902 MHz Wireless Relays Application Manual        B1867

Energy Saving Applications 

RIB with Door/Window Sensor(s) WDWS-EN3

•  RIB activates with closed command from WDWS-EN3 and deactivates with open command.
•  WDWS-EN3 retransmits contact state every 20-30 minutes.
•  Optional modes:  Repeater, Alarm, Delay (see pages 4)

WDWS-EN3 Link Procedure
1.  Charge the WDWS-EN3 per Instructions provided with unit. 
2.  Apply power to RIB. 
3.  Press and hold LRN button on RIB for ½ second. LED will blink slowly.
4.  Press and release Link button on WDWS-EN3 to transmit Teach telegram.
5.  LED on RIB will stay ON for 4 seconds acknowledging telegram reception.
6.  To learn more WDWS-EN3, repeat steps 3-5.

WDWS-EN3

Keycard Switch

PTAC unit with RIBWxxxB-EN3

in Hotel Room Energy Control Mode

RIBWxxxB-EN3 or RIBWxxC-EN3

in Momentary Mode with Keycard Switch

(Wired through J Box)

WKC-EN3

Hotel Room Energy Control 

RIB with 

WDWS-EN3

 

and 

WKC-EN3

Consult factory.

page 6

Load

60Hz A/C Power

DO

BAS Panel

BAS C

on

tr

oller

Wht/Red
Wht/Blu

Yel

Org
Blk

Wht or Red

Tr

ansmitt

er

RIBWxxxB-EN3

or RIBWxxC-EN3

Other Common Applications

Unidirectional Control with a BAS System

In this application the BAS system dry-contact output controls the transmitter and a RIBWxxxB-EN3 or RIBWxxC-EN3 is the receiver.

LRN CLR

Summary of Contents for RIBW***B-EN3 Series

Page 1: ...ception RIBW24B EN3 will not save last state when powered from 24Vdc Each Relay can be Linked to up to 30 transmitters of any combination page 1 902 MHz Model Power Input Vac Contact Rating A Transmis...

Page 2: ...ton for 3 seconds Device Power Dry Contact RIBWxxxB EN3 RIB 1 Device Power RIBWxxxB EN3 or RIBWxxC EN3 RIB 2 Load Bi directional Mode Two RIBWxxxB or one RIBWxxB EN3 and a PHC Gateway Controller Both...

Page 3: ...earning three times quickly 4 LED on RIB will stay ON for 4 seconds indicating telegram reception 5 To learn another switch repeat steps 2 4 Occupancy Detection A Manual ON Auto OFF RIB receiving from...

Page 4: ...y 3 seconds until the LED blinks 1 time 4 Release the LRN and CLR buttons Relay will return to LAST STATE at power up NOTE LAST STATE does not work with RIBW24B EN3 when powered from 24 Vdc Relay Stat...

Page 5: ...FLASH OFF 2 flashes 4 Press and hold LRN button on RIB for 3 seconds until LED pattern changes again to FLASH FLASH FLASH OFF 3 flashes 5 Press and hold the CLR button for 3 seconds until LED blinks t...

Page 6: ...mit Teach telegram 5 LED on RIB will stay ON for 4 seconds acknowledging telegram reception 6 To learn more WDWS EN3 repeat steps 3 5 WDWS EN3 Keycard Switch PTAC unit with RIBWxxxB EN3 in Hotel Room...

Page 7: ...AS System In this application the BAS system dry contact output controls the transmitter on a RIBWxxxB EN3 A second RIBWxxxB EN3 receives the signal and activates it relay A current switch detects cur...

Reviews: