background image

10

3. For the temperature measured, determine the required liquid 

refrigerant pressure from 

Table 4, (page 14)

Table 5, (page 

14)

Table 6, (page 15)

Table 7, (page 15)

Table 8, 

(page  16), 

&

 Table 9, (page 16)

 for 1.5, 2, 2.5, 3, 3.5, & 

4 ton units. For 5 ton units see 

Figure 12 (page 17)

.

•  If the pressure measured in step 1 is greater than the required 

liquid refrigerant pressure determined in step 3, then there 

is too much charge in the system. Remove refrigerant and 

repeat steps 1 through 3 until the system is correctly charged.

•  If the pressure measured in step 1 is less than the required 

liquid refrigerant pressure determined in step 3, then there 

is too little charge in the system. Add refrigerant and repeat 

steps 1 through 3 until the system is correctly charged.

Safety switches

The high-pressure switch is factory-installed and located in the 

liquid line internal to the unit. The switch is designed to protect 

the system when very high pressures occur during abnormal 

conditions. Under normal conditions, the switch is closed. If the 

liquid pressure rises above 650 psig, the switch will open and 

de-energize the unit. The switch will close again when the liquid 

pressure decreases to 460 psig.
NOTE: When the switch opens and then closes, there will be 

a 5 minute short cycling delay before the unit can energize.

AIR CONDITIONER MAINTENANCE

 WARNING:

To prevent electrical shock, personal injury, or 

death, disconnect all electrical power to the unit 

before performing any maintenance or service. 

The unit may have more than one electrical 

supply.

Proper maintenance is important to achieve optimum 

performance from the air conditioner. The ability to properly 

perform maintenance on this equipment requires certain 

mechanical skills and tools. If you do not possess these skills, 

contact your dealer for maintenance. Consult your local dealer 

about the availability of maintenance contracts. 
Routine maintenance should include the following:
•  Inspect and clean or replace air filters at the beginning of each 

heating and cooling season, or more frequently if required.

•  Inspect the condensate drain and outdoor coil at the beginning 

of each cooling season. Remove any debris. Clean the outdoor 

coil and louvers as necessary using a mild detergent and 

water. Rinse thoroughly with water.

•  Inspect the electrical connections for tightness at the beginning 

of each heating and cooling season. Service as necessary.

 CAUTION:

The unit should never be operated without a 

filter in the return air system. Replace disposable 

filters with the same type and size.

•  Do not add additional oil to motors unequipped with oil tubes. 

The compressor is hermetically sealed at the factory and does 

not require lubrication.

3. Set the system mode to ON or COOL.

4. Set the temperature mode below room temperature. Verify 

that the indoor blower, outdoor fan, and compressor energize 

and the cooling function starts.

5. Verify the discharge air grilles are adjusted and the system 

air is balanced.

6. Verify the duct work has no air leaks.

7. Verify the condensate drain is installed correctly and functions 

properly.

8. Set the temperature mode above room temperature. The unit 

should stop.

9. Instruct the homeowner on unit and thermostat operation and 

filter servicing.

Air Circulation

Leave the thermostat system mode on OFF, and set the fan 

mode to ON. Blower should run continuously. Check the air 

delivery at the supply registers and adjust register openings for 

balanced air distribution. Examine ducts for leaks or obstruction 

if insufficient air is detected.
Set the thermostat fan mode to AUTO. The blower should stop 

running.
System Cooling

Set the thermostat’s system mode to COOL and the fan mode 

to AUTO. Lower the thermostat temperature selector below the 

existing room temperature. Allow the cooling system to operate 

for several minutes and check for the discharge of cool air at 

the supply registers.
System Heating

(Available only when Electric heat is supplied) Set the thermostat’s 

system mode to HEAT and the fan mode to either AUTO 

(intermittent air) or to ON (continuous air). Raise the thermostat’s 

temperature selector above the existing room temperature and 

check the following:
1. The compressor and outdoor fan should not run.

2. The blower will run according to the thermostat’s fan mode 

setting.

REFRIGERANT CHARGING

Charging the Unit

(with Outdoor Temperatures Above 65° F)

 CAUTION:

This air conditioner contains liquid and gaseous 

refrigerant under pressure. Adjustment of 

refrigerant charge should only be attempted 

by qualified, trained personnel thoroughly 

familiar with the equipment and safe responsible 

refrigerant handling procedures. Under no 

circumstances should the homeowner attempt 

to install and/or service this equipment. Failure 

to comply with this warning could result in 

equipment damage, personal injury, or death.

NOTE: The refrigerant charge can be checked and adjusted 

through the service ports provided external to the unit. Use 

only gage line sets which have a “Schrader” depression device 

present to actuate the valve.

