36
Func.
Name
Description
Range of
Setting
Unit Def50 Note
F116
Function
Display
Selection
0: F000 ~ F134
1: F000 ~ F154
0,1
─
0
F117
PID Start
Range
When the drive at standby status, the level of
PID start.(F103
≠0)
Start level: SV-F117
0.0~10.0 0.1bar 0.3
F118
Selection of
Water
Shortage
Detection
0: Disable
1: Trip (Fb Lo): Press
“RESET” key to reset.
2: Trip (Fb Lo): Power ON again to reset.
3: Trip (Fb Lo): Drive will automatically restart
according to the setting of F122 (Drive
Shutdown Time for Water Shortage)
0~3
─
1
F119
Water
Shortage
Detection by
Pressure
Level
Set the pressure level to detect if pump
suffers from water shortage conditions.
(0: Disable)
0~100%
of
pressure
command
1%
40
F120
Water
Shortage
Detection by
Current
Level
Set the current level to detect if pump suffers
from water shortage conditions.
(0: Disable)
0~100%
of motor
rated
current
1%
0
F121
Time of
Water
Shortage
Detection
Set the detection time for F119 and F120 to
detect if a pump suffers from water shortage.
0~250
1sec
60
F122
Drive
Shutdown
Time for
Water
Shortage
Drive will automatically restart after the time
setting, when a pump suffers from water
shortage and F118 is set to 3.
(0:off)
0~65
1min
5
F124
Proportion
Type of
Pressure
Transducer
0: Direct proportion signal.
1: Inverse proportion signal.
0,1
─
0
F125
Frequency
Command
Selection
under Close-
Loop
Condition
In the close-loop control, select the frequency
command source when the feedback signal
temporarily bypasses.
0: Multi-fuction input terminal or preset speed.
1: Primary speed (F031) or preset speed.
Preset speed(primary speed
、
preset speed
1~7 and jog speed )
0,1
─
1
F126
AI Range
Selection
0: 4~20mA (2~10V)
1: 0~20mA (0~10V)
0,1
─
0
F127
AI Gain
(Analog
Input)
The gain ratio of analog input terminal AI.
0.00~2.00 0.01 1.00
F128
AI Bias
(Analog
Input)
The bias ratio of analog input terminal AI.
-1.00~
1.00
0.01 0.00
F131
Constant
Speed
Detection
Range
Set the bandwidth of constant speed
detection range.
0.0~10.0
0.1Hz 2.0
function can be set during the operation. / Gray words: The setting use default value.