background image

902 MHz Wireless Relays Application Manual        B1867

Occupancy Detection

B.  Auto On:  

RIB and an Occupancy / Vacancy Sensor (WVSWM-EN3  or  WVSCM-EN3)

•  Relay activates when occupancy is detected and deactivates 30 minutes after last detection of occupancy.
•  It may take up to 2 minutes for the RIB to respond to the Occupancy / Vacancy Sensor immediately following Link.
•  Optional modes:  Repeater (see page 4)

Occupancy / Vacancy Sensor Only Learn Procedure
1.  Charge the Occupancy / Vacancy Sensor per instructions.
2.  Apply power to RIB.
3.  Press and hold LRN button on RIB for ½ second. LED will blink slowly.
4.  Trigger a Teach telegram from the Occupancy / Vacancy Sensor by pressing the Menu button once.
5.  LED on RIB will stay ON for 4 seconds acknowledging telegram reception.
6.  Repeat steps 3-5 for additional Occupancy / Vacancy Sensors.

Continued from Page 3

Optional Modes

•  Relay state after power-up can be set to ON, OFF or LAST STATE
•  Relay state after power-up is LAST STATE by default.

Setting Relay State to OFF at Power-up:
1.  While device is not powered, press and hold the LRN button.
2.  Power-up the device.
3.  Wait approximately 3 seconds until the LED blinks 3 times.
4.  Release the LRN button.
Relay will always be OFF at power-up.

Setting Relay State to ON at Power-up:
1.  While device is not powered, press and hold the CLR button.
2.  Power-up the device.
3.  Wait approximately 3 seconds until the LED blinks 2 times.
4.  Release the CLR button.
Relay will always be ON at power-up.

Setting Relay State to LAST STATE at Power-up: (Default Mode) **
1.  While device is not powered, press and hold the LRN and CLR buttons.
2.  Power-up the device.
3.  Wait approximately 3 seconds until the LED blinks 1 time.
4.  Release the LRN and CLR buttons.
Relay will return to LAST STATE at power-up.
 

**NOTE:

 LAST STATE does not work with RIBW24B-EN3 when powered from 24 Vdc.

Relay State

•  Activating Repeater Mode allows relay to repeat signals from other EnOcean devices within range. The relay “hears” the signal and echoes it but will not respond to it unless it  
    has been linked to the transmitting device.
•  Relay will allow a signal to be repeated up to two times. 

Enabling Repeater Mode 
1.  Apply power to RIB.
2.  Press and hold LRN button on RIB for ½ second. LED will flash slowly.
3.  Press and hold the CLR button for 3 seconds until LED blinks 

twice

 indicating 

Repeater Mode is enabled.

Disabling Repeater Mode 
1.  Apply power to RIB.
2.  Press and hold LRN button on RIB for ½ second.  LED will flash slowly.
3.  Press and hold the CLR button for 3 seconds until LED blinks 

three

 times indicating 

Repeater Mode is disabled.

Repeater Mode

Alarm Mode

•  Activating Alarm Mode requires all learned contact switches, such as WDWS-EN3  or RIBWxxxB-EN3, to transmit a CLOSED telegram before relay will activate. Relay will  
    deactivate if any contact switch transmits an OPEN telegram.

Enabling Alarm Mode 
1.  Apply power to RIB.
2.  Press and hold LRN button on RIB for ½ second.  LED will flash slowly.
3.  Press and hold LRN button on RIB for 3 seconds until LED pattern changes to 
FLASH, FLASH, OFF (2 flashes).
4.  Press and hold the CLR button for 3 seconds until LED blinks 

twice

 indicating 

Alarm Mode is enabled.

Disabling Alarm Mode 
1.  Apply power to RIB.
2.  Press and hold LRN button on RIB for ½ second. LED will flash slowly.
3.  Press and hold LRN button on RIB for 3 seconds until LED pattern changes to FLASH, 
FLASH, OFF (2 flashes).
4.  Press and hold the CLR button for 3 seconds until LED blinks 

three

 times indicating 

Alarm Mode is disabled.

page 4

Summary of Contents for RIBW***B-EN3 Series

Page 1: ...ception RIBW24B EN3 will not save last state when powered from 24Vdc Each Relay can be Linked to up to 30 transmitters of any combination page 1 902 MHz Model Power Input Vac Contact Rating A Transmis...

Page 2: ...ton for 3 seconds Device Power Dry Contact RIBWxxxB EN3 RIB 1 Device Power RIBWxxxB EN3 or RIBWxxC EN3 RIB 2 Load Bi directional Mode Two RIBWxxxB or one RIBWxxB EN3 and a PHC Gateway Controller Both...

Page 3: ...earning three times quickly 4 LED on RIB will stay ON for 4 seconds indicating telegram reception 5 To learn another switch repeat steps 2 4 Occupancy Detection A Manual ON Auto OFF RIB receiving from...

Page 4: ...y 3 seconds until the LED blinks 1 time 4 Release the LRN and CLR buttons Relay will return to LAST STATE at power up NOTE LAST STATE does not work with RIBW24B EN3 when powered from 24 Vdc Relay Stat...

Page 5: ...FLASH OFF 2 flashes 4 Press and hold LRN button on RIB for 3 seconds until LED pattern changes again to FLASH FLASH FLASH OFF 3 flashes 5 Press and hold the CLR button for 3 seconds until LED blinks t...

Page 6: ...mit Teach telegram 5 LED on RIB will stay ON for 4 seconds acknowledging telegram reception 6 To learn more WDWS EN3 repeat steps 3 5 WDWS EN3 Keycard Switch PTAC unit with RIBWxxxB EN3 in Hotel Room...

Page 7: ...AS System In this application the BAS system dry contact output controls the transmitter on a RIBWxxxB EN3 A second RIBWxxxB EN3 receives the signal and activates it relay A current switch detects cur...

Reviews: