Refrigerant Charging Tables
LEGEND
Shaded boxes indicate flooded conditions.
Rated design values. The suction pressure
will vary from design value if outdoor air
flow, entering dry bulb, or entering wet bulb
temperatures vary.
NOTES:
1. All pressures are listed psig and all temperatures in °F
2. Discharge temperatures greater than charted values indicate
an undercharged system.
SUCT.
PRESS.
OUTDOOR TEMPERATURE (° F)
70
75
80
85
90
95
100
105
LIQ.
PRESS.
DIS.
TEMP.
LIQ.
PRESS.
DIS.
TEMP.
LIQ.
PRESS.
DIS.
TEMP.
LIQ.
PRESS.
DIS.
TEMP.
LIQ.
PRESS.
DIS.
TEMP.
LIQ.
PRESS.
DIS.
TEMP.
LIQ.
PRESS.
DIS.
TEMP.
LIQ.
PRESS.
DIS.
TEMP.
134
245
130
136
247
130
267
134
138
250
130
269
134
289
138
140
248
130
272
134
292
138
312
142
142
248
130
271
134
294
138
314
142
335
146
144
271
134
293
138
316
142
336
146
358
150
146
294
137
316
141
338
145
359
150
381
154
148
317
141
338
145
360
149
381
154
404
158
150
317
141
339
145
361
149
382
153
404
158
152
340
145
362
149
383
153
405
157
154
363
149
384
153
406
157
156
386
153
407
157
158
408
157
160
Table 4. Charging Table for 1.5 Ton Units
(018J Model)
Table 5. Charging Table for 2 Ton Units
(024J Model)
SUCT.
PRESS.
OUTDOOR TEMPERATURE (° F)
70
75
80
85
90
95
100
105
LIQ.
PRESS.
DIS.
TEMP.
LIQ.
PRESS.
DIS.
TEMP.
LIQ.
PRESS.
DIS.
TEMP.
LIQ.
PRESS.
DIS.
TEMP.
LIQ.
PRESS.
DIS.
TEMP.
LIQ.
PRESS.
DIS.
TEMP.
LIQ.
PRESS.
DIS.
TEMP.
LIQ.
PRESS.
DIS.
TEMP.
128
130
252
146
132
253
157
275
139
134
255
169
277
149
297
134
136
252
207
279
159
300
143
317
133
333
127
138
253
224
278
186
300
158
321
139
337
134
352
127
140
279
201
302
172
323
149
341
143
356
134
371
128
142
303
186
324
161
344
149
360
140
375
134
389
130
144
326
175
347
158
366
143
379
140
393
135
146
349
168
368
153
387
140
398
141
148
371
163
390
149
409
137
150
392
159
411
146
152
414
155
154