33
Active Protection – Code 21L
– Open low pressure control
Cooling Mode
s )FTHE,0#OPENSTHREE TIMESDURINGTHESAMECALLFOR
cooling operation, the ICC will lockout the compressor
to keep it from continuing to operate and flash a L” on
the dual 7-segment LEDs followed by a “21”.
IMPORTANT:
This mode of active protection
must be manually reset.
2) High Pressure Control Lockout
s )FTHE(0#OPENSTHREE TIMESDURINGTHESAMECALL
for unit operation, the ICC will lockout the compressor
to keep it from continuing to operate and flash a L” on
the dual 7-segment LEDs followed by a “29”.
IMPORTANT:
This mode of active protection
must be manually reset.
3) Locked Rotor
s 4HE)##WILLDISPLAYAFLASHINGh,vFOLLOWEDBYA
flashing “04” when a locked rotor condition occurs.
Active Protection – Code 29L
– Open high pressure control
IMPORTANT:
This mode of active
protection must be manually reset.
4) Open Start Circuit Lockout
s 4HE)##WILLDISPLAYAFLASHINGh,vFOLLOWEDBYA
flashing “06” when an open start circ
uit condition occurs.
If the ICC detects current in the run circuit without
current present in the start circuit, , the ICC will lockout
the compressor to keep it from continuing to operate
and flash a “L” on the dual 7-segment LEDs followed by
a “06”.
IMPORTANT:
This mode of active protection
must be manually reset.
%XITING!CTIVE#OMPRESSOR0ROTECTION,OCKOUT
Three are three methods to reset the ICC after an active
protection lockout:
#YCLETHELINEVOLTAGETOTHEUNIT
#YCLE6!#TOTHE)##REMOVETHE2OR#
CONNECTIONTOTHE)##
0USHTHE4%34BUTTONDOWNFORONE SECONDAND
release
NOTE:
The ICC will attempt to start the unit when
the TEST button is pressed and released
NOTE:
The preferred method of resetting the
)##ISTOPUSHTHERECALLMODESBUTTONDOWNFORONE
second.
Test Mode (Test Button on the ICC)
s %NTERRECALLMODESBYPRESSINGTHE50BUTTONWITHAN
INSULATEDPROBEFORONE SECONDANDRELEASE
Active Protection – Code 6L – Compressor open start circuit
INSTALLATION
ICC Control Operation
Conventional Thermostat Wiring
Summary of Contents for RA17 Series
Page 16: ...16 N R Application not recommended INSTALLATION Table 2 Tubing...
Page 17: ...17 N R Application not recommended INSTALLATION Table 3 Tubing...
Page 54: ...54 R C For Single Phase Models WIRING DIAGRAMS Wiring Diagrams...
Page 55: ...55 WIRING DIAGRAMS Wiring Diagrams...
Page 56: ...56 NOTES...