA Persone esperte fuori da area pubblica Persone esperte area pubblica Uso illimitato a uomo presente A B non possibile a impulsi in vista es s...

Page 7: ...REGOLAZIONE FINECORSA Per la regolazione fig 7 sbloccare i dadi G Stabilito il senso di spostamento della camme H sia in apertura che in chiusura posizionare a vista i due finecorsa F agendo sui pomo...

Page 8: ...IUDE APRE COMUNE M LAMPEGGIATORE 230Vac 40W ALIMENTAZIONE 230Vac 50 Hz ANTENNA CALZA ANTENNA FINECORSA APERTURA FINECORSA CHIUSURA COMUNE FOTOCELLULE PEDONALE APRE STOP CHIUDE PASSO PASSO 24Vdc 0 4A 1...

Page 9: ...sclusi al loro funzionamento i seguenti DIP DIP 7 Encoder DIP 9 Rallentamento DIP 10 Freno elettronico DIP 11 Partenza graduale E il trimmer torque regolatore elettronico della forza OFF Normale gesti...

Page 10: ...llo e delle regolazioni dei trimmer rimettere DIP1 in posizione OFF Il led DL1 si spegne segnalando l uscita dal controllo N B Durante questo controllo l Encoder se presente lo stop le fotocellule e l...

Page 11: ...pulsante di apertura n a COM OPEN possibile aprire e mantenere aperta l automazione finch l interruttore viene premuto o l orologio rimane attivo Ad automazione aperta vengono inibite tutte le funzion...

Page 12: ...omatica viene riattivata se selezionata tramite DIP3 FUNZIONAMENTO AD UOMO PRESENTE IN CASO DI GUASTO DELLE SICUREZZE Se la costa guasta o impegnata per pi di 5 secondi o se la fotocellula guasta o im...

Page 13: ...re con encoder DIP n 7 in On abilitato Il cancello apre e chiude solo per brevi tratti Verificare collegamento encoder eventualmente sostituire Azionando i pulsanti K o CHIUDE il cancello non esegue n...

Page 14: ...tura ambiente motore per riscaldamento dello stesso in climi particolarmente freddi fino a 30 C collegare a connettore J6 cod ACG4665 RADIO RICEVITORI AD AUTOAPPRENDIMENTO RX433 A supereterodina con i...

Page 15: ...LOCK Wi Fi SELETTORE A CHIAVE SENZA FILI cod ACG6098 SPARK Wi Fi LAMPEGGIATORE SENZA FILI cod ACG7064 SUPPORTO LATERALE cod ACG7042 TRASMETTITORE RADIO RED per costa meccanica o elettrica da alimentar...

Page 16: ...m4 D Selecteur E Antenne radio F Signal electrique H Poteau zingu p cellule ne I Photocellules p protection interne L Barre palpeuse m canique fix sur pilier M Barre palpeuse avec syst me RED CARACTE...

Page 17: ...installer conform ment la norme EN12453 TYPE DE COMMANDE USAGE DE LA FERMETURE Personne expertes au dehors d une zone publique Personne expertes zone publique Usage illimit homme presente A B non poss...

Page 18: ...DE COURSE Pour proc der au r glage D bloquer les crous G Une fois tabli le sens du mouvement de la came H en ouverture et en fermeture positionner vue les deux fins de course F en agissant sur les pom...

Page 19: ...RE COMMUN M FEU CLIGNOTANT 230Vac 40W ALIMENTATION 230Vac 50 Hz FIN DE COURSE OUVERTURE FIN DE COURSE FERMETURE PIETON OUVRE STOP FERME PAS A PAS 24Vdc 0 4A 15 LED R 2 2K 1 4W COMMUN BARRE PALPEUSE AN...

Page 20: ...euse DIP 13 ON Gestion fonctionnement des moteurs avec t l rupteurs ext rieurs la carte M me s ils sont activ s les DIP suivants sont exclus de leur fonctionnement DIP 7 Encodeur DIP 9 Ralentissement...

Page 21: ...ctronique en agissant sur le potentiom tre DE COUPLE 6 Apr s 10 s cons cutives de travail en ouverture ou en fermeture le ralentissement se d clenche automatiquement si DIP 9 OFF Effectuez le r glage...

Page 22: ...r de nouveau le portail FONCTION HORLOGE DU BOUTON POUSSOIR D OUVERTURE Pour utiliser la FUNCTION HORLOGE demander S1 avec firmware SPECIFIQUE 05 pour FONCTION HOROLOGE ATTENTION UNE HORLOGE CONNECT S...

Page 23: ...un Test Fonctionnel du cordon ex cut avant de chaque fermeture La fermeture du portail est donc permise seulement si la ou les barre s palpeuse s ont pass avec succ s Test Fonctionnel ATTENTION LE MO...

Page 24: ...ail ouvert 3W quivalent 1 ampoule de 3W ou 5 voyant DEL avec r sistance en s rie de 2 2 Kohm Charge maximale la sortie clignotant 40W avec charge r sistive Courant disponible pour photocellules et acc...

Page 25: ...RADIOR CEPTEURS AUTO APPRENDISSAGE RX433 A superh t rodyne embrochable code ACG5055 RX433 A superh t rodyne avec bornes visser code ACG5056 RX433 A 2CH superh t rodyne deux canaux embrochable code ACG...

Page 26: ...BLOCK Wi Fi S LECTEUR CL SANS FILS code ACG6098 SPARK Wi Fi FEU CLIGNOTANT SANS FILS code ACG7064 SUPPORT LATERAL code ACG7042 TRANSMETTEUR RADIO RED pour barre palpeuse m canique ou lectrique alimen...

Page 27: ...ectric cells internal L Safety strip fixed to column M Safety strip with system RED TECHNICAL DATA SUPER 2200 VENTILATED Max leaf weight kg lbs 2200 4846 Operating speed 0 173 m sec 0 57 ft s Rack 4 E...

Page 28: ...ting the EN 12453 standard COMMAND TYPE USE OF THE SHUTTER Skilled persons out of public area Skilled persons public area Unrestricted use with manned operation A B non possibile with visible impulses...

Page 29: ...on of movement of cam H for opening and closing position the two limit switches F by turning knobs P and judging by sight After checking for correct operation of the two microswitches precisely adjust...

Page 30: ...EN COMMON MOTOR CAPACITOR M BLINKER 230Vac 40W POWER SUPPLY 230Vac 50 Hz LIMIT SWITCH OPEN LIMIT SWITCH CLOSE PEDESTRIAN OPEN STOP CLOSE STEP BY STEP 24Vdc 0 4A 15 LED R 2 2K 1 4W COMMON SAFETY STRIP...

Page 31: ...power relays DIP 14 ON DIP 15 ON DIP 16 OFF DIP 17 ON close command after the transit through the photocell ENABLED OFF close command after the transit through the photocell DISABLED DIP 18 ON Working...

Page 32: ...UST BE TURNED ON 1 The gate must be fully closed 2 Turn DIP2 to ON position LED DL1 starts blinking 3 Press PROG Button motor opens 4 Once reached the open position the open limit switch will cut out...

Page 33: ...if for example the Automatic Closing is enabled DIP3 ON or somebody commands the gate closing It is useful during rush hours when traffic is heavy and the flow is slow e g entrance exit of employees...

Page 34: ...remains engaged for more than 5 seconds or if photocell fails or remain engaded for more than 60 seconds the OPEN CLOSE K BUTTON and PEDESTRIAN commands will work only in dead man mode The signal tha...

Page 35: ...with encoder DIP n 7 at ON enabled The gate opens and closes only for brief intervals Check encoder connection and eventually replace By activating the K or CLOSE button the gate does not move Impuls...

Page 36: ...code ACG5452 CODE LEARNIG SYSTEM RADIORECEIVERS RX433 A super eterodyne and coupling code ACG5055 RX433 A super eterodyne and terminal board code ACG5056 RX433 A 2CH super eterodyne 2 channel and cou...

Page 37: ...ode ACG8043 SAFETY STRIP WITHOUT WIRES code ACG3016 BLOCK Wi Fi KEY SELECTOR WITHOUT WIRES code ACG6098 SPARK Wi Fi BLINKER WITHOUT WIRES code ACG7064 LATERAL SUPPORT code ACG7042 RED RADIO TRANSMITTE...

Page 38: ...tenne F Blinkleuchte H Verzinkte Metalls ule als Photozellentrager I Photozelle Torinnenseitig L Sicherheitskontaktleiste auf dem Schiebetor M Sicherheitskontaktleiste mit RED System TECHNISCHE EIGENS...

Page 39: ...mechanischen Anschl ge ber dem Tor vorhanden sein da diese nicht ausreichend sicher sind Komponenten zur Installation nach der Norm EN1253 STEUERUNGSSYSTEM ANWENDUNG DER SCHLIESSUNG Fachpersonen au er...

Page 40: ...er Zahnstange positioniert werden 7 Zur Einstellung sind die Muttern G zu l sen anschlie end sind nach Festlegung der Bewegungsrichtung des Nockens H f r ffnung und Schlie ung die beiden Endschalter F...

Page 41: ...ALLGEMEINE M BLINKER 230Vac 40W SPEISUNG 230Vac 50 Hz ENDSCHALTER FFNUNG ENDSCHALTER SCHLIESSUNG FUSSG NGER FFNE STOP SCHLIESSE SCHRITT BEI SCHRITT 24Vdc 0 4A 15 LED R 2 2K 1 4W ALLGEMEINE RIPPE ANTEN...

Page 42: ...n die folgenden DIP aus ihrer Funktionsweise ausgeschlossen DIP 7 Encoder DIP 9 Verlangsamung DIP 10 Elektronische Bremse DIP 11 Stufenweiser Start sowie der Trimmer TORQUE elektronischer St rkeregler...

Page 43: ...Kupplung durch 6 Nach 10 Sekunden Betriebs bei ffnung und Schlie ung wird automatisch die Verlangsamung ausgel st wenn DIP 9 auf AUS Verlangsamen Sie die Geschwindigkeit durch Bedienen des Trimmers LO...

Page 44: ...f r UHR VERWENDEN WARNUNG EINE UHR AN DEM S1 mit fw 04 oder mehr verbunden UMFASST DIE BEWEGUNG DES FFNUNG TORS OHNE SICHERHEIT AKTIV Diese Funktion ist in Spitzenzeiten n tzlich wenn der Fahrzeugverk...

Page 45: ...TEN A Test A Mit dem Eingang A TEST und DIP 12 auf AN kann k nnen die Kontaktleiste n berwacht werden Das Check besteht aus Funktionstest der Sicherheitskontaktleiste das vor jeder Schliessung ausgef...

Page 46: ...LEDs mit serienm igem Widerstand von 2 2 Kohm Maximale Spannung am Blinkerausgang 40 W mit ohm scher Last Verf gbarer Strom f r Fotozellen und Zusatzsteuereinrichtungen 400mA 24 Vdc Verf gbarer Storm...

Page 47: ...UNKEMPG NGER RX433 A super eterodyne mit Steckkontakt Kode ACG5055 RX433 A super eterodyne mit Klemmbrett Kode ACG5056 RX433 A 2CH super eterodyne 2 Kan le mit Steckkontakt Kode ACG5051 RX433 A 2CH su...

Page 48: ...SCHL SSELSCHALTER OHNE KABEL Kode ACG6098 SPARK Wi Fi BLINKER OHNE KABEL Kode ACG7064 SEITENLAGER Kode ACG7042 RADIO SENDER RED F r mechanische oder elektrische Kontaktleiste Versorgung mit Mignon Ba...

Page 49: ...M dulo 4 D Interruptor de llave E Antena de radio F Intermitente H Columnas para las fotoc lulas I Fotoc lulas internas L Nervadura mec nica M Nervadura con sistema RED CARACTER STICAS T CNICAS SUPER...

Page 50: ...seguros Componentes a instalar seg n la norma EN12453 TYPO DE MANDO USO DEL CIERRE Personas expertas fuera de un rea p blica Personas expertas rea p blica Uso ilimitado en presencia de alguien A B non...

Page 51: ...g 7 desbloquear las tuercas G Una vez establecido el sentido del movimiento de la camme H ya sea en abertura que en cierre posicionar en vista los dos finales de carrera F operando con los p mulos P D...

Page 52: ...CIERRA ABRE COM N M ALIMENTACI N 230Vac 50 Hz INTERMITENTE 230Vac 40W FINAL DE CARRERA ABRE FINAL DE CARRERA CIERRA PEATONAL ABRE STOP CIERRA PASO PASO 24Vdc 0 4A 15 LED R 2 2K 1 4W COM N COSTAS ANTE...

Page 53: ...ernos a la tarjeta Aunque est n habilitados los siguientes DIP quedan sin funcionamiento DIP 7 Encoder DIP 9 Desaceleraci n DIP 10 Freno electr nico DIP 11 Arranque gradual Y el trimmer torque regulad...

Page 54: ...a del control NOTA Durante este control el Encoder si presente el stop las fotoc lulas y las costas no permanecen activos D PROGRAMACI N DE LOS TIEMPOS NOTA EL DIP7 DEBE ESTAR EN ON La programaci n pu...

Page 55: ...al pulsador de apertura n a COM OPEN es posible abrir o mantener abierta la automatizaci n hasta que se presiona el interruptor o mientras que el reloj permanece activo Con la automatizaci n abierta q...

Page 56: ...iclo siguiente la funci n cierre autom tico vuelve a activarse si se la selecciona mediante DIP 3 FUNCIONAMIENTO A HOMBRE PRESENTE EN CASO DE AVER AS CON LOS ACCESORIOS DE SEGURIDAD Si el burlete de s...

Page 57: ...or eventualmente sustit yalo Accionando el pulsador K o CIERRE el port n no ejecuta ning n movimiento Impulso K o CIERRE siempre habilitado Controle y sustituya eventuales pulsadores o micro interrupt...

Page 58: ...CEPTOR CON AUTO APRENDIZAJE RX433 A superheterodina enchufable c d ACG5055 RX433 A superheterodina con regleta de conexi n c d ACG5056 RX433 A 2CH superheterodina bi canal enchufable c d ACG5051 RX433...

Page 59: ...d ACG3016 BLOCK Wi Fi ELECTOR DE LLAVE SIN CABLES c d ACG6098 SPARK Wi Fi INTERMITENTE SIN CABLES c d ACG7064 SOPORTE LATERAL c d ACG7042 TRANSMISOR RADIO RED para costa mec nica o el ctrica Alimenta...

Page 60: ...60...

Page 61: ...61...

Page 62: ...62...

Page 63: ...gr une installation constitu e d autres l ments Aussi rentre t il dans le champ d application de l art 6 paragraphe 2 de la Directive machines 2006 42 CEE et de ses modifications successives Sa mise e...

Page 64: ...22 con foro quadro CME9353 Cappellotto per SUPER2200 ventilato CME9400 Carcassina CMO1181 Statore SUPER 2200 230V 50 60Hz 1P CMO1314 Rotore con albero SUPER 2200 vent CPL1199 Chiave di sblocco CTC110...