902 MHz Wireless Relays Application Manual

Getting Started

•  Plan where you will mount each receiver and transmitter.
       •  Avoid transmitting along a length of wall, sharp angles and large obstructions.
       •  Avoid mounting inside a metal enclosure.
       •  Typical range is 100’ line of sight.
•  Link devices to each other before installing. See linking instructions (per application) on following pages.
       •  All RIBs must be powered during Link.
•  RIBWxxxB-EN3 is both a transmitter and a receiver. 
•  RIBWxxC-EN3 is only a receiver.
•  Linking a RIB with another RIB puts the pair in Bi-directional mode.
•  PHC Gateway Controller can also link with a RIB and be Bi-directional.
•  Relay state at power-up can be set to ON, OFF or LAST STATE (default).  
    (Exception: RIBW24B-EN3 will not save last state when powered from 24Vdc). 
•  Each Relay can be Linked to up to 30 transmitters of any combination.

page 1

902 MHz Model

Power Input  (Vac)

Contact Rating (A)

Transmission Source       

EEP

RIBW24B-EN3

24 ac/dc

20

Dry-Contact

A5-30-02

RIBW01B-EN3

120

20

Dry-Contact

A5-30-02

RIBW208B-EN3

208

20

Dry-Contact

A5-30-02

RIBW240B-EN3

240

20

Dry-Contact

A5-30-02

RIBW277B-EN3

277

20

Dry-Contact

A5-30-02

RIBW01C-EN3

120

5

NA

A5-30-02

RIBW02C-EN3

208-277

5

NA

A5-30-02

WDWS-EN3

None

NA

Contact Closure

D5-00-01

WWS2-EN3

None

NA

Button Press

F6-02-02

WKC-EN3

None

NA

Insert/Remove Card

F6-04-01

WVSCM-EN3

None

NA

Occupancy Detected

A5-07-01

WVSWM-EN3

None

NA

Occupancy Detected

A5-07-01

Compatible Device from other Manufacturers

PHC Gateway Controller 

EEP  A5-38-08

RIBWxxxB-EN3

RIBWxxC-EN3

WDWS-EN3

WWS2-EN3

LRN CLR

WKC-EN3

Functional Devices, Inc.’s EnOcean

®

 Manufacturer ID is 0x055.

WVSCM-EN3

WVSWM-EN3

Summary of Contents for RIBW***B-EN3 Series

Page 1: ...ception RIBW24B EN3 will not save last state when powered from 24Vdc Each Relay can be Linked to up to 30 transmitters of any combination page 1 902 MHz Model Power Input Vac Contact Rating A Transmis...

Page 2: ...ton for 3 seconds Device Power Dry Contact RIBWxxxB EN3 RIB 1 Device Power RIBWxxxB EN3 or RIBWxxC EN3 RIB 2 Load Bi directional Mode Two RIBWxxxB or one RIBWxxB EN3 and a PHC Gateway Controller Both...

Page 3: ...earning three times quickly 4 LED on RIB will stay ON for 4 seconds indicating telegram reception 5 To learn another switch repeat steps 2 4 Occupancy Detection A Manual ON Auto OFF RIB receiving from...

Page 4: ...y 3 seconds until the LED blinks 1 time 4 Release the LRN and CLR buttons Relay will return to LAST STATE at power up NOTE LAST STATE does not work with RIBW24B EN3 when powered from 24 Vdc Relay Stat...

Page 5: ...FLASH OFF 2 flashes 4 Press and hold LRN button on RIB for 3 seconds until LED pattern changes again to FLASH FLASH FLASH OFF 3 flashes 5 Press and hold the CLR button for 3 seconds until LED blinks t...

Page 6: ...mit Teach telegram 5 LED on RIB will stay ON for 4 seconds acknowledging telegram reception 6 To learn more WDWS EN3 repeat steps 3 5 WDWS EN3 Keycard Switch PTAC unit with RIBWxxxB EN3 in Hotel Room...

Page 7: ...AS System In this application the BAS system dry contact output controls the transmitter on a RIBWxxxB EN3 A second RIBWxxxB EN3 receives the signal and activates it relay A current switch detects cur...