1.  With the system operating at steady-state, measure the liquid 

refrigerant pressure in psig at the service valve.

2. Measure the liquid refrigerant temperature (° F) at the service 

valve.

Summary of Contents for WSPM 018J

Page 1: ...mportant role as well Pay attention to all safety warnings and any other special notes highlighted in the manual Improper installation of the furnace or failure to follow safety warnings could result...

Page 2: ...Voltage Connections 7 Cooling Only Thermostat 8 Heat Cool Thermostat 8 Blower Speed ECM Motor 8 START UP ADJUSTMENTS 8 Pre Start Checklist 8 Start Up Procedure 8 Air Circulation 10 System Cooling 10 S...

Page 3: ...ted below must be followed during the installation service and operation of this unit Unqualified individuals should not attempt to interpret these instructions or install this equipment If you do not...

Page 4: ...s Please read all instructions before installing the unit Locating the Air Conditioner Survey the job site to determine the best location for mounting the outdoor unit Select a solid level position pr...

Page 5: ...stive duct systems it may be necessary to add anadditionalreturnairductandorsupplytoachievemaximum performance and prevent coil icing and refrigerant flood back The air conditioning output of the syst...

Page 6: ...ide of the home where the air conditioner is located 1 Locate the center of the heat duct by cutting a small hole in the fiberboard below the duct at the desired location 2 Cut a hole approximately 3...

Page 7: ...tion serious injury death or property damage Beforeservicing disconnectallelectricalpower to the indoor blower When servicing controls label all wires prior to disconnecting Reconnect wires correctly...

Page 8: ...rflow data found in Table 2 page 9 Place appropriate wire on the appropriate motor speed tap for the required airflow 4 Check all factory wiring as shown in the wiring diagram and inspect the connecti...

Page 9: ...27 1104 29 1051 30 992 32 Tap T3 1460 22 1415 22 1385 23 1335 24 1275 25 1225 26 1170 27 1120 28 Tap T4 1502 21 1466 22 1437 22 1388 23 1345 23 1305 24 1251 25 1204 26 Tap T5 1565 20 1525 21 1490 21 1...

Page 10: ...ble filters with the same type and size Do not add additional oil to motors unequipped with oil tubes Thecompressorishermeticallysealedatthefactoryanddoes not require lubrication 3 Set the system mode...

Page 11: ...12 13 1 38 3 2 3 2 5 29 Side View Figure 9 Unit Dimensions A 3 Opening for 12 Diameter Supply Duct 9 15 17 50 9 0 Opening for 14 Diameter Return Duct 10 15 5 5 B 1 3 15 Rear View 3 5 4 5 Ton MODEL NU...

Page 12: ...en cuivre 3 Ne convient pas aux installations de plus de 150 V a la terre FIELD WIRING LEGEND LOW VOLTAGE HIGH VOLTAGE WIRING DIAGRAM Packaged Air Conditioner Single Phase NOTES 1 Disconnect all powe...

Page 13: ...conducteurs en cuivre 3 Ne convient pas aux installations de plus de 150 V a la terre FIELD WIRING LEGEND LOW VOLTAGE HIGH VOLTAGE WIRING DIAGRAM Packaged Air Conditioner Single Phase NOTES 1 Disconne...

Page 14: ...358 150 146 294 137 316 141 338 145 359 150 381 154 148 317 141 338 145 360 149 381 154 404 158 150 317 141 339 145 361 149 382 153 404 158 152 340 145 362 149 383 153 405 157 154 363 149 384 153 406...

Page 15: ...55 146 357 182 378 171 398 162 415 160 148 380 181 401 172 421 164 150 403 181 423 173 152 426 182 154 SUCT PRESS OUTDOOR TEMPERATURE F 70 75 80 85 90 95 100 105 LIQ PRESS DIS TEMP LIQ PRESS DIS TEMP...

Page 16: ...for 4 Ton Units 048J Model INDOOR WET BULB TEMPERATURE F 57 59 61 63 65 67 69 71 73 75 77 OUTDOOR DRY BULB TEMPERATURE F 60 26 6 27 9 29 5 31 5 33 7 36 3 39 2 40 0 40 0 40 0 40 0 65 21 6 22 8 24 3 26...

Page 17: ...20 440 460 480 500 520 540 560 580 600 75 80 85 90 95 100 105 110 115 120 125 130 135 Liquid Pressure psig Liquid Temperature F Remove refrigerant when above curve Add refrigerant when below curve Fig...

Page 18: ...18...

Page 19: ...19...

Page 20: ...ostat been calibrated YES NO Is the thermostat level YES NO Is the heat anticipator setting correct If Applicable YES NO Rated Voltage _________________________________________________________________...

Reviews: