34

remote is properly memorized LED DL10 (green) blinks.

4 -  The programming time for codes is automatically renewed in order to memorize the next 

remote control.

5 -  To finish programming wait 10 seconds, or press the PROG button briefly. The red LED 

DL1 stops flashing.

6 -  Reset DIP 1 to OFF and DIP 3 to OFF.

  

NOTE: If LED DL1 CONTINUES BLINKING QUICKLY IT MEANS THAT DIP 1 IS STILL SET 

TO ON AND THAT ANY OPERATION IS REFUSED.

7 -  End of procedure.

CANCELLATION PROCEDURE FOR ALL PEDESTRIAN OPENING RADIO CODES

Cancellation can only be performed when the gate is stationary.

1 -  Set DIP 1 to ON and then DIP 3 to ON.

2 -  The red LED DL1 flashes ON for 1 second and OFF for 1 second for 10 seconds.

3 -  Press and hold the PROG button for 5 seconds. Memory cancellation is indicated by two 

flashes of green LED DL10.

4 -  The red LED DL1 remains active and you can add new codes as shown above.

5 -  Reset DIP 1 to OFF and DIP 3 to OFF.

6 -  End of procedure.

INDICATION MEMORY FULL OF PEDESTRIAN OPENING RADIO CODES

Indication only when the gate is stationary.

1 -  Set DIP 1 to ON and then DIP 3 to ON.

2 -  The green LED DL10 flashes 6 times when the memory is full (62 codes).

3 -  The LED DL1 will then remain active for 10 seconds enabling possible cancellation of 

codes.

4 -  Set DIP 1 to OFF and DIP 3 to OFF.

5 -  End of procedure.

CONTROL ACCESSORIES OPERATION

ATTENTION: ONLY IMPULSIVE COMMANDS HAVE TO BE CONNECTED.
Make sure that any other type of command accessories (e.g. mass detectors) 
used on the installation are set in the IMPULSIVE mode, otherwise, the gate will be 
operated even without the protection of the safety devices.

STEP-BY-STEP BUTTON (COM-K BUTTON)

If DIP 6 OFF =>

  It cyclically performs the commands open-stop-close-stop-open etc.

If DIP 6 ON =>

  Opens the gate when closed. There is no effect if activated while opening. 

If activated when gate is open, the gate closes. If activated while closing, 

the gate reopens.

OPEN BUTTON (COM-OPEN)

The button controls the opening movement when the gate is stationary. If activated while 

closing, it reopens the gate.

CLOCK FUNCTION OF OPEN BUTTON

If you want to apply a clock (or more simply a switch) to open and keep open 
the gate, you have to take T2 24V with fw 03 NOUP. 
If fw 03 or higher ATTENTION: IN CASE OF FAILURE OF ONE SAFETY, ONE MINUTE 
AFTER THAT CLOCK OR SWITCH HAVE BEEN ACTIVATED, THE GATE WILL OPEN 
WITHOUT SAFETIES ACTIVE!

This function is useful during peak hours, when vehicle traffic is slow (e.g. entry/exit of 

workers, emergencies in parking or residential areas and, temporarily, for moving operations).

CLOCK FUNCTION APPLICATION

It is necessary to request a T2 24V control panel with firmware 02.

 By connecting a 

switch and/or a daily/weekly clock (instead of or in parallel to the open button N.O. “COM-

OPEN”), you can open and keep the automation open for as long as the switch is pressed 

or the clock remains active. Command functions are inoperative with open automation. 

Releasing the switch or at the preset time, the automation closes immediately.

CLOSE BUTTON (COM-CLOSE)

Controls the closing movement when the gate is stationary.

REMOTE CONTROL

If DIP 6 OFF =>

  It cyclically performs the commands open-stop-close-stop-open etc.

If DIP 6 ON =>

 Opens the gate when closed. There is no effect if activated while opening. 

If activated when gate is open, the gate closes. If activated while closing, the gate reopens.

PEDESTRIAN OPEN BUTTON (COM-PED.BUTT.)

Partial opening and closing control. During pedestrian opening, pausing or closing, you can 

control the opening of any command linked to the T2 24V board.

With DIP 6 you can choose the operation mode of the pedestrian push button.

If DIP 6 OFF =>

  It cyclically performs the commands open-stop-close-stop-open etc.

If DIP 6 ON =>

 Opens the gate when closed. There is no effect if activated while opening. 

If activated when gate is open, the gate closes. If activated while closing, the gate reopens.

 

ELECTRIC LOCK (LOCK)

Set DIP 8 to ON to enable control of the electric lock when opening.

ELECTRIC LOCK PULSE RELEASE IN OPENING

Set DIP 9 to ON to enable the electric lock pulse release when opening (provided DIP 8 is ON).

If a command to open the gate is given when the gate is closed, the closing movement is 

performed for 0.5 seconds and the electric lock is simultaneously activated (followed by a 0.5 

second pause and then the opening of the gate).

ELECTRIC LOCK PULSE ENGAGEMENT

Set DIP 10 to ON to enable the pulse engagement of the electric lock when closing. Upon 

closing, motors are activated for 0.5 seconds at full voltage to ensure lock engagement. 

EASY MOTOR RELEASE

Set DIP 11 to ON to enable easy manual release (provided that DIP 10 is ON), upon closing a 

reverse motion with a fixed time of 0.2 seconds occurs to facilitate manual release.

 

OPERATION OF SAFETY ACCESSORIES

PHOTOCELL (COM-PHOT)

DIP 4 OFF =>  

if an obstacle is placed in range of the photocells when the gate is closed, 

the gate does not open. During operation, photocells work when opening (by 

starting the opening movement only after the obstacle is removed) and closing 

(by starting the reverse movement only after the obstacle is removed).

DIP 4 ON =>  

if an obstacle is placed in range of the photocells when the gate is closed 

and the command to open is given, the gate opens (the photocells do not 

work while opening). Photocells work only during closing (with reverse motion 

restored after a second, even if they are still engaged).

CONTROL OF IMMEDIATE CLOSING AFTER MOVEMENT IN FRONT OF PHOTOCELLS

DIP 16 ON and DIP 4 OFF =>  

if photocells are engaged during opening, the gate stops 

and the gate only closes one second after the photocells 

are disengaged.

DIP 16 ON and DIP 4 ON =>  

if photocells are engaged during opening, the gate continues to 

open. Upon disengagement of the photocells, the gate stops 

and reverses closing motion after a one second pause.

 If total opening is reached (end of opening time), immediate closing is deactivated and 

automatic time closing is activated (if TCA trimmer is activated and LED DL6 is on). If 

during closing there is a rapid movement (e.g. pedestrian) the gate will open again for 

two seconds and then close once again.

DIP 12 OFF =>  

immediate closing after movement in front of the photocells is deactivated.

N.B.:

 Please check photocell operation at least every six months.

EDGE (SAFETY STRIP) (COM-EDGE)

If engaged during opening, reverses the motion when closing.

If engaged when closing, reverses the motion when opening.

If it remains engaged again, it performs a further reversal after 2 seconds, then performs an 

additional short reversal and then gives the sensor failure or engaged alarm (N.O. contact).

If the sensor remains engaged (N.O. contact) no movement is allowed. 

If not used, jump the terminals COM-EDGE.

MONITORING OF SAFETY SENSORS (A+ TEST A-)

Sensors can be monitored through the A+ TEST input and DIP 12 ON.

The monitoring consists of a functional test of the sensor run after every full gate opening.

Closing the gate is therefore permitted only if the sensors have passed the functional test 

after each opening.

CAUTION:

 MONITORING OF THE SENSOR INPUT CAN BE ACTIVATED WITH DIP 12 ON OR 

DEACTIVATED WITH DIP 12 OFF. IN FACT, THE FUNCTIONAL TESTING OF SENSORS IS 

‘POSSIBLE ONLY IF THESE DEVICES HAVE THEIR OWN POWER SUPPLY.

A MECHANICAL SENSOR CAN NOT BE MONITORED, SO DIP 12 SHOULD BE SET TO OFF.

SENSOR AUTOTEST ALARM (DIP 12 ON)

If the sensor fails the monitoring test after opening, an alarm is displayed by the blinker 

lighting up. Gate closure is not allowed in this condition. Normal operation can be restored 

only by repairing the sensor and pressing one of the activated controls.

STOP BUTTON (COM-STOP)

The STOP button stops the gate during any operation.

If held when the gate is fully open (or partially when using the pedestrian control) automatic 

closing is temporarily deactivated (if activated by the TCA trimmer and LED DL6 on). It is 

therefore necessary to use a new command to make it close.

The automatic closing function is reactivated on the next cycle (if activated by the TCA 

trimmer and LED DL6 on).

POWER SENSOR ALARM

The T2 24V control panel has automatic sensors that make the movement of the gate reverse 

in case of impact against objects or persons in accordance with the current EN standards 

G

B

Summary of Contents for AA14031

Page 1: ...ato Patented N 1 503 019 US 7 000 353 B2 Operatore Operateur Operator Torantrieb Operador Alimentazione Alimentation Power Supply Stromspannung Alimentacion Peso max anta Poids maxi battant Max leaf w...

Page 2: ...cati dalla mancata osservanza nell installazione delle norme di sicurezza e delle leggi attualmente in vigore ATTENTION POUR LA SECURITE DES PERSONNES IL EST IMPORTANT DE SUIVRE TOUTES LES INSTRUCTION...

Page 3: ...es caused by the non observance during the installation of the safety standards and of the laws in force at present ACHTUNG F R DIE SICHERHEIT DER PERSONEN IST ES WICHTIG DASS ALLE ANWEISUNGEN GENAU A...

Page 4: ...normas EN 12453 EN 12445 4 El instalador antes de instalar el motor de desplazamiento tiene que controlar que la cancela est en buenas condiciones mec nicas y que se abra y se cierre en forma adecuad...

Page 5: ...za anche il fermo meccanico che interviene durante la chiusura opzionale la corsa massima di traino si riduce di 30 mm 1 5 5 4 4 3 2 1 LAYOUT IMPIANTO I CARATTERISTICHE TECNICHE PRINCE 24V Lunghezza m...

Page 6: ...della norma EN12453 Appendice A E Fotocellule es cod ACG8026 Da applicare ogni 60 70cm per tutta l altezza della colonna del cancello fino ad un massimo di 2 5m EN 12445 punto 7 3 2 1 SBLOCCO DI EMER...

Page 7: ...00 100 765 90 13 5 S3 X A 60 110 100 765 90 14 S3 Y A 80 140 110 765 115 17 S3 X B 100 160 110 765 115 18 S3 X B 120 180 110 765 115 19 5 S3 X B 140 210 110 765 115 21 5 S1 Z B 150 220 120 765 115 23...

Page 8: ...ccarlo serrando la vite da 8mA con una chiave fissa n 13 Per ottenere la chiusura desiderata si dovr spostare il fermo B OPZIONALE bloccandolo come descritto per il fermo A MANUTENZIONE Da effettuare...

Page 9: ...A ANTENNA CHIUDE APRE STOP FUSE T 2 A FOTOCELLULE PASSO PASSO COMUNE COMUNE 24Vdc 0 8A 15 per ACCESSORI 24Vdc 0 8A 15 per AUTOTEST COSTE LAMPEGGIATORE 24Vdc 20W LED R 2 2K 1 4W SERRATURA ELETTRICA PED...

Page 10: ...MPRE DALLA EN12453 IN CASO NON SUSSISTA LA NECESSITA DI OTTEMPERARE ALLA NORMA SOPRA DESCRITTA E SUFFICIENTE POSIZIONARE IL DIP 3 IN OFF IN QUESTO CASO LE ANTE SI FERMERANNO SENZA INVERTIRE IL MOVIMEN...

Page 11: ...ancello 10 A FINE PROGRAMMAZIONE RIMETTERE IL DIP 2 SU OFF D PROGRAMMAZIONE TEMPI PER 1 MOTORE M1 CON SENSORE DI CORRENTE ABILITATO DIP 7 ON ATTENZIONE PER GESTIRE UN SOLO MOTORE IL DIP 13 DEVE ESSERE...

Page 12: ...COMANDO SOLO SE IMPULSIVI Assicurarsi che eventuali altri tipi di accessori di comando per esempio sensori magnetici siano programmati nella modalit IMPULSIVA altrimenti attiverebbero la movimentazion...

Page 13: ...unzionamento del cancello premendo un qualsiasi pulsante di comando FUNZIONAMENTO AD UOMO PRESENTE IN CASO DI GUASTO DELLE SICUREZZE Se la costa guasta o impegnata per pi di 5 secondi o se la fotocell...

Page 14: ...di DL2 e DL4 e che durante la chiusura di M1 e M2 si accendano i led rossi DL3 e DL5 In caso contrario invertire i fili del motore interessato I DIFETTO SOLUZIONE Dopo aver effettuato i vari collegame...

Page 15: ...PIA COLONNINE NOVA cod ACG8039 VERTIGO Wi Fi FOTOCELLULE SENZA FILI SOSTITUTIVE DELLA COSTA VERTIGO Wi Fi 8 cod ACG8042 VERTIGO Wi Fi 10 cod ACG8043 BLOCK Wi Fi SELETTORE A CHIAVE SENZA FILI cod ACG60...

Page 16: ...endant l ouverture Si l on utilise aussi la but e m canique qui intervient pendant la fermeture en option la course maximale d entra nement s courte de 30 mm 1 5 5 4 4 2 CARACTERISTIQUES TECHNIQUES PR...

Page 17: ...appendice A E Cellules photo lectriques code ACG8026 Appliquer chaque 60 70 cm pour toute la taille de la colonne de la porte jusqu un maximum de 2 5 m EN 12445 point 7 3 2 1 MANOEUVRE DE SECOURS Pou...

Page 18: ...00 765 90 13 5 S3 X A 60 110 100 765 90 14 S3 Y A 80 140 110 765 115 17 S3 X B 100 160 110 765 115 18 S3 X B 120 180 110 765 115 19 5 S3 X B 140 210 110 765 115 21 5 S1 Z B 150 220 120 765 115 23 S1 Z...

Page 19: ...acer le collier A et de le bloquer en vissant la vis M8 avec une cl n 13 Pour obtenir la fermeture desir e il est necessarie de deplacer le collier B OPTIONAL et de le bloquer comme indiqu ci dessus E...

Page 20: ...ELLULES PAS A PAS COMMUN COMMUN 24Vdc 0 8A 15 pour ACCESSOIRES 24Vdc 0 8A 15 AUTOTEST pour BARRE PALPEUSE FEU CLIGNOTANT 24Vdc 20W LED R 2 2K 1 4W SERRURE LECTRIQUE PIETON BARRE PALPEUSE ALIMENTATION...

Page 21: ...ISSIBLES RESPECTANT AINSI LES TESTS D IMPACT INDIQUES EGALEMENT PAR LADITE NORME DANS LE CAS OU VOUS NE POURRIEZ PAS RESPECTER LES PRESCRIPTIONS DE LA NORME 12453 POSITIONNER LE DIP 3 SUR OFF DANS CE...

Page 22: ...e portail 10 A LA FIN DE LA PROGRAMMATION REMETTRE LE DIP 2 SUR OFF D PROGRAMMATION DES TEMPS POUR 1 MOTEUR M1 AVEC CAPTEUR DE COURANT ACTIVE DIP 7 ON ATTENTION POUR NE GERER QU UN MOTEUR LE DIP 13 DO...

Page 23: ...quand le portail est ferm S il est actionn pendant le mouvement d ouverture cela ne produit aucun effet S il est actionn lorsque le portail est ouvert il le ferme S il est actionn pendant la fermetur...

Page 24: ...orte quel bouton de commande TRAVAIL AVEC HOMME PRESENT DANS LE CAS DE PANNE DE S CURIT Si le barre palpeuse est en panne ou engag pour plus de 5 secondes ou si la cellule photo lectrique est en panne...

Page 25: ...ts et les donn es techniques des accessoires se conformer aux livrets d instruction correspondants F DEFAUT SOLUTION Apr s avoir effectu les diff rents raccordements et avoir allum le courant toutes l...

Page 26: ...able 12 30V ac dc code ACG6094 avec bornes visser 12 30V ac dc code ACG6099 NOVA Wi Fi PHOTOCELLULES SANS FILS code ACG8037 PAIRE DE POTEAUX NOVA code ACG8039 VERTIGO Wi Fi WIRELESS PHOTOCELLS SUBSTIT...

Page 27: ...ing If the mechanical stopper is used also during the closing optional the maximum stroke is reduced by 30 mm 1 5 5 4 4 3 2 1 TECHNICAL DATA PRINCE 24V Max gate leaf length m 3 Max gate leaf weight kg...

Page 28: ...MANUAL RELEASE This applies only if the unit is not equipped with back up batteries In case of a black out the gate can be pulled open after the operator has been unlocked with the emergency key prov...

Page 29: ...B C D E 110 0 100 100 765 90 13 5 S2 X A 20 100 100 765 90 13 5 S2 Y A 40 100 100 765 90 13 5 S3 X A 60 110 100 765 90 14 S3 Y A 80 140 110 765 115 17 S3 X B 100 160 110 765 115 18 S3 X B 120 180 110...

Page 30: ...A in the needed position by tightening the 8mA screw with a n 13 key To obtain the desired closing limit you must adjust the stopper B OPTIONAL in the needed position and tighten it as for stopper A M...

Page 31: ...LS STEP BY STEP COMMON COMMON 24Vdc 0 8A 15 for ACCESSORY SUPPLY 24Vdc 0 8A 15 for AUTOTEST SAFETY STRIPS BLINKER 24Vdc 20W LED R 2 2K 1 4W ELECTRIC LOCK PEDESTRIAN SAFETY STRIPS POWER SUPPLY 230Vac 5...

Page 32: ...ntrol The slow speed control is performed by adjusting the LOW SPEED TRIMMER which changes the voltage output across the motor s turning it clockwise increases the speed Adjustment is performed to det...

Page 33: ...ical opening stop is reached wait a second then press the PROG button M1 stops and M2 opens 5 When the mechanical opening stop is reached wait 1 second and press the PROG button M2 stops 6 Press the P...

Page 34: ...et DIP 9 to ON to enable the electric lock pulse release when opening provided DIP 8 is ON If a command to open the gate is given when the gate is closed the closing movement is performed for 0 5 seco...

Page 35: ...a closing command the closing of the gate will be carried out with a total delay between the two gate leaves Therefore first the leaf M2 will close completely once it is off M1 will start closing This...

Page 36: ...O TRANSMITTER SUN Wi Fi DEVICES MASTER Wi Fi RECEIVER CARD TO MANAGE WIRELESS SYSTEM with connector 12 30V ac dc code ACG6094 with terminal block 12 30V ac dc code ACG6099 NOVA Wi Fi PHOTOCELLS WITHOU...

Page 37: ...eingebautem mechanischen Anschlag der w hrend der ffnung anspricht Wird auch der optionale mechanische Anschlag benutzt der w hrend des Schlie ens anspricht so reduziert sich der maximale Zughub um 30...

Page 38: ...e und oder andere Sicherheitseinrichtungen muessen mit den Norm EN12453 uebereinstimmen Anhang A E Photozelle wie Kode ACG8026 Jede 60 70 cm f r die ganze H he der Spalte des Gatters bis zu einem Maxi...

Page 39: ...0 13 5 S3 X A 60 110 100 765 90 14 S3 Y A 80 140 110 765 115 17 S3 X B 100 160 110 765 115 18 S3 X B 120 180 110 765 115 19 5 S3 X B 140 210 110 765 115 21 5 S1 Z B 150 220 120 765 115 23 S1 Z B 20 11...

Page 40: ...ungsweite einzustellen gen ngt es die Endschalter A zu verstellen und sie mit Hilfe eines Imbusschl els an der Mutterschraube festzuziehen Um die erw nschte Schliessweite einzustellen m ssen Sie die E...

Page 41: ...LIMPULS GEMEINSAME ERDUNGSKONTAKTE GEMEINSAME ERDUNGSKONTAKTE 24Vdc 0 8A 15 f r ZUBEH RE 24Vdc 0 8A 15 f r AUTOTEST KONTAKTLEISTE BLINKER 24Vdc 20W LED R 2 2K 1 4W ELEKTROSCHLOSS FUSSG NGER KONTAKLEIS...

Page 42: ...LL SCHLIESSEN SICH DIE FL GEL OHNE DIE BEWEGUNG ZU INVERTIEREN TRIMMER RUN TR1 Elektronischer Regler f r hohe Geschwindigkeit Mit diesem Trimmer kann die Motorgeschwindigkeit eingestellt werden Standa...

Page 43: ...EINEM MOTOR MUSS DIP 13 AUF GESTELLT WERDEN ON W HREND DER PROGRAMMIERUNG BLEIBT DER STROMSENSOR IMMER AKTIV Das Tor muss vollst ndig geschlossen sein 1 DIP 2 auf EIN stellen Die LED AnzeigeDL1 begin...

Page 44: ...ie Taste w hrend der ffnungsbewegung gedr ckt Wird die Taste bei offenem Tor gedr ckt so wird das Tor geschlossen dr ckt man sie bei geschlossenem Tor f hrt das zur ffnung FFNUNGS TASTE COM OPEN Bei s...

Page 45: ...tspanne ist eine Stabilisierung der Funktionsweise des Tores durch Dr cken einer beliebigen Befehlstaste m glich ARBEIT IM MANNSBEISEIN IM FALL EINES AUSFALLS DER SICHERHEITEN Wenn die Kontaktleiste i...

Page 46: ...CG4648 OPTIONEN F r die Anschl sse und die technischen Daten der Zubeh re verweisen wir auf die entsprechenden Betriebsanleitungen D FEHLER L SUNG Nachdem die verschiedenen Verbindungen gelegt sind un...

Page 47: ...blockierung 12 30V ac dc Kode ACG6099 NOVA Wi Fi FOTOZELLEN OHNE KABEL Kode ACG8037 EIN PAAR FOTOZELLEN ST NDER NOVA Kode ACG8039 VERTIGO Wi Fi KABELLOSE FOTOZELLE ERSETZT DIE SCHALTLEISTEN VERTIGO Wi...

Page 48: ...i n el seguro mec nico que interviene durante el cierre opcional la carrera m xima de remolque se reduce de 30 mm DISPOSICI N DE LA INSTALACI N 1 5 5 4 4 3 2 1 CARACTER STICAS T CNICAS PRINCE 24V Long...

Page 49: ...s dispositivos que limitan las fuerzas entre limites de las normas EN 12453 Appendix A E Fotoc lulas como c d ACG8026 Da applicare cada 60 70 cm por toda la altura de la puerta hasta un m ximo de 2 5...

Page 50: ...100 765 90 13 5 S3 X A 60 110 100 765 90 14 S3 Y A 80 140 110 765 115 17 S3 X B 100 160 110 765 115 18 S3 X B 120 180 110 765 115 19 5 S3 X B 140 210 110 765 115 21 5 S1 Z B 150 220 120 765 115 23 S1...

Page 51: ...da 8mA con la llave fija n 13 Para obtener el cierre deseado se tendr que mover el seguro B OPCIONAL bloccandolo come descritto per il fermo A MANTENIMIENTO Estas operaciones deben ser efectuadas excl...

Page 52: ...OTOC LULAS PASSO PASSO COM N COM N 24Vdc 0 8A 15 para ACCESSORIOS 24Vdc 0 8A 15 para AUTOTEST COSTAS INTERMITENTE 24Vdc 20W LED R 2 2K 1 4W CERRADURA EL CTRICA PEATONAL COSTAS ALIMENTACION 230Vac 50Hz...

Page 53: ...EN ESTE CASO LAS PUERTAS SE DETENDR N SIN INVERTIR EL MOVIMIENTO TRIMMER RUN TR1 Regulador electr nico de la alta velocidad Con este trimmer es posible regular la velocidad del motor por defecto se co...

Page 54: ...N POSICI N ON DURANTE LA PROGRAMACI N EL SENSOR DE CORRIENTE EST SIEMPRE ACTIVO La cancela debe estar completamente cerrada 1 Coloque el DIP 2 en posici n ON El led DL1 emitir parpadeos breves 2 Presi...

Page 55: ...sores magn ticos est n programados en el modo de IMPULSO de lo contrario pueden activar el movimiento de la puerta sin tener activos los elementos de seguridad PULSADOR DE MANDO PASO PASO COM K BUTTON...

Page 56: ...a de seguridad se estropea o se queda empe ada por mas de 60 segundos los comandos ABRE CIERRE K BUTTON y el PEATONAL funcionar n solo a hombre presente El signal de activaci n de este funcionamiento...

Page 57: ...do OPCIONALES Para las conexiones y datos t cnicos de los accesorios consultar los manuales respectivos E S DEFECTO SOLUCI N Despu s de haber efectuado varias conexiones y haber dado tensi n todos los...

Page 58: ...BLES con enchufe 12 30V ac dc c d ACG6094 con regleta 12 30V ac dc c d ACG6099 NOVA Wi Fi FOTOC LULAS SIN CABLES c d ACG8037 PAR DE COLUMNAS NOVA c d ACG8039 VERTIGO Wi Fi FOTOC LULAS SIN CABLES PARA...

Page 59: ...aphe 2 de la Directive machines 2006 42 CEE et de ses modifications successives Sa mise en service est interdite avant que l installation ait t d clar e conforme aux dispositions pr vues par la Direct...

Page 60: ...ermo meccanico in chiusura PRINCE BA01046 Serie access cilind PRINCE BA01076 Sacch access PRINCE CAL1157 Semiguscio inferiore CAL1158 Semiguscio superiore CCA1263 Gruppo Forcella Perno CCA1351 Piastra...

Reviews: