background image

5

Figure 2. Single & Multiple Duct Applications

MULTIPLE DUCT APPLICATION

SINGLE DUCT APPLICATION

SUPPLY AIR

RETURN AIR

Transition

Duct Screws

Duct

Dimples

Figure 3. Return & Supply Air Collars (Optional)

4. Tap collar (if necessary) to ensure engagement with unit 

opening and install second screw.

5. Tighten first screw and rotate collar clockwise so joint is near 

3 o’clock position.

Return Duct

1. Assemble the collar by overlapping the two ends. 

NOTE: One 

end of the collar is slotted and the opposite end has two small 

holes. Position the end with small screw holes underneath 

the slotted end.

2. Fasten the collar ends with two self drilling sheet metal screws.

3. Position the collar over the unit opening. Align the four holes 

in the collar with the four dimples or holes (depending on unit 

model) in the panel.

4. Secure the collar to the rear panel using self drilling screws 

(10-16x.5).

Locating & Installing the Return Air Assembly

To simplify installation, locate and install the return air assembly 

first. If desired, the return opening can be located inside a closet 

with louvered doors that has an open area equal to or greater 

than a 12” x 20” grille. The return air grille can be placed in the 

wall of a closet and the air ducted into the filter box through a 

boxed-in area at the closet floor level (

Figure 4 (page 6)

). 

Verify the filter is readily accessible.
NOTE:
 The return air box with grille and filter should not be 

located in heavy traffic areas like hallways or center of rooms. 

A good spot is in a corner or under a table, if a minimum two 

inch clearance is available.

•  Duct work should be attached directly to the unit flanges for 

horizontal applications.

•  For highly resistive duct systems it may be necessary to add 

an additional return air duct and or supply to achieve maximum 

performance and prevent coil icing and refrigerant flood back.

•  The air conditioning output of the system will not cool 

the home if air is lost to the outside through leaks in the 

duct system. Ducts that are collapsed or restricted by 

foreign objects will also prevent adequate air flow.

•  All duct work passing through unconditioned space must 

be properly insulated to minimize duct losses and prevent 

condensation. Use insulation with an outer vapor barrier. 

Refer to local codes for insulation material requirements.

AIR CONDITIONER INSTALLATION

Unpacking the Unit

It is recommended that the unit be unpacked at the installation 

site to minimize damage due to handling.

 CAUTION:

Do not tip the unit on its side. Oil may enter the 

compressor and cause damage.

1. Remove the bands from around the unit.

2. Unfold the top and bottom cap flanges.

3. Carefully remove the top cap and tube.
Installing Return & Supply Air Collars (Optional)

If the supply and return collars are supplied with the unit, they 

will be located in the supply duct. They can be easily positioned 

over the supply and return ducts (

Figure 3

) and secured with 

sheet metal screws. Return and supply duct opening sizes 

are shown in 

Figure 9 

Table 3, (page 11)

NOTE: Before 

permanently installing the collars, it is recommended you pre-fit 

them over the openings first to determine best fit and alignment.
Supply Duct

1. Position the supply duct collar so the edge of the unit opening 

fits between the flange and the bead.

2. Overlap the collar ends keeping the small screw holes 

underneath.

3. Align the holes in the crimped area and install one screw. 

NOTE: It may be necessary to loosen the four screws that 

hold the transition duct in order to install the supply fitting. 

Re-tighten when installation is complete.

Summary of Contents for WSPM 018J

Page 1: ...mportant role as well Pay attention to all safety warnings and any other special notes highlighted in the manual Improper installation of the furnace or failure to follow safety warnings could result...

Page 2: ...Voltage Connections 7 Cooling Only Thermostat 8 Heat Cool Thermostat 8 Blower Speed ECM Motor 8 START UP ADJUSTMENTS 8 Pre Start Checklist 8 Start Up Procedure 8 Air Circulation 10 System Cooling 10 S...

Page 3: ...ted below must be followed during the installation service and operation of this unit Unqualified individuals should not attempt to interpret these instructions or install this equipment If you do not...

