Diagnostics
SYMPTOM
POSSIBLE CAUSE
REMEDY
Unit will not run
• ower o or loose electrical connection
• Thermostat out of calibration set too high
• Defective control board
• lown fuses tripped brea er
• Transformer defective
• igh-pressure control open
Low-pressure control open
• iswiring of communications communication
light on continuously)
• hec for correct voltage at line voltage connections in
condensing unit.
• eset.
• hec control board diagnostic codes.
• eplace fuses reset brea er.
• hec wiring. eplace transformer.
• eset. Also see high head pressure remedy. The high-
pressure control opens at 610 PSIG.
• hec communication wiring.
Outdoor fan runs,
compressor doesn't
• un or start capacitor defective
• ontactor defective
• oose connection
• ompressor stuc , grounded or open motor
winding, open internal overload.
• ow-voltage condition
• eplace.
• eplace.
• hec for correct voltage at compressor. hec and
tighten all connections.
• ait at least 3 hours for overload to reset. If still open,
replace the compressor.
• Add start it components.
Insu cient cooling
• Improperly si ed unit
• Improper indoor air ow
• Incorrect refrigerant charge
• Air, noncondensibles, or moisture in system
• ad ID
• ecalculate load.
• hec . Should be approximately 400
per ton.
• harge per procedure attached to unit service panel.
• ecover refrigerant. vacuate and recharge. Add lter
drier.
• eplace
Compressor short
cycles
• Incorrect voltage
• Defective overload protector
• efrigerant undercharge
• At compressor terminals, voltage must be 10 of
nameplate marking when unit is operating.
• eplace. hec for correct voltage.
• Add refrigerant.
Registers sweat
• ow indoor air ow
• Increase speed of blower or reduce restriction.
eplace air lter.
High head, low vapor
pressures
• estriction in liquid line, expansion device, or
lter drier
• ad
• emove or replace defective component.
• erify thermistor and pressure transducer connection
and operation.
High head, high
or normal vapor
pressure – Cooling
mode
• Dirty outdoor coil
• efrigerant overcharge
• utdoor fan not running
• Air or noncondensibles in system
• lean coil.
• orrect system charge.
• epair or replace.
• ecover refrigerant. vacuate and recharge.
Low head, high vapor
pressures
•
in bypass mode
• ad compressor
• erify thermistor and pressure transducer connection
and operation.
• eplace compressor.
Low vapor, cool
compressor, iced
indoor coil
• ow indoor air ow
• perating below 65 outdoors
• oisture in system
• losed ID circuit
• Increase speed of blower or reduce restriction.
eplace air lter.
• Add ow Ambient it.
• ecover refrigerant. vacuate and recharge. Add lter
drier.
• epair or replace ID coil
High vapor pressure
• xcessive load
• Defective compressor
• echec load calculation.
• eplace.
Fluctuating head and
vapor pressures
•
hunting
• Air or noncondensibles in system
• hec thermistor to vapor line connection.
• hec air distribution on coil.
• hec suction thermistor and pressure transducer
and operation.
• ecover refrigerant. vacuate and recharge.
• emove and con rm
movement. lean
inside
with nitrogen to remove any debris then reinstall.
Gurgle or pulsing
noise at expansion
device or liquid line
• Air or noncondensibles in system
• ecover refrigerant. vacuate and recharge.
DIAGNOSTICS
General Troubleshooting Chart
WARNING:
Disconnect all power to
unit before servicing. Contactor may break only one
side. Failure to shut off power can cause electrical
shock resulting in personal injury or death.
Summary of Contents for RA17 Series
Page 16: ...16 N R Application not recommended INSTALLATION Table 2 Tubing...
Page 17: ...17 N R Application not recommended INSTALLATION Table 3 Tubing...
Page 54: ...54 R C For Single Phase Models WIRING DIAGRAMS Wiring Diagrams...
Page 55: ...55 WIRING DIAGRAMS Wiring Diagrams...
Page 56: ...56 NOTES...