5
General Information
Model
Number
Voltage Phase
Freq
Rated Load
Amperes
(RLA)
Locked Roto r
Amperes
(LRA)
Fan
Motor
Full
Load
Amperes
(FLA )
Minimum
Circuit
Ampacity
Amperes
Maximum
Amperes
Minimum
Amperes
Face
Area
Sq. Ft .
[m
2
]
No.
Rows
CFM
[L/s]
Refrig .
Per
Circuit
(oz. )
[g]
Net
Lbs.
[kg]
Shipping
Lbs. [kg]
Fuse or HACR
Circuit Breaker
Outdoor Coil
Weight
Compressor
ELECTRICAL
PHYSICAL
RA1724AJ2CB
RA1736AJ2CB
RA1748AJ2CB
RA1760AJ2CB
208-230
208-230
208-230
208-230
1
1
1
1
60
60
60
60
11.7/11.7
15.3/15.3
21.2/21.2
28.8/28.8
58.3
83.0
104.0
152.9
16/16
21/21
32/32
42/42
25/25
35/35
50/50
60/60
20/20
25/25
40/40
50/50
19.76 [1.84]
22.23 [2.07]
32.30 [3.00]
32.30 [3.00]
1
1
1
1
5133 [2423]
3540 [1671]
4251 [2006]
5133 [2423]
128 [3629]
151 [4281]
204 [5783]
223 [6322]
160 [72.6]
180 [81.6]
231 [104.8]
241 [109.3]
167 [75.7]
187 [84.8]
238 [108.0]
248 [112.5]
1.40
1.20
5.30
5.30
RA17
GENERAL INFORMATION
Electrical and Physical Data - cont.
UNIT MODEL NUMBER EXPLANATION
A
J 2 C B
R A
TYPE
C - COMMUNICATING
TYPE
2 - TWO STAGE
VOLTAGE
J = 1 PH, 208-230/60
CAPACITY
24 = 24,000 BTU/HR [7.03 kW]
36
= 36,000 BTU/HR [10.55 kW]
48 = 48,000 BTU/HR [14.07 kW]
60 = 60,000 BTU/HR [17.58 kW]
SEER
CONDENSER
BRAND
17 24
MAJOR SERIES
MINOR SERIES
DIMENSIONAL DATA
RA17
24
36
48
60
35 [889]
39 [991]
51 [1295]
51 [1295]
33.75 [857]
33.75 [857]
35.75 [908]
35.75 [908]
33.75 [857]
33.75 [857]
35.75 [908]
35.75 [908]
Height “H” inches [mm]
Length “L” inches [mm]
Width “W” inches [mm]
Summary of Contents for RA17 Series
Page 16: ...16 N R Application not recommended INSTALLATION Table 2 Tubing...
Page 17: ...17 N R Application not recommended INSTALLATION Table 3 Tubing...
Page 54: ...54 R C For Single Phase Models WIRING DIAGRAMS Wiring Diagrams...
Page 55: ...55 WIRING DIAGRAMS Wiring Diagrams...
Page 56: ...56 NOTES...