Page 4: ...s Please read all instructions before installing the unit Locating the Air Conditioner Survey the job site to determine the best location for mounting the outdoor unit Select a solid level position pr...

Page 5: ...stive duct systems it may be necessary to add anadditionalreturnairductandorsupplytoachievemaximum performance and prevent coil icing and refrigerant flood back The air conditioning output of the syst...

Page 6: ...ide of the home where the air conditioner is located 1 Locate the center of the heat duct by cutting a small hole in the fiberboard below the duct at the desired location 2 Cut a hole approximately 3...

Page 7: ...tion serious injury death or property damage Beforeservicing disconnectallelectricalpower to the indoor blower When servicing controls label all wires prior to disconnecting Reconnect wires correctly...

Page 8: ...rflow data found in Table 2 page 9 Place appropriate wire on the appropriate motor speed tap for the required airflow 4 Check all factory wiring as shown in the wiring diagram and inspect the connecti...

Page 9: ...27 1104 29 1051 30 992 32 Tap T3 1460 22 1415 22 1385 23 1335 24 1275 25 1225 26 1170 27 1120 28 Tap T4 1502 21 1466 22 1437 22 1388 23 1345 23 1305 24 1251 25 1204 26 Tap T5 1565 20 1525 21 1490 21 1...

Page 10: ...ble filters with the same type and size Do not add additional oil to motors unequipped with oil tubes Thecompressorishermeticallysealedatthefactoryanddoes not require lubrication 3 Set the system mode...

Page 11: ...12 13 1 38 3 2 3 2 5 29 Side View Figure 9 Unit Dimensions A 3 Opening for 12 Diameter Supply Duct 9 15 17 50 9 0 Opening for 14 Diameter Return Duct 10 15 5 5 B 1 3 15 Rear View 3 5 4 5 Ton MODEL NU...

Page 12: ...en cuivre 3 Ne convient pas aux installations de plus de 150 V a la terre FIELD WIRING LEGEND LOW VOLTAGE HIGH VOLTAGE WIRING DIAGRAM Packaged Air Conditioner Single Phase NOTES 1 Disconnect all powe...

Page 13: ...conducteurs en cuivre 3 Ne convient pas aux installations de plus de 150 V a la terre FIELD WIRING LEGEND LOW VOLTAGE HIGH VOLTAGE WIRING DIAGRAM Packaged Air Conditioner Single Phase NOTES 1 Disconne...

Page 14: ...358 150 146 294 137 316 141 338 145 359 150 381 154 148 317 141 338 145 360 149 381 154 404 158 150 317 141 339 145 361 149 382 153 404 158 152 340 145 362 149 383 153 405 157 154 363 149 384 153 406...

Page 15: ...55 146 357 182 378 171 398 162 415 160 148 380 181 401 172 421 164 150 403 181 423 173 152 426 182 154 SUCT PRESS OUTDOOR TEMPERATURE F 70 75 80 85 90 95 100 105 LIQ PRESS DIS TEMP LIQ PRESS DIS TEMP...

Page 16: ...for 4 Ton Units 048J Model INDOOR WET BULB TEMPERATURE F 57 59 61 63 65 67 69 71 73 75 77 OUTDOOR DRY BULB TEMPERATURE F 60 26 6 27 9 29 5 31 5 33 7 36 3 39 2 40 0 40 0 40 0 40 0 65 21 6 22 8 24 3 26...

Page 17: ...20 440 460 480 500 520 540 560 580 600 75 80 85 90 95 100 105 110 115 120 125 130 135 Liquid Pressure psig Liquid Temperature F Remove refrigerant when above curve Add refrigerant when below curve Fig...

Page 18: ...18...

Page 19: ...19...

Page 20: ...ostat been calibrated YES NO Is the thermostat level YES NO Is the heat anticipator setting correct If Applicable YES NO Rated Voltage _________________________________________________________________...

Reviews: